background image

8 Troubleshooting

Installation and operation manual

10

FXSN50~112A2VEB

CO

 Conveni-Pack: indoor unit

4P602815-1C – 2020.05

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do  NOT  use  cleaning  materials  other  than  those

recommended by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The  refrigerant  R744  (CO

2

)  inside  the  unit  is  odourless,

non-flammable and, in moderate concentrations, non-toxic,
and normally does NOT leak.

If  the  refrigerant  leaks  in  the  room,  it  may  have  negative
effects 

on 

its 

occupants 

(asphyxiant 

in 

high

concentrations). Ventilate the room and contact the dealer
where you purchased the unit (see 

"7.3.1 About refrigerant

leak detection" 

[

4

 10]).

Do  NOT  use  the  unit  until  a  service  person  confirms  that
the  part  from  which  the  refrigerant  leaked  has  been
repaired.

7.3.1

About refrigerant leak detection

In  order  to  detect  refrigerant  leaks,  a  CO

2

  refrigerant  leak  detector

(field  supply)  MUST  be  installed.  The  CO

2

  refrigerant  leak  detector

may  require  annual  tests.  For  more  details,  see  the  documentation
of the installed device.

In case a CO

2

 refrigerant leak is detected

▪ the fan of the indoor unit is stopped to prevent the refrigerant from

being spread,

▪ the  user  interface  displays  error  code  A0  or  U9  (

  for  the

Madoka; to display error codes, refer to the reference guide of the
Madoka),

▪ a  warning  sound  will  come  from  the  user  interface  (  only  for

Madoka with buzzer, see option list) or from another safety alarm
in combination with a CO

refrigerant leak detector (field supply).

Actions required by the user

1

Ventilate  the  room  and  immediately  contact  the  dealer  where
you purchased the unit. Do NOT use the unit before the fault is
fixed.

Actions required by the installer or the service person

INFORMATION

During  detection  of  the  refrigerant  leakage,  the  contact
between  terminals  T1  and  T2  disconnects.  During  normal
operation,  the  contact  between  terminals  T1  and  T2  is
closed (acting as a short circuit).

1

If  field  supplied  stop-valves  are  NOT  installed:  Close  the  stop
valves of the gas and liquid pipe on the outdoor unit.

2

If  field  supplied  shut-off  valves  are  installed:  If  the  refrigerant
leak  to  the  room  has  stopped,  you  can  use  the  air  conditioner
for other rooms where the refrigerant leak did NOT occur.

3

Locate  and  repair  the  cause  of  the  refrigerant  leak.  If
necessary, replace the indoor unit.

4

Refill the refrigerant if needed.

5

Perform manual power reset and resume operation.

NOTICE

After the refrigerant leakage is detected, the unit will send
a  signal  at  regular  intervals  to  confirm  if  the  CO

2

concentration  is  at  a  safe  level.  Even  when  the  CO

2

concentration is at a safe level, do NOT resume operation
before the fault is fixed and the refrigerant is refilled.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT function properly.

Turn OFF all main power
supply switches to the
unit.

If water leaks from the unit.

Stop operation.

The operation switch does NOT function
properly.

Turn OFF the power
supply.

If the user interface displays 

 or an

error code.

Notify your installer and
report the error code. To
display error codes, see
the reference guide of the
user interface.

The user interface displays error code

A0 or U9 (or 

), the fan stops and you

can hear a warning sound from the user
interface (in case of Madoka) or from
another safety alarm in combination
with a gas detection device (if installed).

A refrigerant leak may be
detected (see 

"7.3.1 About

refrigerant leak
detection" 

[

4

 10]).

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until power is restored. If a power failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

The system stops
immediately after
starting operation.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check  if  the  air  filter  is  clogged  (see

"7.2.2 To clean the air filter" 

[

4

 9]).

Summary of Contents for FXSN50A2VEB

Page 1: ...Installation and operation manual CO Conveni Pack indoor unit English Installation and operation manual CO Conveni Pack indoor unit FXSN50A2VEB FXSN71A2VEB FXSN112A2VEB...

Page 2: ...ie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi...

Page 3: ...ectrical wiring to the indoor unit 19 13 3 To connect appropriate measures for appliances filled with CO 20 14 Commissioning 20 14 1 Checklist before commissioning 20 14 2 To perform a test run 21 14...

Page 4: ...11 2 2 Guidelines when installing the ducting 415 CAUTION Make sure the installation of the duct does NOT exceed the setting range of the external static pressure for the unit Refer to the technical d...

Page 5: ...te the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are marked...

Page 6: ...Chemicals could collect in the unit and endanger the health of people who are hypersensitive to chemicals CAUTION NEVER expose little children plants or animals directly to the airflow WARNING Do NOT...

Page 7: ...ubleshooting see 8 Troubleshooting 410 WARNING Stop operation and shut off the power if anything unusual occurs burning smells etc Leaving the unit running under such circumstances may cause breakage...

Page 8: ...nt Target temperature for the Cooling Heating and Auto operation modes Setback A function that keeps the room temperature in a specific range when the system is turned off by the user the schedule fun...

Page 9: ...igh places 7 2 Cleaning the air filter and air outlet 7 2 1 To clean the air outlet WARNING Do NOT let the indoor unit get wet Possible consequence Electric shock or fire NOTICE Do NOT use gasoline be...

Page 10: ...form manual power reset and resume operation NOTICE After the refrigerant leakage is detected the unit will send a signal at regular intervals to confirm if the CO2 concentration is at a safe level Ev...

Page 11: ...sed If the operation lamp lights the air conditioner is in normal condition It does not restart immediately because one of its safety devices actuates to prevent the air conditioner from being overloa...

Page 12: ...ional installation site requirements for CO refrigerant 413 Make sure to install a CO2 leak detector field supply and enable the function for refrigerant leak detection see 15 1 Field setting 421 11 1...

Page 13: ...efrigerant leak detector WARNING Install the unit only in locations where the doors of the occupied space are not tight fitting WARNING When using safety shut off valves make sure to install measures...

Page 14: ...efrigerant charge limit B Room volume a Installation is not allowed b 2 appropriate measures required c 1 appropriate measures required d No measure required INFORMATION Even if there is no refrigerat...

Page 15: ...ter onto the drain pan or the air filter If the metal duct passes through a metal lath wire lath or metal plate of the wooden structure separate the duct and wall electrically Install the outlet grill...

Page 16: ...sation Insulate the complete drain piping in the building Combining drain pipes You can combine drain pipes Make sure to use drain pipes and T joints with the correct gauge for the operating capacity...

Page 17: ...or the service manual of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet completed 417 11 3 R...

Page 18: ...n of pipes No other types of connections are allowed Expanding of pipes is not allowed 1 Insert the field pipe into the piping on the indoor unit side 2 Connect refrigerant piping to the unit using on...

Page 19: ...wiring and power supply wiring may cross but may NOT run parallel 1 Remove the service cover 2 User interface cable Route the cable through the frame connect the cable to the terminal block symbols P1...

Page 20: ...sures to the indoor unit terminal block symbols T1 T2 3 If the CO2 refrigerant leak detector is installed enable the function for refrigerant leak detection as described in 15 1 Field setting 421 P1P2...

Page 21: ...ke the following field settings so that they correspond with the actual installation setup and with the needs of the user Bottom suction or rear suction installation setting External static pressure s...

Page 22: ...al data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentic...

Page 23: ...eaker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant...

Page 24: ...4P602815 1C 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: