Installation of drain piping

Install the drain piping as shown in figure and take measures against
condensation. Improperly rigged piping could lead to leaks and
eventually wet furniture and belongings.

Install the drain pipes.
-

Keep piping as short as possible and slope it downwards at a 
gradient of at least 1/100 so that air may not remain trapped 
inside the pipe.

-

Keep pipe size equal to or greater than that of the connecting 
pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

-

Push the supplied drain hose as far as possible over the 
drain socket.

-

Tighten the metal clamp until the screw head is less than 
4 mm from the metal clamp part as indicated in the 
illustration.

-

After the testing of drain piping is finished, attach the drain 
sealing pad (4) supplied with the unit over the uncovered part 
of the drain socket (= between drain hose and unit body).

-

Wrap the supplied large sealing pad over the metal clamp 
and drain hose to insulate and fix it with clamps.

-

Insulate the complete drain piping inside the building (field 
supply).

-

If the drain hose cannot be sufficiently set on a slope, fit the 
hose with drain raising piping (field supply).

How to perform piping 

(See figure 7)

1

Connect the drain hose to the drain raising pipes, and insulate
them.

2

Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.

Precautions
-

Install the drain raising pipes at a height of less than 675 mm.

-

Install the drain raising pipes at a right angle to the indoor 
unit and no more than 300 mm from the unit.

-

To prevent air bubbles, install the drain hose level or slightly 
tilted up (

75 mm).

Testing of drain piping

After piping work is finished, check if drainage flows smoothly.

Add approximately 1 

l of water gradually through the air

discharge outlet.
Method of adding water. See 

figure 11

.

Check the drainage flow.

In case electric wiring work is finished

Check drainage flow during COOL running, explained in 

"Test

operation" on page 9

.

In case electric wiring work is not finished

-

Remove the control box lid. Connect the power supply
firmly to the terminal. See 

figure 10

.

-

Reattach the control box lid and turn on the power.

-

Do not touch the drain pump. It may result in electric
shock.

1

Hanging bar

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)

4

Drain sealing pad (supplied with the unit)

5

Large sealing pad (supplied with the unit)

6

Drain piping (field supply)

1-1.5 m

1

2

1

1

6

2

4

3

5

4 mm

3
5

2

A

A'

A-A'

1

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe (nominal diameter of vinyl pipe = 25 mm)

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To  ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 9

.  Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

Plastic watering can (tube should be about 100 mm long)

2

Service drain outlet (with rubber plug) (Use this outlet to 
drain water from the drain pan)

3

Drain pump location

4

Drain pipe

5

Drain socket (water flow view point)

1

Control box lid

2

Power supply wiring

3

Power supply terminal block

4

Clamp (field supply)

5

Unit transmission wiring

6

Terminal block for transmission wiring

7

Opening for cables

8

Wiring diagram label
(on the back side of the control box lid)

9

Earth cable

10

Remote controller wiring

Summary of Contents for FXFQ20P8VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20P8VEB FXFQ25P8VEB FXFQ32P8VEB FXFQ40P8VEB FXFQ50P8VEB FXFQ63P8VEB FXFQ80P8VEB FXFQ100P8VEB FXFQ125P8VEB System air conditioners...

Page 2: ...1 1 2 1500 1500 3 2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 80 100 mm 2 7 2 2 4 5 6 5 10 7 9 4 3 5 1 2 2 2 1 5 10 4 4 1 2...

Page 3: ...til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 va...

Page 4: ...tion Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the...

Page 5: ...te controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent light...

Page 6: ...lder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing and on the paper pattern for installation A...

Page 7: ...ooking stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazi...

Page 8: ...if drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water See figure 11 Check the drainage flow In case electric wiring work is finis...

Page 9: ...rminal While doing this pull the wires inside through the hole in the casing and clamp the wires along with other wires using a clamp as indicated in the figure Unit transmission wiring and remote con...

Page 10: ...Incomplete connections could result in overheating and in the worse case electric shock or fire WIRING EXAMPLE Fit the power supply wiring of each unit with a switch and fuse as shown in figure 17 Com...

Page 11: ...ay Do not display 5 Information to I manager I touch controller Only unit sensor value or remote sensor value if installed Sensor value as set by 10 2 0X or 10 6 0X 6 Thermostat sensor in group contro...

Page 12: ...r filter back in place perform actions 2 to 4 in the illustration in reverse order Attach the air filter to the suction grille by hanging it over the projected portion above the suction grille Press t...

Page 13: ...nce with relevant local and national legislation NOTES NOTE Do not use gasoline benzene thinner polishing powder liquid insecticide It may cause discoloring or warping Do not let the indoor unit get w...

Page 14: ...ed H4P Light emmiting diode Defrost Orange SS1 Selector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector a...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...4PW44997 1 Copyright Daikin...

Reviews: