www.DaikinApplied.com 19
IM 830-6
Lifting The Unit Into Position
Remove the two end panels to provide access to the mounting
holes once the unit is lifted. If the installed location will not
allow access through the end of the unit, remove the two
hinged bottom panels instead of the end panels prior to placing
on lifting device.
Apply protective material to lifting support(s) that come in contact
with unit to prevent scratching or denting the unit. Support the unit
across the entire length to prevent twisting or racking, throughout
the process of mounting.
CAUTION
!
Figure 38: Suggested Lifting Method
Lifting Device
AH Ceiling Unit
Protective Material To Prevent
Scratching and Denting of
Unit. Support Across Entire
Length of Unit to Prevent
Twisting or Racking.
Figure 39: Mounting Hole Locations
Model
Dimension "A"
H07, V07
48" (1219)
H10, V10
60" (1524)
H13, V13
72" (1829)
H15, V15
84" (2134)
H20, V20
84" (2134)
Release End Panel Fasteners To Gain
Access To Interior Mounting Holes
Note:
Shaded
area = 36" horizontal clearance
recommended at right end for service (24"
minimum). Amount of recess must consider
location of end panel fasteners. Recess
flanges must not interfere with access to
these fasteners.
Table 3: Ceiling AH General Data
Unit Size
H07, V07
H10, V10
H13, V13
H15, V15
H20, V20
Nominal Airflow - cfm (L/s)
750 (354)
1000 (472)
1250 (590)
1500 (708)
2000 (944)
Fan Data
Number of Fans
2
3
4
4
4
Size
inches (mm)
Diameter
8.12 (206)
8.12 (206)
8.12 (206)
8.12 (206)
9½ (241)
Width
8.25 (210)
8.25 (210)
8.25 (210)
8.25 (210)
6 (152)
Filter Data
(Quantity) Size
Inches
(1) 10 x 36½ x 1
(1) 10 x 48½ x 1
(1) 10 x 60½ x 1
(2) 10 x 36½ x 1
(2) 10 x 36½ x 1
(mm)
254 x 927 x 25
254 x 1232 x 25
254 x 1587 x 25
254 x 927 x 25
254 x 914 x 25
Area
Ft.
2
(m
2
)
2.54 (.24)
3.37 (.31)
4.20 (.39)
5.08 (.47)
5.08 (.47)
Shipping Weight
lbs. (kg)*
Discharge Air
Arrangement
AH, AT
350 (159)
425 (193)
495 (225)
570 (259)
N/A
FD, FG or BD
385 (179)
465 (211)
540 (245)
620 (281)
680 (309)
Coil Water
Volume
Gal. (Ltrs)
1-Row Coil
.25 (0.95)
.31 (1.17)
.38 (1.44)
.44 (1.67)
.44 (1.67)
2-Row Coil
.45 (1.70)
.57 (2.16)
.69 (2.61)
.82 (3.10)
.82 (3.10)
3-Row Coil
.64 (2.42)
.82 (3.10)
1.01 (3.82)
1.19 (4.50)
1.19 (4.50)
4-Row Coil
.83 (3.14)
1.08 (4.09)
1.32 (5.00)
1.57 (5.94)
1.57 (5.94)
5-Row Coil
1.03 (3.90)
1.34 (5.07)
1.64 (6.21)
1.95 (7.38)
1.95 (7.38)
*
Approximate weights based on Face and Bypass Damper Controlled Unit with 4- row cooling coil, high capacity hot water coil and MicroTech
®
II controls.