FTXM-V Series EDUS042101
41
3P628775-1
9
Refrigerant Piping Work
WARNING
• Do not apply mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the service life of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with this unit.
• Never install a dryer to this R32 unit in order to guarantee its service life.
• The drying material may dissolve and damage the system.
• Improper flaring may result in refrigerant gas leakage.
1.
Flaring the pipe end
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward,
so that the filings do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring has been done correctly.
2.
Refrigerant piping
CAUTION
• Use the flare nut fixed to the main unit. (This is to prevent the flare nut from cracking as a result of deterioration over time.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32 or R410A.)
• Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
• Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand, then tighten them fully with a spanner and a torque wrench.
Caution on piping handling
• Protect the open end of the pipe against dust and moisture.
• All pipe bends should be as gentle as possible. Use a pipe bender for bending.
Selection of copper and heat insulation materials
When using commercial copper pipes and fittings, observe the following:
• Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F (0.035 to 0.045kcal/mh°C))
Be sure to use insulation that is designed for use with HVAC Systems.
• ACR Copper only.
• Be sure to insulate both the gas and liquid piping and observe the insulation dimensions as
below.
• Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
• Using finishing tape, bundle and wrap the indoor unit piping and drain hose together so that the drain hose is below the other piping.
Piping size
Minimum bend radius
Piping thickness
Thermal insulation size
Thermal insulation thickness
Gas side
O.D. 3/8 inch
(9.5mm)
1-3/16 inch (30mm)
or more
0.031 inch (0.8mm)
(C1220T-O)
I.D. 15/32-19/32 inch
(12-15mm)
13/32 inch
(10mm) Min.
O.D. 1/2 inch
(12.7mm)
1-9/16 inch (40mm)
or more
0.031 inch (0.8mm)
(C1220T-O)
I.D. 9/16-5/8 inch
(14-16mm)
O.D. 5/8 inch
(15.9mm)
1-15/16 inch (50mm)
or more
0.039 inch (1.0mm)
(C1220T-O)
I.D. 5/8-13/16 inch
(16-20mm)
Liquid side
O.D. 1/4 inch
(6.4mm)
1-3/16 inch (30mm)
or more
0.031 inch (0.8mm)
(C1220T-O)
I.D. 5/16-13/32 inch
(8-10mm)
A
A
Flaring
Set exactly at the position shown below.
Die
0-0.020 inch
(0-0.5mm)
Clutch-type
Flare tool for
R32 or R410A
0.039-0.059 inch
(1.0-1.5mm)
Clutch-type
(Rigid-type)
0.059-0.079 inch
(1.5-2.0mm)
Wing-nut type
(Imperial-type)
Conventional flare tool
The flare’s inner surface must be
flaw-free.
When flaring, do not over-tighten
and crack.
The pipe end must be evenly flared
in a perfect circle.
Make sure that the flare nut is fitted.
Check
Cut exactly at
right angles.
Remove burrs.
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration
oil only to the inner
surface of the flare.
Do not apply refrigeration
oil to the flare nut to avoid
tightening with excessive
torque.
Apply oil
Torque wrench
Piping union
Flare nut
Spanner
Tighten
Piping size
O.D. 5/8 inch
(15.9mm)
Gas side
Liquid side
O.D. 1/4 inch
(6.4mm)
Flare nut tightening
torque
45-5/8–55-5/8lbf • ft
(61.8-75.4N • m)
O.D. 1/2 inch
(12.7mm)
36-1/2–44-1/2lbf • ft
(49.5-60.3N • m)
O.D. 3/8 inch
(9.5mm)
24-1/8–29-1/2lbf • ft
(32.7-39.9N • m)
10-1/2–12-3/4lbf • ft
(14.2-17.2N • m)
Wall
If no flare cap is
available, cover the
flare mouth with
tape to keep dirt
and water out.
Rain
Be sure to
place a cap.
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Summary of Contents for INVERTER FTXM-V Series
Page 1: ...Heat Pump Split Type Air Conditioners FTXM V Series EDUS042101...
Page 2: ......
Page 10: ...8 FTXM V Series EDUS042101 C 3D129694 FTXM24VVJU...
Page 11: ...FTXM V Series EDUS042101 9 3D123362 RXM18VVJU 3D131944B RXM09 12VVJU 4 2 Outdoor Unit...
Page 12: ...10 FTXM V Series EDUS042101 3D107983A RXM24VVJU...
Page 14: ...12 FTXM V Series EDUS042101 C 3D129644B RXM18 24VVJU C 3D129643B RXM09 12VVJU 5 2 Outdoor Unit...
Page 16: ...14 FTXM V Series EDUS042101 3D132216 RXM18VVJU 3D131979 RXM09 12VVJU 6 2 Outdoor Unit...
Page 17: ...FTXM V Series EDUS042101 15 3D132217 RXM24VVJU...
Page 28: ...26 FTXM V Series EDUS042101 3D133582A 8 Operation Limit...
Page 30: ...28 FTXM V Series EDUS042101 C 3D133575 FTXM12VVJU C 3D133574 FTXM09VVJU 9 2 Indoor Unit...
Page 31: ...FTXM V Series EDUS042101 29 C 3D133577 FTXM24VVJU C 3D133576 FTXM18VVJU...
Page 32: ...30 FTXM V Series EDUS042101 C 3D133581 RXM12VVJU C 3D133580 RXM09VVJU 9 3 Outdoor Unit...
Page 33: ...FTXM V Series EDUS042101 31 C 3D133618 RXM24VVJU C 3D133617 RXM18VVJU...
Page 117: ...FTXM V Series EDUS042101 115 C 3P628774 1 Quick Reference...
Page 149: ...FTXM V Series EDUS042101 147 1P124687 1A...
Page 150: ...148 FTXM V Series EDUS042101 1P124687 1A...
Page 151: ...FTXM V Series EDUS042101 149 1P124687 1A...
Page 152: ...150 FTXM V Series EDUS042101 1P124687 1A...
Page 156: ...154 FTXM V Series EDUS042101 3P124623 1E 4 Fig 6 Fig 5 Fig 8 Fig 7...
Page 167: ...FTXM V Series EDUS042101 165 3P124623 1E 15...
Page 177: ...FTXM V Series EDUS042101 175 3P124623 1E 25 Fig 9 Fig 12 Fig 10 Fig 11...
Page 178: ...176 FTXM V Series EDUS042101 3P124623 1E 26 Fig 14 Fig 13 Fig 16 Fig 15...
Page 180: ...178 FTXM V Series EDUS042101 1P126474 1B...
Page 181: ...FTXM V Series EDUS042101 179 1P126474 1B...
Page 182: ...180 FTXM V Series EDUS042101 1P126474 1B...
Page 183: ...FTXM V Series EDUS042101 181 1P126474 1B...
Page 188: ...186 FTXM V Series EDUS042101 3P162015 1A...
Page 189: ...FTXM V Series EDUS042101 187 3P162015 1A...
Page 190: ...188 FTXM V Series EDUS042101 3P162015 1A...
Page 191: ...FTXM V Series EDUS042101 189 3P162015 1A...
Page 207: ...FTXM V Series EDUS042101 205 3P534932 1D 13 14 KPW063B4 Air Direction Adjustment Grille...
Page 208: ...206 FTXM V Series EDUS042101 3P534932 1D...
Page 209: ...FTXM V Series EDUS042101 207 2P403095 1 13 15 KKG063A42 Back Protection Wire Net...
Page 229: ...FTXM V Series EDUS042101 227 3P436071 1 13 21 KPS063A41 Snow Hood Intake Side Plate...
Page 230: ...228 FTXM V Series EDUS042101 3P436071 1...
Page 231: ...FTXM V Series EDUS042101 229 3P436072 1 13 22 KPS063A44 Snow Hood Intake Rear Plate...
Page 232: ...230 FTXM V Series EDUS042101 3P436072 1...
Page 233: ...FTXM V Series EDUS042101 231 3P436073 1 13 23 KPS063A47 Snow Hood Outlet...
Page 234: ...232 FTXM V Series EDUS042101 3P436073 1...
Page 235: ......