16
|
Unit installation
Installer and user reference guide
53
FXZA15~50A2VEB
VRV system air conditioner
4P599623-1A – 2020.06
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will not occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic disturbance of other equipment and use conduit tubes for power
and transmission lines.
▪
Take care that in the event of a water leak, water cannot cause any damage to
the installation space and surroundings.
▪
Choose a location where the operation noise or the hot/cold air discharged from
the unit will not disturb anyone.
▪
Air flow.
Make sure nothing blocks the air flow.
▪
Drainage.
Make sure condensation water can be evacuated properly.
▪
Paper pattern for installation
(upper part of packing) (accessory). When
selecting the installation location, use the paper pattern. It contains the
dimensions of the unit and the required ceiling opening.
▪
Air flow directions
. You can select different air flow directions. Choose the one
best suited for the room. For more information, see the installation manual of
the optional blocking pad kit.
Example:
a
b
c
a
4-way air flow (all air outlets open)
b
3-way air flow (1 air outlet closed) (optional blocking pad kit required)
c
2-way air flow (2 air outlets closed) (optional blocking pad kit required)
▪
Ceiling insulation
. When conditions in the ceiling exceed 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, then additional
insulation is required (minimum 10 mm thickness, polyethylene foam).
▪
Spacing
. Mind the following requirements:
(mm)
≥1500
≥2000
≥4000
≥1500
A
B
C
b
a
d
a
c
A
Minimum distance to the wall
≥1500 mm
: Air outlet open
≥200 mm
: Air outlet closed
B
Minimum and maximum distance to the floor (see below)
C
≥295 mm
: In case of installation with BYFQ60B
≥308 mm
: In case of installation with BYFQ60C
a
Indoor unit
b
Lighting (the figure shows ceiling-mounted lighting, but recessed lighting is also allowed)
c
Air fan
d
Static volume (example: table)