20B7Y1R

Air cooled refrigeration condensing unit

4P360438-1B – 2014.01

Installation manual

18

CAUTION

• Conduct an airtight test and vacuum drying precisely through the 

service ports of both liquid and gas shutoff valves.

• Use charge hoses (provided with a pushing rod each) when using 

the service ports.

8-2 Thermal insulation work

• Be sure to perform thermal insulation of the piping after the airtight 

test and vacuum drying.

• Be sure to perform the thermal insulation of the liquid and gas 

pipes in the connecting piping. Otherwise, water leakage may 
result.

• Be sure to insulate liquid and gas connection piping. Failure to do 

so may result in water leakage. Consult the following chart as a 
general guide when selecting the insulation thickness.

• Liquid pipe arrival minimum temperature 0°C

Gas pipe arrival minimum temperature –45°C

• Reinforce the insulation material for the refrigerant piping 

according to the environment of thermal installation. Otherwise, the 
surface of the insulation material may result in dew condensation.

• If the dew condensation water on the shutoff valves is likely to flow 

to the indoor unit side through the clearance between the insulation 
material and piping because the outdoor unit is installed above the 
indoor unit or for some other reasons, perform appropriate 
treatment such as the caulking of the joints (see the illustrations 
below).

• Attach the cover of the piping outlet with a knock hole opened. If 

there is a feature of small animals intruding through the piping 
outlet, cover the piping outlet with a blocking material (field supply) 
on completion of the steps of 

"10. REFRIGERANT 

REPLENISHMENT" on page 19

 (see the illustrations below).

Use the piping outlet for jobs required during the steps of 

"10. REFRIGERANT REPLENISHMENT" on page 19

 (e.g., a job 

of taking in the charge hose).

Note

• After knocking out the holes, we recommend you remove burrs in 

the knock holes and paint the edges and areas around the edges 
using the repair paint.

• Make sure there is no gap in the Y–joint.

8-3 Checking of device and installation conditions

Be sure to check the followings.

For those doing electrical work

See 

"7-2 Procedure for incoming wiring" on page 14

.

1.

Make sure there is no faulty power wiring or loosing of a nut.
See 

"7-3 Procedure for power supply wiring" on page 14

.

2.

Has the insulation of the main power circuit deteriorated?
Measure the insulation and check the insulation is above regular 
value in accordance with relevant local and national regulations.

For those doing pipe work

1.

Make sure piping size is correct.
See 

"6-1 Selection of piping material" on page 7

.

2.

Make sure insulation work is done. 
See 

"8-2 Thermal insulation work" on page 18

.

3.

Make sure there is no faulty refrigerant piping.
See 

"6. REFRIGERANT PIPING" on page 6

.

9. CHECKS AFTER WORK COMPLETION

• Make sure the following works are complete in accordance with the 

installation manual.

Piping work

Wiring work

Air tight test/vacuum drying

Installation work for indoor unit

Pressure-reducing valve

Nitrogen

Used for refrigerant 
replenishment

Tank

(with siphon)

Meter

Vacuum pump

Valve

Charge 
hose

Gas side shutoff valve

Shutoff valve 
service port

Liquid side 
shutoff valve

Field pipings

Note:

Connection procedure for gauge 
manifold and vacuum pump

R410A

Outdoor unit

To indoor 
unit

Liquid side 
shutoff valve

Gas side 
shutoff valve

Indoor/Outdoor 
interunit piping

Insulation material

Coking, etc.

Piping lead-out 
hole lid

Gas side piping

Liquid side piping

Open a knock 
hole at

Block 

Summary of Contents for LREQ-BY1R

Page 1: ...INSTALLATION MANUAL LREQ15B7Y1R LREQ20B7Y1R Air cooled refrigeration condensing unit ...

Page 2: ...ifikatet C i enlighet med den Tekniska Konstruktionsfilen D som positivt intygats av E Fastsatt modul F G Riskkategori H Se även nästa sida 12 som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C som det fremkommer i den Tekniske Konstruksjonsfilen D og gjennom positiv bedømmelse av E Anvendt modul F G Risikokategori H Se også neste side 13 jotka on esitetty asiakirjassa A...

Page 3: ... bar Минимално максимално допустима температура TS TSmin Минимална температура от страната на ниското налягане L C TSmax Температура на насищане съответстваща на максимално допустимото налягане PS M C Охладител N Настройка на предпазното устройство за налягане P bar Фабричен номер и година на производство вижте табелката на модела 22 Maksimalus leistinas slėgis PS K bar Minimali maksimali leistina...

Page 4: ...n accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire When installing the unit in a small room take measures so that the refrigerant may not exceed the limiting concentration in the event of refrigerant leakage Contact your dealer for further information If the refrigerant leaks and exceeds the limiting concentratio...

Page 5: ...h containing less than 95 kg refrigerant charge CAUTION This unit is already filled with a certain amount of R410A Never open liquid and gas shutoff valve until the step specified in 9 CHECKS AFTER WORK COMPLETION on page 18 The refrigerant R410A requires that strict precautions be observed for keeping the system clean dry and tightly sealed Read the chapter 6 REFRIGERANT PIPING on page 6 carefull...

Page 6: ...mber of indoor units be sure to install them at the same level Use either off cycle defrosting or electric heater defrosting as the defrosting type Hot gas defrosting models cannot be used Make sure the total internal volume of indoor units connected to the condensing units is 80 l or lower Starting from an outdoor temperature of 32 C the total indoor unit capacity needs to be 50 or more of the to...

Page 7: ... for front side no higher than 1500 mm Wall height on the suction side no higher than 500 mm Wall height for sides no limit Make sure each unit is installed level Install the slave unit adjacent to the master unit Make sure the slave unit faces the same direction as the master unit Provide enough space for maintaining and servicing the units Provide adequate space for the air in and outlets Make s...

Page 8: ... See Engineering Data for details 5 If the outdoor units are installed in areas with heavy snowfall the installation of a snowbreak hood is required This is available as an optional accessory If the units are installed in a location where the ambient temperature can drop below 10 C install a windbreak board or a snowbreak hood 1 Snowbreak hood installation Required parts 2 Windbreak board installa...

Page 9: ...When installing on a roof make sure the roof floor is strong enough and be sure to water proof all work Make sure the area around the machine drains properly by setting up drainage grooves around the foundation Drain water is sometimes discharged from the outdoor unit when it is running If the condensing unit is of brine damage resistant or heavy brine damage resistant type use nuts provided with ...

Page 10: ...sed is clean and free of contaminants such as sulphur oxide dust chips oil and fat and water It is desirable that the maximum oil adhesion in the piping is 30 mg per 10 m Use the following type of refrigerant piping Material Seamless phosphorus deoxidized copper tube C1220T O for a maximum outer diameter of 15 9 mm and C1220T 1 2H for a minimum outer diameter of 19 1 mm Refrigerant piping size and...

Page 11: ...or units connected downstream Total capacity of indoor units after branching Liquid pipe size less than 4 0 kW Ø6 4 x 0 8 O type 4 0 kW over and less than 14 0 kW Ø9 5 x 0 8 O type 14 0 kW over and less than 30 0 kW Ø12 7 x 0 8 O type 30 0 kW over and less than 50 0 kW Ø15 9 x 1 0 O type 50 0 kW or over Ø19 1 x 1 0 O type Total capacity of indoor units after branching Gas pipe size Medium temperat...

Page 12: ...mplete Wait until all oil is dripped out 7 Cut the pinched piping off with a pipe cutter just above the brazing point or just above the marking in case there is no brazing point 8 Wait until all oil is dripped out in case the recovery was not complete and only then proceed with connection of the field piping 1 Service port 2 Stop valve 3 Point of pipe cutting just above brazing point or above mark...

Page 13: ... to the valve cover mount and the screw thread of the service port Otherwise dew condensation water will intrude inside and freeze Therefore refrigerant gas leakage or a compressor malfunction may result from the cap deformation or damage 3 Connecting refrigerant piping to outdoor units Use the outdoor unit multi connection piping kit EKHRQZM to split up the gas piping and connect it to the differ...

Page 14: ...onnected at the lateral side bottom CAUTION Only use the dedictated outdoor unit multi connection piping kit EKHRQZM When brazing make sure there are no flammable materials around 1 Connect gas side accessory pipes 1 to field supplied branch pipes Gas side accessory pipes 1 are supplied with the outdoor units 2 Connect gas side accessory pipes 1 to the gas side shutoff valves 1 Gas side accessory ...

Page 15: ...moisture Follow instructions in the dryer instruction manual concerning dryer brazing Repair any burning of dryer paint that occurs during dryer brazing Contact the manufacturer for more information about paint for repair use Flow direction is specified for some type of the dryer Set the flow direction according to the operation manual of the dryer Install the dryer on the main liquid pipe Sight g...

Page 16: ... to install an earth leakage circuit breaker This unit uses an inverter so install the earth leakage circuit breaker that be capable of handling high harmonics in order to prevent malfunctioning of the earth leakage circuit breaker itself Earth leakage circuit breaker which are especially for protecting ground faults should be used in conjunction with main switch or fuse for use with wiring Electr...

Page 17: ...l field supply 7 3 Procedure for power supply wiring Procedure for Power Supply Wiring 1 Power supply 3 phase 50 Hz 380 415 2 Overcurrent circuit breaker earth leakage circuit breaker all pole disconnection switch 3 Earth wire 4 Power supply terminal block 5 Mount insulation sleeves 6 Fix the power supply wiring for phases L1 L2 L3 and N respectively with the provided clamp 1 to the resin clamp 7 ...

Page 18: ...stem on page 13 by all means when connecting the operation output wiring A compressor failure may result if the operating output wiring is not connected Remote switch wiring connections When installing a remote switch clamp as indicated by the following diagram This connection is only required for the master unit X3M wire specifications Wiring connection for low noise mode Wiring connection for lo...

Page 19: ...put operation output wiring from the front 10 When routing remote operating switch wiring from the front 11 Remote switch terminal block X3M 12 When routing remote switch wiring through a wiring opening 13 Separate by at least 50 mm 14 Fixed to the rear side of the support with the provided clamp 2 15 Perform wiring carefully so that the sound insulation of the compressor will not come off 16 Supp...

Page 20: ...unit for one hour and then check that the reading on the vacuum gauge is not rising If the reading on the vacuum gauge is rising water may be remaining in the system or leakage may be occurring In that case perform necessary repair and then conduct the air tightness test again 1The design pressure of the indoor unit locally procured needs to be 2 5 MPa or more Contact the manufacturer in advance f...

Page 21: ... page 19 see the illustrations below Use the piping outlet for jobs required during the steps of 10 REFRIGERANT REPLENISHMENT on page 19 e g a job of taking in the charge hose Note After knocking out the holes we recommend you remove burrs in the knock holes and paint the edges and areas around the edges using the repair paint Make sure there is no gap in the Y joint 8 3 Checking of device and ins...

Page 22: ...operation d Turn off the operation switch of the outdoor unit after the speci fied amount of refrigerant is replenished To prevent liquid compression e Caution Fully open the shutoff valves on the gas and liquid sides promptly Otherwise a piping explosion may result from liquid sealing Label pasting position z 1 Master unit 2 Additional refrigerant charge label 3 Additional refrigerant oil label 4...

Page 23: ...sin ballpoint or another non conducting object Close the inspection door after the work is finished A Inspection hole upper left B Inspection hole upper right 1 Inspection door left 2 Lift to open 3 Operation switch S1S 4 Electric component box cover 5 LED H1P H7P 6 Push button switch BS1 BS5 7 DIP switch DS1 DS2 8 Inspection door right Making field settings Settings are made on the master unit on...

Page 24: ... malfunction code items can be displayed on the condensing unit 1 Make sure that the LED H1P is off If the LED is on press the MODE button BS1 once 2 Press the MODE button BS1 once The LED H1P starts blinking 3 Press the RETURN button BS3 to display the first digit of the malfunction code on the LED 4 Press the SET button BS2 to display the second digit of the malfunction code on the LED 5 Press t...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...4P360438 1B 2014 01 Copyright 2013 Daikin 4P360438 1 B 0000000_ ...

Reviews: