www.DaikinApplied.com 49
IM 830-6
MicroTech Unit Electrical
Connections
WARNING
!
To avoid electrical shock, personal injury or death, be sure that field
wiring complies with local and national fire, safety, and electrical
codes, and voltage to the system is within the limits shown in the
job-specific drawings and unit electrical data plate(s).
WARNING
!
Power supply to unit must be disconnected before making field
connections. To avoid electrical shock, personal injury or death, be
sure to rigorously adhere to field wiring procedures regarding proper
lockout and tag out of components.
See
and the job-specific electrical drawings
before proceeding with field power and control wiring. See also
the wiring diagram provided on the unit ventilator right front
access panel.
Unit ventilators equipped with an optional electric heating coil
have electric heating coil power connections at right end only.
Procedure
1. Provide power supply to right end compartment to match
unit nameplate.
Use copper conductors only. Use of aluminum conductors
may result in equipment failure and overheating hazards. All
wiring in right hand compartment must be class 1.
CAUTION
!
2. Wire leads provided from unit ventilator electric connection
box to load side of unit power switch, (switch provided by
Daikin).
The junction box has 1"(25mm) and 2"(51mm) knockouts,
located 10-1/2"(267mm) from right end of unit.
3. Provide ground wire from grounding screw in switch
junction box to switch ground terminal.
4. Wire field power supply to line side of unit power switch.
Wire ground conductor to switch ground terminal.
5. Mount unit power switch in switch junction box and install
switch cover plate (provided).
6. On units with electric heat, the 2 pole unit power switch
is replaced by a 3 pole switch and is mounted in the
locations as shown in
. (A) shows
switch location for valve control units and (B), and (C)
show location for Face & Bypass control units. (B) is for
208, 230 and 265 volt horizontal (AH) units. (C) shows
location for 460 volt horizontal (AH) units.
Figure 85: Electric Heat Unit Power Switch Locations
See Electrical Data/Motor Data and Unit Amp without
electric heat
.
See Electric Heat wiring data
Figure 86: MicroTech Control DDC Electric Connection Box
Located in Right End Compartment (See
number descriptions)
1
MicroTech Unit Ventilator Controller (UVC)
2
Plug-in Communication Module Location
3
Local User Interface (LUI)
4
External Signal Connection Plugs
5
Electric Connection Box
7 Fuse(s)
8
Control Transformer