background image

FXFQ20~125P8VEB
VRV System air conditioners
4PW44997-1

Installation and operation manual

4

R

EFRIGERANT

 

PIPING

 

WORK

For refrigerant piping of outdoor unit, refer to the installation manual
supplied with the outdoor unit.

Execute heat insulation work completely on both sides of the gas
piping and the liquid piping. Otherwise, this can sometimes result in
water leakage.

Before rigging tubes, check which type of refrigerant is used.

Use a pipe cutter and flare suitable for the used refrigerant.

To prevent dust, moisture or other foreign matter from infiltrating
the tube, either pinch the end, or cover it with tape.

Use copper alloy seamless pipes (ISO 1337).

The outdoor unit is charged with refrigerant.

To  prevent water leakage, execute heat insulation work
completely on both sides of the gas and liquid piping. When
using a heat pump, the temperature of the gas piping can reach
up to approximately 120°C, use insulation which is sufficiently
heat resistant.

Be sure to use both a spanner and torque wrench together when
connecting or disconnecting pipes to/from the unit.

Do not mix anything other than the specified refrigerant, such as
air, etc..., inside the refrigerant circuit.

Refer to 

Table 1

 for the dimensions of flare nut spaces and the

appropriate tightening torque. (Overtightening may damage the
flare and cause leaks.)

Table 1

When connecting the flare nut, coat the flare both inside and
outside with ether oil or ester oil and initially tighten by hand 3 or
4 turns before tightening firmly. 
Coat here with ether oil or ester oil

If the refrigerant gas leaks during the work, ventilate the area. A
toxic gas is emitted by the refrigerant gas being exposed to a fire.

Make sure there is no refrigerant gas leak. A toxic gas may be
released by the refrigerant gas leaking indoor and being
exposed to flames from an area heater, cooking stove, etc.

Finally, insulate as shown in the figure below (use the supplied
accessory parts)

Piping insulation procedure

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

All field piping must be provided by a licensed refrigeration
technician and must comply with the relevant local and
national codes.

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe gauge

Tightening torque

Flare dimension A 

(mm)

Flare shape

Ø6.4

14.2~17.2 N•m

8.7~9.1

Ø9.5

32.7~39.9 N•m

12.8~13.2

Ø12.7

49.5~60.3 N•m

16.2~16.6

Ø15.9

61.8~75.4 N•m

19.3~19.7

1

2

4

3

R0.4~0.8

45

° ±

2

90

°±

2

A

Gas piping

Liquid piping

1

Piping insulation material (field supply)

2

Flare nut connection

3

Insulation for fitting (delivered with the unit)

4

Piping insulation material (main unit)

5

Main unit

6

Clamp (field supply)

7

Medium 1 sealing pad for gas piping (delivered with the unit)
Medium 2 sealing pad for liquid piping (delivered with the unit)

A

Turn seams up

B

Attach to base

C

Tighten the part other than the piping insulation material

D

Wrap over from the base of the unit to the top of the flare nut 
connection

For local insulation, be sure to insulate local piping all
the way into the pipe connections inside the unit.

Exposed piping may cause condensation or may
cause burns when touched.

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1
2

5

3

4
5

1

Liquid pipe

2

Gas pipe

3

Insulation for fitting for liquid 
pipe

4

Insulation for fitting for gas 
pipe

5

Clamps 
(use 2 clamps per insulation)

A

B

D

C

7

1

2

3

4

5

6

6

A

B

C

1

2

3

4

5

6

6

D

7

1

2

3

4

5

6

6

Summary of Contents for FXFQ20P8VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20P8VEB FXFQ25P8VEB FXFQ32P8VEB FXFQ40P8VEB FXFQ50P8VEB FXFQ63P8VEB FXFQ80P8VEB FXFQ100P8VEB FXFQ125P8VEB System air conditioners...

Page 2: ...1 1 2 1500 1500 3 2 4 5 1 50 100 2 1 3 4 950 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 4 3 1 2 4 100 80 100 mm 2 7 2 2 4 5 6 5 10 7 9 4 3 5 1 2 2 2 1 5 10 4 4 1 2...

Page 3: ...til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 va...

Page 4: ...tion Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting the installation site use the...

Page 5: ...te controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible away from fluorescent light...

Page 6: ...lder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing and on the paper pattern for installation A...

Page 7: ...ooking stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazi...

Page 8: ...if drainage flows smoothly Add approximately 1 l of water gradually through the air discharge outlet Method of adding water See figure 11 Check the drainage flow In case electric wiring work is finis...

Page 9: ...rminal While doing this pull the wires inside through the hole in the casing and clamp the wires along with other wires using a clamp as indicated in the figure Unit transmission wiring and remote con...

Page 10: ...Incomplete connections could result in overheating and in the worse case electric shock or fire WIRING EXAMPLE Fit the power supply wiring of each unit with a switch and fuse as shown in figure 17 Com...

Page 11: ...ay Do not display 5 Information to I manager I touch controller Only unit sensor value or remote sensor value if installed Sensor value as set by 10 2 0X or 10 6 0X 6 Thermostat sensor in group contro...

Page 12: ...r filter back in place perform actions 2 to 4 in the illustration in reverse order Attach the air filter to the suction grille by hanging it over the projected portion above the suction grille Press t...

Page 13: ...nce with relevant local and national legislation NOTES NOTE Do not use gasoline benzene thinner polishing powder liquid insecticide It may cause discoloring or warping Do not let the indoor unit get w...

Page 14: ...ed H4P Light emmiting diode Defrost Orange SS1 Selector switch MAIN SUB SS2 Selector switch wireless address set Connector for optional parts X24A Connector wireless remote controller X33A Connector a...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...4PW44997 1 Copyright Daikin...

Reviews: