11
Application Information
Cable Size
Cooling only
Model
Unit
FDN80HV1
FDN100HV1
RN80HY1
RCN100HY1
Voltage range**
Indoor
220 - 240V / 1Ph / 50Hz +
Outdoor
380 - 415V / 3Ph / 50Hz + N +
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
mm
2
mm
2
mm
2
1.0
2.5
2.5
-
5.0
1.0
2.5
2.5
-
5.0
Interconnection cable size*
Number of conductors
mm
2
1.0
4.0
1.0
4.0
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
A
A
A
6.0
32.0
32.0
16.0
32.0
40.0
Model
Unit
FDN125HY1
FDN150HY1
2FDN200HY1
RCN125HY1
RCN150HY1
RCN100HY1 x 2
Voltage range**
Indoor
380 - 415V / 3Ph / 50Hz + N +
Outdoor
380 - 415V / 3Ph / 50Hz + N +
Power supply cable size*
a) Indoor Unit
b) Outdoor Unit
c) Total
Number of conductors
a) Indoor Unit
b) Outdoor Unit
mm
2
mm
2
mm
2
1.0
4.0
4.0
3.0
5.0
1.0
10.0
10.0
3 .0
5.0
1.0
2.5
-
5.0
5.0
Interconnection cable size*
Number of conductors
mm
2
1.0
4.0
1.0
4.0
1.0
1.0
Recommended fuse/
circuit breaker rating*
a) Indoor Unit
b) Outdoor Unit
c) Total
A
A
A
4.0
40.0
40.0
6.0
50.0
50.0
10.0
32.0
-