Daikin FXFQ100AVEB Installation And Operation Manual Download Page 9

Installation and operation manual

6

-

Tighten the metal clamp until the screw head is less than 
4 mm from the metal clamp part as indicated in the 
illustration.

-

After the testing of drain piping is finished, attach the drain 
sealing pad (4) supplied with the unit over the uncovered 
part of the drain socket (= between drain hose and unit 
body).

-

Wrap the supplied large sealing pad over the metal clamp 
and drain hose to insulate and fix it with clamps.

-

Insulate the complete drain piping inside the building (field 
supply).

-

If the drain hose cannot be sufficiently set on a slope, fit 
the hose with drain raising piping (field supply).

How to perform piping 

(See figure 7)

1

Connect the drain hose to the drain raising pipes, and
insulate them.

2

Connect the drain hose to the drain outlet on the indoor unit,
and tighten it with the clamp.

Precautions
-

Install the drain raising pipes at a height of less than 
675 mm.

-

Install the drain raising pipes at a right angle to the indoor 
unit and no more than 300 mm from the unit.

-

To prevent air bubbles, install the drain hose level or 
slightly tilted up (

75 mm).

Testing of drain piping

After piping work is finished, check if drainage flows smoothly.

Add approximately 1 l of water gradually through the air
discharge outlet.
Method of adding water. See 

figure 11

.

Check the drainage flow.

In case electric wiring work is finished

Check drainage flow during COOL running, explained in 

"Test operation"

on page 9

.

In case electric wiring work is not finished

-

Remove the control box lid. Connect the power supply firmly to
the terminal. See 

figure 10

.

-

Reattach the control box lid and turn on the power.

-

Do not touch the drain pump. It may result in electric shock.

-

Confirm the drain operation looking at the drain socket.

-

After checking the drainage flow, turn off the power, remove the
control box lid and disconnect the power supply from the
terminal again.

-

Reattach the control box lid.

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)

4

Drain sealing pad (supplied with the unit)

5

Large sealing pad (supplied with the unit)

6

Drain piping (field supply)

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe (nominal diameter of vinyl pipe = 25 mm)

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

2

1

1

6

2

4

3

5

4 mm

3
5

2

A

A'

A-A'

1

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 9

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

Plastic watering can (tube should be about 100 mm long)

2

Service drain outlet (with rubber plug) (Use this outlet to 
drain water from the drain pan)

3

Drain pump location

4

Drain pipe

5

Drain socket (water flow view point)

1

Control box lid

2

Power supply wiring

3

Power supply terminal block

4

Clamp (field supply)

5

Unit transmission wiring

6

Terminal block for transmission wiring

7

Opening for cables

8

Wiring diagram label
(on the back side of the control box lid)

9

Earth cable

10

Remote controller wiring

Power supply terminal block (3)

L

N

EN3P320142-1F.book  Page 6  Tuesday, October 3, 2017  2:46 PM

Summary of Contents for FXFQ100AVEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20AVEB FXFQ25AVEB FXFQ32AVEB FXFQ40AVEB FXFQ50AVEB FXFQ63AVEB FXFQ80AVEB FXFQ100AVEB FXFQ125AVEB System air conditioners...

Page 2: ...valorado positivamente por B de acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer p...

Page 3: ...4 2 1 950 950 860 910 840 780 860 910 4 125 130 0 3 3 1 1 840 910 840 910 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 5 1 2 2 2 1 4 70 90 mm 0 15 m...

Page 4: ...pervision If the supply cord is damaged it must be replaced by the manufacturer a service agent or similarly qualified persons in order to avoid a hazard Do not install or operate the unit in rooms me...

Page 5: ...TO THE MODELS AND VALUES STATED IN THIS TABLE Models A B C D E FXFQ20AVEB 1 8 0 4 2 5 0 038 49 FXFQ25AVEB 2 1 0 7 3 2 0 038 49 FXFQ32AVEB 2 8 0 8 4 0 038 49 FXFQ40AVEB 3 4 1 1 5 0 038 51 FXFQ50AVEB 4...

Page 6: ...r discharge in 3 directions it is necessary to make field settings by means of the remote controller and to close the air outlet s Refer to the installation manual of the optional blocking pad kit and...

Page 7: ...gure 8 Adjust the height of the unit until it matches the indication in figure 8 3 Adjust the unit to the right position for installation Refer to Preparations before installation on page 3 4 Check if...

Page 8: ...aks and eventually wet furniture and belongings Install the drain pipes Keep piping as short as possible and slope it downwards at a gradient of at least 1 100 so that air may not remain trapped insid...

Page 9: ...rol box lid and turn on the power Do not touch the drain pump It may result in electric shock Confirm the drain operation looking at the drain socket After checking the drainage flow turn off the powe...

Page 10: ...er connection Attach the small sealing supplied with the unit around the cables to prevent infiltrating of water from the outside into the unit If two or more cables are used divide the small sealing...

Page 11: ...s no space between the unit body and decoration panel Otherwise air may leak through the gap and cause dewdrop Field setting Field setting must be made from the remote controller in accordance with th...

Page 12: ...high places After a long use check the unit stand and fitting for damage If damaged the unit may fall and cause injury Do not touch the heat exchanger fins The fins are sharp and could result in cutti...

Page 13: ...dry thoroughly See figure 24 5 Install the air filter back in place perform actions 2 to 4 in the illustration in reverse order 6 Reattach the suction grille by performing procedure step 2 in reverse...

Page 14: ...DEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P320142 1F 2017 08 Copyright 2012 Daikin...

Reviews: