background image

6

English

NOTE

The incline of attached drain hose should be  
3 in. (75 mm) or less so that the drain socket does 
not have to withstand additional force.
To ensure a downward slope of 1:100, install 
hanging bars every 39-1/2 in. (1 m) to 60 in.  
(1.5 m).
When unifying multiple drain pipes, install the 

pipes as shown in figure 8. Select converging 

drain pipes whose gauge is suitable for the 
operating capacity of the units. 

T-joint converging drain pipes

Testing of drain piping

After the piping work is finished, check if drainage flows smoothly.

 

„

Add approximately 0.25 gal (1 

) of water gradually through the air 

discharge outlet. 

Method of adding water (See figure 10)

Plastic watering can (tube should be about 4 in. (100 mm) long)

Service drain outlet (with rubber plug) (Use this outlet to drain water 
from the drain pan)

Drain pump location

Drain pipe

Drain socket (water flow view point)

 

„

Check the drainage flow.

 

„

In case electric wiring work is finished

 

Check drainage flow during cooling operation, explained in 

 

“Test operation” on page 10.

 

„

In case electric wiring work is not finished

 

-

Remove the control box lid by means of two screws. Connect 

the single-phase power supply (208/230V 60Hz) to 
connections L1 and L2 on the terminal block power supply and 

connect the ground wire firmly (See figure 9).

 

-

Reattach the control box lid and turn on the power.

 

- Do not touch the drain pump. It may result in electric shock.

Control box lid

Power supply wiring

Ground wire

Terminal block for power supply

Clamp

Transmission wiring

Terminal block for transmission wiring

Openings for wires

Wiring diagram label 

(on the back side of the control box lid)

10 

Remote controller wiring

Terminal block for power supply (4) 

L

1

L

2

 

-

Confirm the drain operation looking at the drain socket.

 

-

After checking the drainage flow, turn off power, remove the 
control box lid and disconnect the power supply wiring from the 
terminal block for power supply again. Attach the control box 

lid as before.

Electric wiring work

General instructions

 

„

All field wiring and components must be installed by a licensed 

electrician and must comply with relevant national, state and local 
code.

 

„

Use copper wire only.

 

„

Follow the ‘Wiring diagram label’ attached to the back side of the 

control box lid to wire outdoor unit, indoor units and the remote 

controller. For details on hooking up the remote controller, refer to 
the “Installation manual of the remote controller”.

 

„

All wiring must be performed by an authorized electrician.

 

„

A main switch or other means for disconnection, having a contact 

separation in all poles, must be incorporated in the fixed wiring in 

accordance with relevant local and national code.

 

„

Note that the operation will restart automatically if the main power 
supply is turned off and then turned back on again.

 

„

Be sure to ground the air conditioner.

 

„

Do not connect the ground wire to:

 

-

gas pipes: might cause explosions or fire if gas leaks.

 

- telephone ground wires or lightning rods: might cause abnormally 

high electric potential in the ground during lightning storms.

 

- plumbing pipes: no grounding effect if hard vinyl piping is used.

01_EN_3P493125-1.indd   6

9/21/2017   10:16:30

Summary of Contents for FXZQ05TAVJU

Page 1: ...anual in a handy place for future reference This manual should be left with the equipment owner Lire soigneusement ces instructions avant l installation Conserver ce manuel à portée de main pour référence ultérieure Ce manuel doit être donné au propriétaire de l équipement Lea cuidadosamente estas instrucciones antes de instalar Guarde este manual en un lugar a mano para leer en caso de tener algu...

Page 2: ...205 8 11 16 220 BYFQ60C BYFQ60B 25 3 8 645 H1 H2 24 13 16 630 8 2 4 7 1 9 10 5 6 5 2 7 4 3 5 6 7 7 1 16 180 13 16 20 13 16 20 2 1 2 63 27 9 16 700 1 22 5 8 575 3 21 533 4 23 1 16 26 585 660 2 23 1 16 26 585 660 2 27 9 16 700 1 23 1 16 26 585 660 2 22 5 8 575 3 21 533 4 8 11 1 4 285 6 24 7 16 620 1 7 1 2 190 23 1 16 23 7 16 585 595 2 22 5 8 575 3 24 7 16 620 1 23 1 16 23 7 16 585 595 2 1 2 12 5 1 2...

Page 3: ...2 3 5 IN D OUT D F1 F2 F1 F2 Control box L2 L1 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 L2 L1 P1 P2 P1 P2 F1 F2 T1 T2 L2 L1 L2 L1 P1 P2 P1 P2 F1 F2 T1 T2 L1 L2 1 4 2 3 14 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box P1 P2 L2 L1 P1 P2 F1 F2 T1 T2 1 6 2 3 16 A B 4 4 4 4 2 3 2 3 17 A B 18 10 Unit in mm 2 1 5 4 4 100 3 11 2 2 L1 L2 L1 L2 1 L1 L2 L1 L2 2 3 4 5 6 1 L1 L2 ...

Page 4: ... may cause injuries or death by suffocation WARNING Only qualified personnel must carry out the installa tion work Installation must be done in accordance with this installation manual Improper installation may result in water leakage electric shock or fire When installing the unit in a small room take mea sures to keep the refrigerant concentration from ex ceeding allowable safety limits Excessiv...

Page 5: ...nit is for R410A See the catalog for in door models that can be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit far away from fluorescent lamps as much as possible Indoor units are for indoor inst...

Page 6: ...0A The connectable outdoor units must be designed exclusively for R410A Precautions This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised ...

Page 7: ...oor unit b Lighting The figure describes a surface mounted light but a recessed ceiling light is not restricted c Air fan A If the air outlet is closed space marked A should be 8 in 200 mm at least B 60 in 1500 mm from any static obstruction 1 Select an installation site where the following conditions are fulfilled and that meets your customer s approval Where optimum air distribution can be ensur...

Page 8: ...making an opening in the ceiling it may be necessary to reinforce ceiling beams to keep the ceiling level and to prevent it from vibrating Consult the builder for details 3 Install the suspension bolts Use either a M8 M10 size bolt or equivalent Use anchors for existing ceilings and a sunken insert sunken anchors or other field supplied parts for new ceilings to reinforce the ceiling in order to b...

Page 9: ...rant such as air etc inside the refrigerant circuit Only use annealed material for flare connections Refer to Table 1 for the dimensions of flare nut spaces and the appropriate tightening torque Overtightening may damage the flare and cause leaks Table 1 Pipe size Tightening torque Flare dimensions A in Flare φ1 4 10 4 12 7 ft lbf 0 342 0 358 R0 016 0 031 φ1 2 36 5 44 5 ft lbf 0 638 0 654 Refer to...

Page 10: ...g of drain piping is finished attach the drain sealing pad 4 supplied with the unit over the uncovered part of the drain socket between drain hose and unit body 1 5 2 3 4 3 4 2 A A A A 1 1 Drain socket attached to the unit 2 Drain hose supplied with the unit 3 Metal clamp supplied with the unit NOTE Bend the tip of the metal clamp without tearing the sealing 4 Large sealing pad supplied with the u...

Page 11: ... wire 4 Terminal block for power supply 5 Clamp 6 Transmission wiring 7 Terminal block for transmission wiring 8 Openings for wires 9 Wiring diagram label on the back side of the control box lid 10 Remote controller wiring Terminal block for power supply 4 L1 L2 Confirm the drain operation looking at the drain socket After checking the drainage flow turn off power remove the control box lid and di...

Page 12: ...set the remote controller Connection of power supply transmission and remote controller wiring How to connect wiring See figure 9 1 Remove the control box lid 2 screws 1 2 1 Screws 2 Control box lid 2 Insert the power supply and ground wires into the conduit pipe and secure the conduit to the hole in the control box using the lock nut and the washer for conduit as shown below 5 3 7 8 6 4 3 Hole in...

Page 13: ...ightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that they do not obstruct other equipment such as popping open the service cover Make sure the cover closes tight Incomplete connections could result in overheating and in the worst case electric shock or fire Wiring example Fit the power supply wiring of each unit...

Page 14: ...peed 4 Differential automatic changeover 0 F 0 C 1 8 F 1 C 3 6 F 2 C 5 4 F 3 C See note 6 5 Auto restart after power failure Disabled Enabled 6 Fan setting during thermostat OFF at cooling operation LL Set speed 13 23 0 Setting for air outlet velocity This setting is to be changed in function of ceiling height 8 to 3 4 ft 2 7 m or less 8 3 4 to 10 2 7 3 0 10 to 11 1 2 3 0 3 5 1 Selection for air f...

Page 15: ...on Remote control is available by connecting the external input to the terminal T1 and T2 on the terminal block for transmission wiring F2 T1 T2 FORCED OFF Input A Wiring specification Sheathed vinyl cord or 2 core cable Gauge AWG18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of 15 V DC 1 mA 2 Actuation Input A of FORCED OFF an...

Page 16: ... 1709 HT 3P493125 1 EM17A018 ...

Reviews: