background image

Trail  Operation And Testing 

1. Trial operation and testing

•  Check that the inter-unit wire is correctly connected. 
•  Trial operation should be carried out in COOL operation. 

1-1  Measure the supply voltage and make sure that it is within the specified range. 

1-2  Select the lowest programmable temperature. 

1-3 Carry out the trial operation following the instructions in the operation manual to ensure that all functions and parts, 

such as the movement of the flaps, are working properly. 

• To protect the air conditioner,  restart operation is disabled  for 3 minutes after the system has been turned off.

1-4 After trial operation is complete, set the temperature to a normal level (26

°

C to 28

°

C in COOL  operation, 20

°

c to 24

°

in HEAT operation). 

•  When operating the air conditioner in COOL operation in winter, or HEAT operation in summer, set it to the trial operation mode using the following method. 

1)  Press NMODE" button and select the cooling or heating mode. 

2)  Press "ON/OFF" button to  turn on the system. 

3)  Press both of "TEMP" button and NMODE" button at the same time. 

4)  Press "TEMP· button, select Nr•, and press "MODE" button for confirmation. 

• Trial operation will stop automatically after about 30 minutes. To stop the operation press ·oN/OFF" button. 

• The air conditioner draws a small amount of power in its standby mode. If the system is not to be used for some time after installation, shut off the circuit breaker to 

eliminate unnecessary power consumption. 

• If the circuit breaker trips to shut  off the  power  to the air conditioner,  the system  will  restore the original operation mode when  the circuit  breaker is 

turned  on again. 

2. Items to Check

Test  Items 

Symptom 

Check 

Indoor and outdoor units  are  installed securely. 

Fall,  vibration,  noise 

No refrigerant gas leaks. 

Incomplete cooling function 

Refrigerant gas and  liquid pipes and indoor  drain hose 

Water  leakage 

extension are  thermally  insulated. 

Draining  line is  properly  installed. 

Water  leakage 

System is  properly  earthed. 

Electrical leakage 

Only specified wires are  used for all wiring,  and all 

No operation or  burn damage 

wires  are  connected correctly. 

Indoor or outdoor unit's air intake or exhaust has clear path of air.  Incomplete  cooling  function 

Stop valves are opened. 

Incomplete cooling function 

Indoor unit properly receives remote controller commands. 

No operation 

Pump Down Operation 

� WARNING---------------

• Make sure that air or any matter other than refrigerant (R32) does not get into the refrigeration cycle. 

• When performing a pump down, turn off the compressor before detaching the refrigerant pipes.  {If the refrigerant pipes are detached when 

the compressor is operating and the stop valves are open, air will be drawn in leading to abnormally high pressure in the 

refrigeration cycle. This may result in rupturing and bodily injury.) 

In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 

1)  Remove the valve cap from the liquid stop valve and gas stop valve. 

2)  Begin forced cooling operation. 

3)  After 5 to  10 minutes, close the liquid stop valve with a hexagonal wrench. 

4)  After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation. 

5)  Attach the valve cap once procedures are complete. 

Forced cooling operation 

■  Using the indoor unit ON/OFF switch 

Press and hold the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.) 

• Forced cooling operation will stop automatically after about 15 minutes. 

To stop the operation, press the indoor unit ON/OFF switch. 

Disclaimer: Appearance of indoor & outdoor unit may differ 

between different models. 

Hexagonal 
wrench 

11 

Summary of Contents for GTKC48UV16W

Page 1: ...ODELS F G MTKM35UV16W F G MTKM50UV16U F G MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71...

Page 2: ...uality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that producenaked flames...

Page 3: ...er Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop long beep 13 In...

Page 4: ...remote controller 7 9 10 14 13 S NO 1 2 3 4 5 6 7 10 Never expose the remote controller to direct sunlight DAIKIN 011 II POWER LL 11 DEjaR I II T P BIi 11COANDA HP 11 El I STREAMER DIS j LAY ll CE I1...

Page 5: ...ontroller Do not get it wet The maximum transmission distance is about 7m To attach the accessory filters i Receiver Set the accessory filters under the tabs of the filter Ac esso yfUte i n h 0 Y u f...

Page 6: ...the accessory filter and the decomposition power of the streamer discharge combine to reduce unpleasant odours and viruses cleaning the air in the room To start operation 1 Press I c I STREAMER When l...

Page 7: ...LD LOCK disables all the buttons except when ECONO and POWERFULL button press together for about 5 seconds To set the CHILD LOCK Press and o_WE_R_c 1L together for about 5 seconds e will be displayed...

Page 8: ...1SWIN and SWING and e are displayed on the LCD The flap and louvres move in turn To cancel 3 D airflow press either 4swiNaj or sw1NG again The flap or louvres will stop moving I II l _ ry _ ___ To se...

Page 9: ...uses the settings to be cancelled and disappears from the LCD ECONO operation functions in COOL and DRY operation POWER CHILL and ECONO operation cannot be used at the same time is displayed on the LC...

Page 10: ...time default 2HR are displayed on the LCD IC O ON OFF c J The TIMER lamp lights Display orange TEMP 2 Press v while C is blinking Each pressing of the button changes tempera ture shift value by 1 c Yo...

Page 11: ...Set temperature does not display when the unit is in DRY operation or FAN operation Inverter output and set temperature may not display depending on the operation mode that is active The display turns...

Page 12: ...Dry mode OFF Cooling operation To cancel DEW CLEAN operation Turn OFF the machine from Remote Controller Wi Fi Control NOTE Note on LED 7 Segment Brightness Control Ld indicates for the brightness Li...

Page 13: ...age the front panel shaft on the other side in the same manner After disengaging both front panel shafts pull the front panel toward yourself and remove it 3 Clean the front panel Wipe it with a soft...

Page 14: ...with a vacuum cleaner If the dust does not come off easily wash them with neutral detergent thinned with lukewarm water then let them dry in the shade Be sure to remove the accessory filter optional p...

Page 15: ...m Titanium apatite deodorizing air purifying filter 1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Micro filter PM2 5 for streamer unit 1 set Micro filter PM 1 0 for st...

Page 16: ...es operation in about 3 minutes Voltage range protection 130V 285V Voltage range protection 130V 265V for F GTKL71UV16T Models A sound is heard A sound like flowing water This sound is generated becau...

Page 17: ...been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is the airflo...

Page 18: ...air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood stop operation and turn off the circu...

Page 19: ...E7 DC FAN MOTOR FAULT E8 OVERCURRENT INPUT F3 HIGH TEMPERATURE DISCHARGE PIPE CONTROL F6 HIGH PRESSURE CONTROL IN COOLING F8 OPERATION HALT DUE TO COMPRESSOR INTERNAL TEMPERATURE ABNORMALITY OUTDOOR H...

Page 20: ......

Page 21: ...MTKM35UV16W F G MTKM50UV16U F G MTKM60UV16U FTKT35UV16W FTKT50UV16V FTKT60UV16U FTKN35UV16W FTKN50UV16V A D F G MTKL35UV16W A D F G MTKL50UV16V A D F G MTKL50UV16U A D F GTKL60UV16U F GTKL71UV16T A F...

Page 22: ...rant gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas le...

Page 23: ...many television orradio set theunit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby The outdoor unit shoul...

Page 24: ...rder to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensions of ODU instal...

Page 25: ...hing up pull it toward you Installation method 1 Push up 1 Install the front grille and firmly engage the upper hooks 3 locations 2 Install 3 screws of the front grille 3 Install the air filter and th...

Page 26: ...peend Drainhose position Type H X W X D A B C CD 298 X 800 X 229 800 116 5 116 5 0 298 X 821 X 235 821 128 126 5 298 X 885 X 229 885 116 5 116 5 298 X 906 X 235 906 127 127 5 Unit size available on na...

Page 27: ...to set it on the A mounting plate hooks Make sure the wire lead do not catch on the edgeofthe indoor unit 9 Securethe indoor unit to the A mounting plate with the E indoor unit fixing screws M4 x 12L...

Page 28: ...not included with the unit TableNo 6 6 WARNING Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst connections as they may cause overheat...

Page 29: ...Heat insulationpipe cover Slit __ 7 Z_J r I I I I 1 I I I I I J Slit Vinyl1ape _ This illustration shows the case of the left rear piping Sectional view wire Insulation tape Overwrap more than half of...

Page 30: ...m 0 D 9 5mm 333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 505 615 kgf cm 48 1 59 7N m 0 D 15 9mm 61 8 75 4N m 490 610 kgf cm 10 8 14 7N m 110 150 kgf cm 630 770 kgf cm 14 2 17 2N m 21...

Page 31: ...ve s service port thenfullyopenliquidandgas stop valves Do not attempt to tum valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wren...

Page 32: ...installed securely Fall vibration noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Drai...

Page 33: ...020 Meaning of E waste under E Waste Management Rules 2022 E waste Rules Waste electrical and electronic equipment whole or in part of reject from their manufacturing and repair process which are inte...

Reviews: