2

For the following items, take special care during
construction and check after installation is finished

Tick 

 when checked

2. Ceiling height

This indoor unit may installed on ceilings up to 3m in height.

3. Use suspension bolts for installation. Check whether the

ceiling is strong enough to support the weight of the
indoor unit. If there is a risk, reinforce the ceiling before
installing the unit.

(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring
reinforcing.)
Space required for installation see figure 1.

PREPARATIONS BEFORE INSTALLATION

1. Relation of ceiling opening to unit and suspension bolt

position. (see figure 2)

Model

A

B

C

D

FXYCP20,25,32

990

820

780

1030

FXYCP40,50

1205

1035

995

1245

FXYCP63

1390

1220

1180

1430

FXYCP80,125

1880

1710

1670

1920

1

Decoration panel

2

Ceiling opening

3

Indoor unit

4

Suspension bolt (x4)

5

Suspension pitch

6

Unit outside dimensions

7

Panel outside dimensions

2. Make the ceiling opening needed for installation where

applicable. (For existing ceilings.)

Refer to the paper pattern for installation for the ceiling
opening dimensions.

Create the ceiling opening required for installation. From
the side of the opening to the casing outlet, implement the
refrigerant and drain piping and wiring for remote controller
(unnecessary for wireless type) and indoor-outdoor unit
casing outlet. Refer to each piping or wiring section.

After making an opening in the ceiling, it may be necessary
to reinforce ceiling beams to keep the ceiling level and to
prevent it from vibrating. Consult the builder for details.

3. Install the suspension bolts. (use either a W3/8 or M10

size bolt.)

Use anchors for existing ceilings, and a sunken insert, sunken
anchors or other field supplied parts for new ceilings to
reinforce the ceiling in order to bear the weight of the unit.
Adjust clearance from the ceiling before proceeding further.
Installation example see figure 3.

1

Ceiling slab

2

Anchor

3

Long nut or turn-buckle

4

Suspension bolt

5

False ceiling

NOTE 

All the above parts are field supplied.

For other installation than standard installation, contact
your Daikin dealer for details.

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on
the name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the
indoor or outdoor units?

It may result in insufficient cooling.

Are refrigerant piping length and additional refrigerant charge
noted down?

The refrigerant charge in the system might not be clear.

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the
system and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site.
Be sure to fill out the appropriate installation specifications in
the chapter "What to do before operation" of the outdoor unit
operation manual.

SELECTING INSTALLATION SITE

1. Select an installation site where the following conditions

are fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service
can be ensured.

Where piping between indoor and outdoor units is possible
within the allowable limit. (Refer to the installation manual
of the outdoor unit.)

Keep indoor unit, outdoor unit, power supply wiring and
transmission wiring at least 1 meter away from televisions
and radios. This is to prevent image interference and noise
in those electrical appliances.
(Noise may be generated depending on the conditions
under which the electric wave is generated, even if 1 meter
is kept.)

Summary of Contents for FXYCP125K7V1

Page 1: ...INSTALLATION AND OPERATION MANUAL System air conditioner FXYCP20K7V1 FXYCP25K7V1 FXYCP32K7V1 FXYCP40K7V1 FXYCP50K7V1 FXYCP63K7V1 FXYCP80K7V1 FXYCP125K7V1 ...

Page 2: ...dos de acordo com as nossas instruções overholder følgende standard er eller andet andre retningsgivende dokument er forudsat at disse anvendes i henhold til vore instrukser respektive utrustning är utförd i överensstämmelse med och följer följande standard er eller andra normgivande dokument under förutsättning att användning sker i överensstämmelse med våra instruktioner respektive utstyr er i o...

Page 3: ...4 6 5 1 1 7 5 6 2 3 4 5 6 8 7 9 13 12 10 11 3 4 2 1 1 2 3 4 P 1 P 2 F 1 F 2 T 1 T 2 8 7 5 6 4 3 1 2 1 2 3 4 3 4 1 2 100 mm 1 9 8 5 6 10 11 12 1 2 7 13 1 3 6 4 5 2 1500 1500 1000 H 350 100 100 520 5 640 2 600 6 680 7 20 20 20 20 C B 2 6 A 7 5 D 1 2 3 4 ...

Page 4: ... T1 T2 1 2 3 4 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 3 5 2 4 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 15 16 18 17 20 19 14 21 F2 T1 T2 FORCED OFF 1 AIR CONDITIONER SETTING 2 4 3 1 7 3 4 1 2 5 6 9 8 ...

Page 5: ...described in this manual Caution concerning new refrigerant series The connectable outdoor units must be RSX Y P K or RSEYP K the outdoor units designed exclusively for R407C If outdoor units for R22 are connected the system will not work properly Precautions Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plas...

Page 6: ... parts are field supplied For other installation than standard installation contact your Daikin dealer for details Is the indoor unit fixed firmly The unit may drop vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit fully insulated Condensate water may drip Does drainage flow smoothly Condensate water may drip Does the power supply voltage corresp...

Page 7: ...before installation 5 Check if the unit is horizontally levelled Do not install the unit tilted The indoor unit is equipped with a built in drain pump and float switch If the unit is tilted against condensate flow the float switch may malfunction and cause water to drip Check if the unit is levelled at all four corners with a water level or a water filled vinyl tube as shown in figure 7 1 Water le...

Page 8: ...stand additional force To ensure a downward slope of 1 100 install hanging bars every 1 to 1 5m If unifying multiple drain pipes install the pipes as shown in figure 9 Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 1 T joint converging drain pipes 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximatel...

Page 9: ... bush A and clamp the wires along with other wires using clamp A untightening the clip of clamp A by pressing After the connection tighten clamp A as before Unit wiring and remote controller wiring Remove the switch box lid 2 and pull the wires inside through the rubber bush B and connect to the terminal board for unit transmission wiring PRECAUTIONS see figure 13 1 Terminal board for unit transmi...

Page 10: ...ised control forced off and on off operation 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25mm2 Length Max 100m External terminal Contact that can ensure the minimum applicable load of 15V DC 10mA See figure 20 1 Inp...

Page 11: ...ll on one side and open by pulling toward yourself while holding it up NOTE Do not let go of the suction grill when opening or closing it If released the grill will spring back closed 2 Remove the air filters Push the air filters operation section with both hands in the direction indicated by the arrow undo the air filter clips and take out downward 1 Clip 2 Operation section 3 Air filter 3 Clean ...

Page 12: ...r polishing powder nor liquid insecticide It may cause discolouring or warping Do not let the indoor unit get wet It may cause electric shock or fire Clean the air suction grill when it is closed DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant oil and eventual other parts should be done in accordance with the relevant local and national regulations NOTES ...

Page 13: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWE09081 1 ...

Reviews: