6-21
Set point temperature
0˚C
Occurrence read out from the recording chart
When defrosting, the inside temperature
temporarily drops.
Abnormal content and abnormal point
Since the liquid solenoid valve is not closed,
pump-down operation before defrost starts is
not performed, and cooling operation
continues with the evaporator fan stopped.
The normal operation starts 2 min. after
defrosting has been terminated forcibly, but the
evaporator is still cold.