4. PREPARATIONS BEFORE INSTALLATION

(1) Confirm the positional relationship between the unit

and suspension bolts. (Refer to Fig. 2)

Install the inspection opening on the control box side where
maintenance and inspection of the control box and drain
pump are easy.  Install the inspection opening also in the
lower part of the unit.

(length: mm)

(2) Make sure the range of the unit’s external static pres-

sure is not exceeded.

(See the technical documentation for the range of the
external static pressure setting.)

(3) Open the installation hole. (Pre-set ceilings)

Once the installation hole is opened in the ceiling where

the unit is to be installed, pass refrigerant piping, drain

piping, transmission wiring, and remote controller wiring

(It is not necessary if using a wireless remote controller)

to the unit’s piping and wiring holes.

See “

6. REFRIGERANT PIPING WORK

”, “

7. DRAIN

PIPING WORK

”, and “

10.

 

WIRING EXAMPLE

”.

After opening the ceiling hole, make sure ceiling is level if 

needed. It might be necessary to reinforce the ceiling

frame to prevent shaking.

Consult an architect or carpenter for details.

(4) Install the suspension bolts.

(Use W3/8 to M10 suspension bolts.)

Use a hole-in-anchor for existing ceilings, and a sunken

insert, sunken anchor or other part to be procured in the

field to reinforce the ceiling to bearing the weight of the unit

for new ceiling. 

(Refer to Fig. 3)

(5) In case of bottom suction

(1) Remove the chamber lid. (7 locations)

(2) Reattached the removed chamber lid in the orientation

shown in Fig. 4. (7 locations)

(3) Attach the air filter (accessory) in the manner shown in

the diagram.

The four holes which cannot be covered by the air filter 

should be covered with commercially available tape.

Model

A

B

15-20-25-32  type

750

740

40-50  type

950

940

63  type

1150

1140

B

A

620

500

450×450

620

A

Drain pump

SERVICE SPACE

Fig. 2

Inspection door

(Ceiling opening)

Allow view 

Control box

Air inlet

(length : mm)

Suspension 
bolt pitch

Air outlet

Ceiling

(Inspection 

opening size)

(Suspension bolt pitch)

Fig. 3

Ceiling slab

Indoor unit

Anchor bolt

Long nut or turn-buckle

Suspension bolt

Note: All the above parts are field supplied.

(1)

(2)

Chamber lid

Chamber lid

Air discharge

Air inlet

Air discharge

Fig. 4

Air inlet

4PEN325876-1F.book  Page 4  Thursday, April 20, 2017  8:20 AM

Summary of Contents for FXDQ20A3VEB

Page 1: ...INSTALLATION MANUAL FXDQ15A3VEB FXDQ20A3VEB FXDQ25A3VEB FXDQ32A3VEB FXDQ40A3VEB FXDQ50A3VEB FXDQ63A3VEB System Inverter Air Conditioners 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM...

Page 2: ...e acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o...

Page 3: ...lation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified pers...

Page 4: ...the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an...

Page 5: ...ould be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If ther...

Page 6: ...prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anch...

Page 7: ...a ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the t...

Page 8: ...Use phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluo...

Page 9: ...Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain pipi...

Page 10: ...on area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use a...

Page 11: ...o not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of p...

Page 12: ...ower sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring...

Page 13: ...stem For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 1...

Page 14: ...achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to th...

Page 15: ...n man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote...

Page 16: ...GHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THE...

Page 17: ...4P325876 1H book Page 1 Thursday April 27 2017 10 43 AM...

Page 18: ...4P325876 1F 2017 02 Copyright 2012 Daikin 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM...

Reviews: