background image

4

Table 1

Pipe gauge

Tightening torque

Flare dimension A

Flare shape

(mm)

Ø 6.4

1420~1720N•cm

8.3~8.7

(144~176kgf•cm)

Ø 9.5

3270~3990N•cm

12.0~12.4

(333~407kgf•cm)

Ø 12.7

4950~6030N•cm

15.4~15.8

(504~616kgf•cm)

Ø 15.9

6180~7540N•cm

18.6~19.0

(630~770kgf•cm)

Ø 19.1

9720~11860N•cm

22.9~23.3

(990~1210kgf•cm)

DRAIN PIPING WORK

Rig the drain piping as shown in figure and take measures
against condensation. Improperly rigged piping could lead to
leaks and eventually wet furniture and belongings.

1

Hanging bar

1. Install the drain pipes.

Keep piping as short as possible and slope it downwards
so that air may not remain trapped inside the pipe.

Keep pipe size equal to or greater than that of the
connecting pipe (Vinyl pipe of 25mm nominal diameter and
32mm outer diameter).

Insert the supplied drain hose into the drain socket, up to
the white tape.

Tighten the clamp until the screw head is less then 4mm
from the hose.

1

Clamp metal

2

Drain hose

3

White tape (field supply)

Insulate the drain hose inside the building.

If the drain hose cannot be sufficiently set on a slope, fit
the hose with drain raising piping (field supply).

HOW TO PERFORM PIPING (see figure 8)

1

Ceiling slab

2

Hanger bracket

3

Adjustable (310 or less)

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

1 Connect the drain hose to the drain raising pipes, and insulate

them.

2 Connect the drain hose to the drain outlet on the indoor unit,

and tighten it with the clamp.

PRECAUTIONS

Instal the drain raising pipes at a height of less than 310mm.

Install the drain raising pipes at a right angle to the indoor unit
and no more than 300mm from the unit.

NOTE 

The incline of attached drain hose should be 75mm or less
so that the drain socket does not have to stand additional
force.

To ensure a downward slope of 1:100, install hanging bars
every 1 to 1.5m.

If unifying multiple drain pipes, install the pipes as shown
in figure 9. Select converging drain pipes whose gauge is
suitable for the operating capacity of the unit.

1

T-joint converging drain pipes

2. After piping work is finished, check if drainage flows

smoothly.

Open the water inlet lid, add approximately 2.5l of water
gradually and check the drainage flow.

Method of adding water. See figure 10.

1

Portable pump

2

Water inlet lid

3

Close

4

Open

5

Bucket

6

Refrigerant piping

7

Water inlet

If adding water from the charge inlet at the fan casing, be
sure to put the lid back in its original position.

WHEN ELECTRIC WIRING WORK IS FINISHED

Check drainage flow during COOL running, explained in chapter
"TEST OPERATION".

WHEN ELECTRIC WIRING WORK IS NOT FINISHED

Remove the switch box lid and connect the power supply and
remote controller to the terminals.
See figure 11.

1

Clamps A and B details

2

Clip

3

Terminal board

4

220V-240V single phase power supply

5

Electric parts box

6

Terminal board for transmission wiring

7

Clamp B

8

Transmission wiring

9

Guide plate

10

Power supply wiring

11

Clamp A

12

Terminal board for power supply

13

Electric parts box lid

Next, press the inspection/test operation button 

TEST

 on the

remote controller. The unit will engage the test operation

mode. Press the operation mode selector button 

 until

selecting fan operation 

. Then, press the on/off button 

.

The indoor unit fan and drain pump will start up. Check that

the water has drained from the unit. Press 

TEST

 to go back to

the first mode.

You can check whether drainage is satisfactory or not by
removing the access opening lid and checking the water level
of the drain pan through the access opening. 

Be careful

when doing so because the fan is turning at the same
time.

 See figure 12.

1

Access opening

2

Access opening lid

3

Close

4

Open

1

1-1.5m

R0.4~0.8

45

° ±

2

90

°±

0.5

A

;

;

2

1

3

Summary of Contents for FXYCP125K7V1

Page 1: ...INSTALLATION AND OPERATION MANUAL System air conditioner FXYCP20K7V1 FXYCP25K7V1 FXYCP32K7V1 FXYCP40K7V1 FXYCP50K7V1 FXYCP63K7V1 FXYCP80K7V1 FXYCP125K7V1 ...

Page 2: ...dos de acordo com as nossas instruções overholder følgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning är utförd i överensstämmelse med och följer följande standard er eller andra normgivande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i o...

Page 3: ...4 6 5 1 1 7 5 6 2 3 4 5 6 8 7 9 13 12 10 11 3 4 2 1 1 2 3 4 P 1 P 2 F 1 F 2 T 1 T 2 8 7 5 6 4 3 1 2 1 2 3 4 3 4 1 2 100 mm 1 9 8 5 6 10 11 12 1 2 7 13 1 3 6 4 5 2 1500 1500 1000 H 350 100 100 520 5 640 2 600 6 680 7 20 20 20 20 C B 2 6 A 7 5 D 1 2 3 4 ...

Page 4: ... T1 T2 1 2 3 4 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 3 5 2 4 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 15 16 18 17 20 19 14 21 F2 T1 T2 FORCED OFF 1 AIR CONDITIONER SETTING 2 4 3 1 7 3 4 1 2 5 6 9 8 ...

Page 5: ...described in this manual Caution concerning new refrigerant series The connectable outdoor units must be RSX Y P K or RSEYP K the outdoor units designed exclusively for R407C If outdoor units for R22 are connected the system will not work properly Precautions Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plas...

Page 6: ... parts are field supplied For other installation than standard installation contact your Daikin dealer for details Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Condensate water may drip Does drainage flow smoothly Condensate water may drip Does the power supply voltage corresp...

Page 7: ...before installation 5 Check if the unit is horizontally levelled Do not install the unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four corners with a water level or a water filled vinyl tube as shown in figure 7 1 Water le...

Page 8: ...stand additional force To ensure a downward slope of 1 100 install hanging bars every 1 to 1 5m If unifying multiple drain pipes install the pipes as shown in figure 9 Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 1 T joint converging drain pipes 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximatel...

Page 9: ... bush A and clamp the wires along with other wires using clamp A untightening the clip of clamp A by pressing After the connection tighten clamp A as before Unit wiring and remote controller wiring Remove the switch box lid 2 and pull the wires inside through the rubber bush B and connect to the terminal board for unit transmission wiring PRECAUTIONS see figure 13 1 Terminal board for unit transmi...

Page 10: ...ised control forced off and on off operation 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25mm2 Length Max 100m External terminal Contact that can ensure the minimum applicable load of 15V DC 10mA See figure 20 1 Inp...

Page 11: ...ll on one side and open by pulling toward yourself while holding it up NOTE Do not let go of the suction grill when opening or closing it If released the grill will spring back closed 2 Remove the air filters Push the air filters operation section with both hands in the direction indicated by the arrow undo the air filter clips and take out downward 1 Clip 2 Operation section 3 Air filter 3 Clean ...

Page 12: ...r polishing powder nor liquid insecticide It may cause discolouring or warping Do not let the indoor unit get wet It may cause electric shock or fire Clean the air suction grill when it is closed DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant oil and eventual other parts should be done in accordance with the relevant local and national regulations NOTES ...

Page 13: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE09081 1 ...

Reviews: