background image

 

Installation and operation manual

7

Electric wiring work

General instructions

All field supplied parts and materials and electric works must conform to
local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the unit body to wire the
outdoor unit, indoor units and the remote controller. For details on
hooking up the remote controller, refer to the "Installation manual of the
remote controller".

All wiring must be performed by an authorized electrician.

Attach the earth leakage circuit breaker and fuse to the power supply
line.

A main switch or other means for disconnection, having a contact
separation in all poles, must be incorporated in the fixed wiring in
accordance with relevant local and national legislation.
Note that the operation will restart automatically if the main power
supply is turned off and then turned back on again.

This system consists of multiple indoor units. Mark each indoor unit as
unit A, unit B..., and be sure the terminal block wiring to the outdoor unit
and BS unit are properly matched. If wiring and piping between the
outdoor unit and an indoor unit are mismatched, the system may cause
a malfunction.

Be sure to ground the air conditioner.

Do not connect the ground wire to:
-

gas pipes: might cause explosions or fire if gas leaks.

-

telephone ground wires or lightning rods: might cause abnormally 
high electric potential in the ground during lightning storms.

-

plumbing pipes: no grounding effect if hard vinyl piping is used.

Electrical characteristics

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)

Specifications for field supplied fuses and wire

Wiring example and how to set the remote 
controller

How to connect wiring 

(See figure 10)

Power supply wiring
Remove the control box lid (1) and connect the wires to the power
supply terminal block inside (L, N) and connect the ground wire to the
grounding terminal. While doing this, pull the wires inside through the
hole in the casing and clamp the wires along with other wires using a
clamp as indicated in the figure.

Unit transmission wiring and remote controller wiring
Remove the control box lid (1) and pull the wires inside through the hole
in the casing and connect to the terminal block for unit transmission
wiring (F1, F2) and remote controller wiring (P1, P2). Securely fix the
wiring using a clamp as indicated in the figure.

After connection
Attach the small sealing (supplied with the unit) around the cables to
prevent infiltrating of water from the outside into the unit. If two or more
cables are used, divide the small sealing into the required number of
pieces and wrap them around all the cables.

Attach the control box lid.

Precautions

1

Observe the notes mentioned below when wiring to the power supply
terminal block.

-

Use a round crimp-style terminal for insulation sleeve for connection 
to the terminal block for wiring the units. When none are available, 
follow the instructions below.

-

Do not connect wires of different gauge to the same power supply 
terminal. (Looseness in the connection may cause overheating.)

-

When clamping wiring, use the clamps (delivered with the unit) to 
prevent outside pressure being exerted on the wiring connections. 
Tie up firmly. When doing the wiring, make sure the wiring is neat 
and does not cause the control box to stick up. Close the cover 
firmly.

-

When connecting wires of the same gauge, connect them according 
to the figure.

Use the specified electric wire. Connect the wire securely to the terminal.
Lock the wire down without applying excessive force to the terminal. Use
torques according to the table below.

-

When attaching the control box lid, make sure not to pinch any 
wires.

-

After all wiring connections are done, fill in any gaps in the casing 
wiring holes with putty or insulation material (field supply) thus to 
prevent small animals or dirt from entering the unit from outside and 
causing short circuits in the control box.

Model

Hz

Volts

Voltage range

FXFQ20~125

50 / 60

220-240 / 220

min. 198-max. 264 / 

min. 198-max. 242

power supply

Fan motor

Model

MCA

MFA

KW

FLA

FXFQ20~32

0.4

16 A

0.056

0.3

FXFQ40

0.5

16 A

0.056

0.4

FXFQ50

0.6

16 A

0.056

0.5

FXFQ63

0.9

16 A

0.056

0.7

FXFQ80

0.9

16 A

0.120

0.7

FXFQ100

1.4

16 A

0.120

1.1

FXFQ125

1.9

16 A

0.120

1.5

NOTE

For details, refer to "Electrical data".

Power supply wiring

Model

Field fuses

Wire

Size

FXFQ20~125

16 A

H05VV-U3G

Local codes

Transmission wiring

Model

Wire

Size

FXFQ20~125

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to 

"Wiring example" on page 8

.

Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:

Outdoor unit - indoor unit: max. 1000 m 
(total wiring length: 2000 m)

Indoor unit - remote controller: max 500 m

Tightening torque (N•m)

Terminal block for unit transmission and 
remote controller

0.79~0.97

Terminal block for power supply

1.18~1.44

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

EN3P320142-1F.book  Page 7  Tuesday, October 3, 2017  2:46 PM

Summary of Contents for FXFQ100AVEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXFQ20AVEB FXFQ25AVEB FXFQ32AVEB FXFQ40AVEB FXFQ50AVEB FXFQ63AVEB FXFQ80AVEB FXFQ100AVEB FXFQ125AVEB System air conditioners...

Page 2: ...valorado positivamente por B de acuerdo con el Certi cado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certi cato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer p...

Page 3: ...4 2 1 950 950 860 910 840 780 860 910 4 125 130 0 3 3 1 1 840 910 840 910 1 1 5 35 35 3 5 0 75 675 850 175 300 mm 1 1 5 m 2 3 1 5 6 100 mm 1 0 675 mm 1 3 3 1 2 4 100 4 3 5 1 2 2 2 1 4 70 90 mm 0 15 m...

Page 4: ...pervision If the supply cord is damaged it must be replaced by the manufacturer a service agent or similarly qualified persons in order to avoid a hazard Do not install or operate the unit in rooms me...

Page 5: ...TO THE MODELS AND VALUES STATED IN THIS TABLE Models A B C D E FXFQ20AVEB 1 8 0 4 2 5 0 038 49 FXFQ25AVEB 2 1 0 7 3 2 0 038 49 FXFQ32AVEB 2 8 0 8 4 0 038 49 FXFQ40AVEB 3 4 1 1 5 0 038 51 FXFQ50AVEB 4...

Page 6: ...r discharge in 3 directions it is necessary to make field settings by means of the remote controller and to close the air outlet s Refer to the installation manual of the optional blocking pad kit and...

Page 7: ...gure 8 Adjust the height of the unit until it matches the indication in figure 8 3 Adjust the unit to the right position for installation Refer to Preparations before installation on page 3 4 Check if...

Page 8: ...aks and eventually wet furniture and belongings Install the drain pipes Keep piping as short as possible and slope it downwards at a gradient of at least 1 100 so that air may not remain trapped insid...

Page 9: ...rol box lid and turn on the power Do not touch the drain pump It may result in electric shock Confirm the drain operation looking at the drain socket After checking the drainage flow turn off the powe...

Page 10: ...er connection Attach the small sealing supplied with the unit around the cables to prevent infiltrating of water from the outside into the unit If two or more cables are used divide the small sealing...

Page 11: ...s no space between the unit body and decoration panel Otherwise air may leak through the gap and cause dewdrop Field setting Field setting must be made from the remote controller in accordance with th...

Page 12: ...high places After a long use check the unit stand and fitting for damage If damaged the unit may fall and cause injury Do not touch the heat exchanger fins The fins are sharp and could result in cutti...

Page 13: ...dry thoroughly See figure 24 5 Install the air filter back in place perform actions 2 to 4 in the illustration in reverse order 6 Reattach the suction grille by performing procedure step 2 in reverse...

Page 14: ...DEBRIDGE R RESISTOR DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS...

Page 15: ...IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1...

Page 16: ...3P320142 1F 2017 08 Copyright 2012 Daikin...

Reviews: