IM 796
Installation Guidelines
Installation Diagram
Installation of Outdoor Unit
Outdoor Unit Clearances
Install the outdoor unit in a manner to prevent mixing hot
discharged air with return air flow. Also the unit should be a
suitable distance from obstructions
See Figure 1
for installa-
tion clearances. Double the dimensions shown if surround-
ings are more than 72" tall, or if there is an obstruction on
top. Select the coolest possible place where intake air tem-
perature is not greater than the outside air temperature (maxi-
mum 113°F).
Figure 1. Outdoor Unit Minimum Clearances
Installation of the Indoor Unit
Indoor Unit Clearances
The indoor unit must be installed in a manner to prevent mixing
the cool discharged air with the hot return air. Please follow the
installation clearances shown in
Figure 2.
Do not place the
indoor unit in direct sunlight. The location must be suitable for
piping and drainage, and be away from doors or windows.
Figure 2
.
Indoor Unit Minimum Clearances
Piping
The refrigerant piping can enter the indoor unit at several dif-
ferent locations. Use the knock outs provided in the room
cabinet.
See Figure 3
.
Figure 3. Indoor Unit
Bend the pipes carefully to prevent kinks and restrictions. It’s
best to use a tube bender. The condensation drain hose can be
taped to the pipes.
See Figure 4.
Figure 4. Rear View of Indoor Unit
40"
20"
12"
12"
Air
Intake
Air
Intake
Air
Discharge
Unit
Access
2"
2"
2"
Air Flow
Direction
Floor
72" Min.
Height
Drain Hose