HXHD125A7V1B
VRVIII system indoor unit
4PW62584-1A – 11.2010
Installation manual
39
9
Automatic temperature compensation
00
Leaving water temperature compensation value
(heating)
0
–2~2
0.2
°C
01
Domestic hot water tank compensation value
0
–5~5
0.5
°C
02
Thermo ON/OFF admission
0
–5~5
0.5
°C
03
Not applicable. Do not change the default value.
0
—
—
—
04
Not applicable. Do not change the default value.
0
—
—
—
A
Option setup
00
Current limitation.
0
0~2
1
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Set point: heating required temperature difference
for leaving and returning water
10
3~15
1
°C
03
Set point: multiple set point 1 required temperature
value
35
25~80
1
°C
04
Set point: multiple set point 2 required temperature
value
65
25~80
1
°C
b
Domestic hot water set points
00
Set point: reheat minimum temperature
35
35~65
1
°C
01
Set point: reheat maximum temperature
45
35~75
1
°C
02
Status: weather dependent domestic water
heating
1 (ON)
0/1
—
—
03
Set point: storage temperature
70
45~75
1
°C
04
Automatic maximum domestic hot water storage
temperature
70
55~75
1
°C
C
Leaving water temperature limits
00
Set point: heating leaving water maximum
temperature
80
37~80
1
°C
01
Set point: heating leaving water minimum
temperature
25
25~37
1
°C
02
Not applicable. Do not change the default value.
20
—
—
—
03
Not applicable. Do not change the default value.
5
—
—
—
04
Not applicable. Do not change the default value.
0
—
—
—
d
Domestic water heating retention times
00
Set point: minimum time for domestic water
heating
10
5~20
1
—
01
Set point: maximum time for domestic water
heating
30
10~60
5
—
02
Set point: interval minimum stop time of domestic
water heating
15
5~30
5
—
03
Not applicable. Do not change the default value.
15
—
—
—
04
Not applicable. Do not change the default value.
40
—
—
—
E
Service mode
00
Vacuum mode R134a
0
0/1
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Not applicable. Do not change the default value.
0
—
—
—
03
Not applicable. Do not change the default value.
1
—
—
—
04
Pump only operation
0
0~25
1
—
F
Option setup continued
00
Not applicable. Do not change the default value.
5
—
—
—
01
Not applicable. Do not change the default value.
0
—
—
—
02
Heat recovery allowance setting
1
0~2
—
—
03
Not applicable. Do not change the default value.
10
—
—
—
04
Not applicable. Do not change the default value.
50
—
—
—
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range
Step
Unit
Date
Value
Date