52
FTXM-V Series EDUS042101
3P628775-2A
8
• When piping work is complete, it is necessary to perform a pressure test
and evacuate system with a vacuum pump.
• If using additional refrigerant, purge the air from the refrigerant pipes and
indoor unit using a vacuum pump, then charge additional refrigerant.
•
Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench to the
specified tightening torque.
Compound
pressure gauge
Pressure
meter
High-pressure
valve
Gauge
manifold
Low-pressure
valve
Charging
hoses
Vacuum pump
Service port
Valve caps
Liquid
stop
valve
Gas stop valve
1) Pressurize the liquid pipe and gas pipe from the service ports of each stop valve to 604psi (4.17MPa) (do not pressurize
more than 604psi (4.17MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks,
make repairs and perform the pressure test again.
2) Connect the gauge manifold’s charging hose to the gas stop valve’s service port.
3) Fully open the low-pressure valve (Lo) on the gauge manifold and fully close the high-pressure valve (Hi).
(High-pressure valve will require no further operation.)
4) Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.
5) Close the low-pressure valve (Lo) on the gauge manifold and stop vacuum pumping.
(Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing
back.)*
1
6)
Remove the valve caps from the liquid stop valve and gas stop valve.
7) To open the liquid stop valve, turn the rod of the valve 90° counter-clockwise using a hexagonal wrench.
Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from the indoor unit’s flare and outdoor unit’s flare and valve rods.
After the check is complete, wipe all soapy water off.*
2
8)
Disconnect the charging hoses from the service port for the gas stop valve, then fully open the liquid and gas stop valves.
(Do not attempt to turn the valve rods further than they can go.)
9) Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specified
torques.
Refer to
“4. Refrigerant piping” on page 6 for details.
*
1
If the compound pressure gauge pointer swings back, the refrigerant may have water content or there may be a loose
pipe joint.
Check all pipe joints and retighten nuts as needed, then repeat steps 3) through 5).
*
2
Under no circumstances shall potential sources of ignition be used in the searching for or detection of
refrigerant leaks.
A halide torch (or any other detector using a naked flame) shall not be used.
Do not use substances containing chlorine and electronic leak detection for gas leak detection.
Summary of Contents for INVERTER FTXM-V Series
Page 1: ...Heat Pump Split Type Air Conditioners FTXM V Series EDUS042101...
Page 2: ......
Page 10: ...8 FTXM V Series EDUS042101 C 3D129694 FTXM24VVJU...
Page 11: ...FTXM V Series EDUS042101 9 3D123362 RXM18VVJU 3D131944B RXM09 12VVJU 4 2 Outdoor Unit...
Page 12: ...10 FTXM V Series EDUS042101 3D107983A RXM24VVJU...
Page 14: ...12 FTXM V Series EDUS042101 C 3D129644B RXM18 24VVJU C 3D129643B RXM09 12VVJU 5 2 Outdoor Unit...
Page 16: ...14 FTXM V Series EDUS042101 3D132216 RXM18VVJU 3D131979 RXM09 12VVJU 6 2 Outdoor Unit...
Page 17: ...FTXM V Series EDUS042101 15 3D132217 RXM24VVJU...
Page 28: ...26 FTXM V Series EDUS042101 3D133582A 8 Operation Limit...
Page 30: ...28 FTXM V Series EDUS042101 C 3D133575 FTXM12VVJU C 3D133574 FTXM09VVJU 9 2 Indoor Unit...
Page 31: ...FTXM V Series EDUS042101 29 C 3D133577 FTXM24VVJU C 3D133576 FTXM18VVJU...
Page 32: ...30 FTXM V Series EDUS042101 C 3D133581 RXM12VVJU C 3D133580 RXM09VVJU 9 3 Outdoor Unit...
Page 33: ...FTXM V Series EDUS042101 31 C 3D133618 RXM24VVJU C 3D133617 RXM18VVJU...
Page 117: ...FTXM V Series EDUS042101 115 C 3P628774 1 Quick Reference...
Page 149: ...FTXM V Series EDUS042101 147 1P124687 1A...
Page 150: ...148 FTXM V Series EDUS042101 1P124687 1A...
Page 151: ...FTXM V Series EDUS042101 149 1P124687 1A...
Page 152: ...150 FTXM V Series EDUS042101 1P124687 1A...
Page 156: ...154 FTXM V Series EDUS042101 3P124623 1E 4 Fig 6 Fig 5 Fig 8 Fig 7...
Page 167: ...FTXM V Series EDUS042101 165 3P124623 1E 15...
Page 177: ...FTXM V Series EDUS042101 175 3P124623 1E 25 Fig 9 Fig 12 Fig 10 Fig 11...
Page 178: ...176 FTXM V Series EDUS042101 3P124623 1E 26 Fig 14 Fig 13 Fig 16 Fig 15...
Page 180: ...178 FTXM V Series EDUS042101 1P126474 1B...
Page 181: ...FTXM V Series EDUS042101 179 1P126474 1B...
Page 182: ...180 FTXM V Series EDUS042101 1P126474 1B...
Page 183: ...FTXM V Series EDUS042101 181 1P126474 1B...
Page 188: ...186 FTXM V Series EDUS042101 3P162015 1A...
Page 189: ...FTXM V Series EDUS042101 187 3P162015 1A...
Page 190: ...188 FTXM V Series EDUS042101 3P162015 1A...
Page 191: ...FTXM V Series EDUS042101 189 3P162015 1A...
Page 207: ...FTXM V Series EDUS042101 205 3P534932 1D 13 14 KPW063B4 Air Direction Adjustment Grille...
Page 208: ...206 FTXM V Series EDUS042101 3P534932 1D...
Page 209: ...FTXM V Series EDUS042101 207 2P403095 1 13 15 KKG063A42 Back Protection Wire Net...
Page 229: ...FTXM V Series EDUS042101 227 3P436071 1 13 21 KPS063A41 Snow Hood Intake Side Plate...
Page 230: ...228 FTXM V Series EDUS042101 3P436071 1...
Page 231: ...FTXM V Series EDUS042101 229 3P436072 1 13 22 KPS063A44 Snow Hood Intake Rear Plate...
Page 232: ...230 FTXM V Series EDUS042101 3P436072 1...
Page 233: ...FTXM V Series EDUS042101 231 3P436073 1 13 23 KPS063A47 Snow Hood Outlet...
Page 234: ...232 FTXM V Series EDUS042101 3P436073 1...
Page 235: ......