IM 820
Page 5
Installation Guidelines
Installation Diagram
Installation of Outdoor Unit
Install the outdoor unit in a manner to prevent mixing hot
discharged air with return air flow. Also, the unit should be a
suitable distance from obstructions
See Figure 1
for mini-
mum installation clearances. Double the dimensions shown if
surroundings are more than 72" tall, or if there is an obstruc-
tion on top. Select the coolest possible place where intake air
temperature is not greater than the outside air temperature
(maximum 113°F). See Table 1, Page 7 for weight of outdoor
unit.
Figure 1. Outdoor Unit Minimum Clearances
Air Discharge Swing Baffle
IR Receiver and
LED Indicator Lights
Air Discharge Grille
Air Intake Grille
Air Intake
Air Discharge Nozzle
Refrigerant Tubing
and Insulation
Air Intake
Air Filters
OUTDOOR UNIT
INDOOR UNIT
Optional Wired
Wall Control
Wireless IR
Remote Control
40"
20"
12"
12"
Air
Intake
Air
Intake
Air
Discharge
Service
Access
Min.
Min.
Min.
Min.