FXZQ20~50M8V1B
VRV System air conditioners
4PW25085-1C

Installation and operation manual

3

2.

Make the ceiling opening needed for installation where
applicable. (For existing ceilings.)

Refer to the paper pattern for installation for the ceiling opening
dimensions.

Create the ceiling opening required for installation. From the side
of the opening to the casing outlet, implement the refrigerant and
drain piping and wiring for remote controller (unnecessary for
wireless type) and indoor-outdoor unit wiring. Refer to each
piping or wiring section.

After making an opening in the ceiling, it may be necessary to
reinforce ceiling beams to keep the ceiling level and to prevent it
from vibrating. Consult the builder for details.

3.

Install the suspension bolts. (use either a M8 or M10 size bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to reinforce the
ceiling in order to bear the weight of the unit. Adjust clearance from
the ceiling before proceeding further.

Installation example see 

figure 4

.

I

NDOOR

 

UNIT

 

INSTALLATION

When installing optional accessories, read also the installation
manual of the optional accessories. Depending on the field
conditions, it may be easier to install optional accessories before the
indoor unit is installed (except for the decoration panel). However, for
existing ceilings, install fresh air inlet component kit and branch duct
before installing the unit.

1.

Install the indoor unit temporarily.

 

Attach the hanger bracket to the suspension bolt. Be sure to fix it
securely by using a nut and washer from the upper and lower
sides of the hanger bracket.

Securing the hanger bracket see 

figure 5

.

2.

Fix the paper pattern for installation. (For new ceilings
only.)

The paper pattern for installation corresponds with the measure-
ments of the ceiling opening. Consult the builder for details.

The centre of the ceiling opening is indicated on the paper
pattern for installation. The centre of the unit is indicated on the
paper pattern for installation.

After removing the packaging material from the paper pattern for
installation, attach the paper pattern for installation to the unit
with the supplied screws as shown in 

figure 8

.

3.

Adjust the unit to the right position for installation.

(Refer to the chapter 

"Preparations before installation" on page 2

.)

4.

Check if the unit is horizontally levelled.

Do not install the unit tilted. The indoor unit is equipped with a
built-in drain pump and float switch.
(If the unit is tilted against condensate flow, the float switch may
malfunction and cause water to drip.)

Check if the unit is levelled at all four corners with a water level or
a water-filled vinyl tube as shown in 

figure 9

.

5.

Remove the paper pattern for installation. (For new ceilings
only.)

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation
manual supplied with the outdoor unit.

Execute heat insulation work completely on both sides of the
gas piping and the liquid piping. Otherwise, this can sometimes
result in water leakage.
(When using a heat pump, the temperature of the gas piping can
reach up to approximately 120°C. Use insulation which is
sufficiently resistant.)

Also, in cases where the temperature and humidity of the
refrigerant piping sections might exceed 30°C or RH 80%,
reinforce the refrigerant insulation (20 

mm or thicker).

Condensation may form on the surface of the insulating
material.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for the used refrigerant.

Apply ether oil or ester oil around the flare portions before
connecting.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

Use copper alloy seamless pipes (ISO 1337).

The outdoor unit is charged with refrigerant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc.., inside the refrigerant circuit.

Refer to the table below for the dimensions of flare nuts and the
appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE

All the above parts are field supplied.

For other installation than standard installation,
contact your Daikin dealer for details.

1

Nut (field supply)

2

Hanger bracket

3

Washer (supplied with the unit)

4

Tighten with double nuts (field supply)

1

Paper pattern for installation (supplied with the unit)

2

Screws (supplied with the unit)

1

Water level

2

Vinyl tube

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe gauge

Tightening torque

Flare dimension A 

(mm)

Flare shape

Ø6.4

14.2~17.2 N•m

(144~176 kgf•cm)

8.7~9.1

Ø12.7

49.5~60.3 N•m

(504~616 kgf•cm)

16.2~16.6

1

2

4

3

R0.4~0.8

45

° ±

2

90

°±

2

A

Summary of Contents for FXZQ20M8V1B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ20M8V1B FXZQ25M8V1B FXZQ32M8V1B FXZQ40M8V1B FXZQ50M8V1B System air conditioners ...

Page 2: ... 4 50 100 2 2 3 4 5 1 1 2 45 45 5 6 533 3 575 2 585 660 1 700 4 700 2 585 660 3 575 4 533 1 585 660 8 7 20 20 180 2 1500 1500 1500 2500 1500 1500 1500 1500 1 2 2 1 2 3 3 2 1 4 2 3 4 1 2 1 2 2 1 295 5 4 2 1 3 6 16 1 2 3 4 5 6 7 8 9 10 10 11 11 1 2 3 4 5 6 7 8 9 10 11 1x 1x 1x 8x 4x 1x 1x 1x 1x 2x 1x 2 3 1 4 5 6 7 8 10 9 11 12 15 14 13 17 16 ...

Page 3: ... LN P1 P2 P1 P2 F1 F2 T1 T2 3 4 2 1 SETTING 2 1 4 3 23 24 1 2 3 4 5 6 7 8 9 10 11 12 13 13 1 2 3 8 7 4 4 5 5 5 6 6 6 5 21 3 2 1 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box P1 P2 LN P1 P2 F1 F2 T1 T2 L N 6 3 4 2 5 1 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 20 18 19 22 20 21 ...

Page 4: ...ych pod warunkiem że używane są zgodnie z naszymi instrukcjami 18 sunt în conformitate cu următorul următoarele standard e sau alt e document e normativ e cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili 20 on vastavuses järgmis t e standardi te ga või t...

Page 5: ...tchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also...

Page 6: ... more than 2 5 m so that the user cannot easily touch 3 Air flow directions Select the air flow directions best suited to the room and point of installation For air discharge in 2 or 3 directions it is necessary to make field settings by means of the remote controller and to close the air outlet s Refer to the installation manual of the optional blocking pad kit and to the chapter Field setting on...

Page 7: ...e unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four corners with a water level or a water filled vinyl tube as shown in figure 9 5 Remove the paper pattern for installation For new ceilings only REFRIGERANT PIPING WORK Fo...

Page 8: ... and drain hose to insulate How to perform piping See figure 15 Precautions Install the drain raising pipes at a height of less than 545 mm Install the drain raising pipes at a right angle to the indoor unit and no more than 300 mm from the unit NOTE Not recommended but in case of emergency You must use a torque wrench but if you are obliged to install the unit without a torque wrench you may foll...

Page 9: ...ion manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the circuit breaker and switch and wiring instructions Be sure to ground the air conditioner Do not connect the ground wire to gas pipes water pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Water pipes no grounding ef...

Page 10: ... branch must be sheathed in order to provide an equal or greater degree of insulation as power supply wiring itself 3 Do not connect wires of different gauge to the same grounding terminal Looseness in the connection may deteriorate the protection 4 Remote controller cords and wires connecting the units should be located at least 50 mm away from power supply wiring Not following this guideline may...

Page 11: ...nsorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display indications Display Do not display 5 Information to I manager I touch controller Only unit sensor value or remote sensor value if installed Sensor value as set by...

Page 12: ...efer to the manual of each optional controller for centralized control INSTALLATION OF THE DECORATION PANEL Read the chapter Test operation on page 8 before making a test run without attaching the decoration panel Refer to the installation manual delivered with the decoration panel After installing the decoration panel ensure that there is no space between the unit body and decoration panel Otherw...

Page 13: ...TO CLEAN AIR FILTER display disappears For details refer to the operation manual of the outdoor unit How to clean the air outlet and outside panels Clean with a soft cloth When it is difficult to remove stains use water or neutral detergent When the blade is extremely contaminated remove it as below and clean it How to clean the suction grill 1 Open the suction grill Push both knobs simultaneously...

Page 14: ...ED H2P LIGHT EMITTING DIODE SERVICE MONITOR GREEN H3P LIGHT EMITTING DIODE SERVICE MONITOR RED H4P LIGHT EMITTING DIODE SERVICE MONITOR ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELECTOR SWITCH WIRELESS ADDRESS SET CONNECTOR FOR OPTIONAL PARTS X16A CONNECTOR ADAPTOR FOR WIRING X18A CONNECTOR ADAPTOR FOR ELECTRICAL APPENDICES FIELD WIRING BLK BLACK PNK PINK TERMINAL BLU BLUE RED RED CONNECTOR GRN GRE...

Page 15: ...25 27 29 28 26 T1 T2 10 15 mm A D 1 2 3 4 5 6 7 8 15 11 9 15 10 15 8 15 10 15 B 11 12 12 13 14 1 0 1 5 m m C E REMOTE CONTROL TRANSMISSION WIRING FORCED OFF L N L N 25 26 27 28 29 ...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25085 1C ...

Reviews: