background image

FXCQ20~125M8V3B
VRV System air conditioners
4PW25081-1A

Installation and operation manual

6

Summary of field settings

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and
the other to "SUB".

Main/sub changeover

1.

Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. 

(See figure 17)

(The remote controller PC board is attached to the upper part of
the remote controller.)

2.

Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". 

(See figure 18)

(Leave the switch of the other remote controller set to "M".)

Computerised control (forced off and on/off operation)

1.

Wire specifications and how to perform wiring.

Connect input from outside to terminals T1 and T2 of the terminal
board (remote controller to transmission wiring).

See 

figure 19

.

2.

Actuation

The following table explains "forced off" and "on/off operations" in
response to input A.

3.

How to select forced off and on/off operation

Turn the power on and then use the remote controller to select
operation.

Set the remote controller to the field set mode. For details, refer to
the chapter "How to set in the field", in the remote controller
manual.

When in the field set mode, select mode No. 12, then set the first
code (switch) No. to ´1´. Then set second code (position) No. to
´01´ for forced off and to ´02´ for on/off operation. (forced off at
factory set.) 

(See figure 20)

Centralized control

For centralized control, it is necessary to designate the group
No. For details, refer to the manual of each optional controller for
centralized control.

Mode 

No.

(Note 1)

First 

code 

No.

Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light
= Setting to define 
time between 2 filter 
cleaning display 
indications. (When 
contamination is 
high, setting can be 
changed to half the 
time inbetween 2 
filter cleaning 
display indications.)

Ultra-long-
life filter

Light

±10,000 hrs.

Hea

vy

±5,000 hrs.

Long-life 
filter

±2,500 hrs.

±1,250 hrs.

Standard 
filter

±200 hrs.

±100 hrs.

1

Long-life filter type
Change the setting when ultra-
long-life filter is installed.
This setting is important for time 
between 2 filter cleaning display 
indications (refer to 10-0-0X).

Long-life filter

Ultra-long-life 
filter

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only. 
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

5

Information to I-manager, 
I-touch controller

Only unit sensor 
value (or remote 
sensor value if 
installed).

Sensor value as 
set by 10-2-0X 
or 10-6-0X.

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit senor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on + 
compressor run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

2

Thermostat differential 
changeover = Setting when 
remote sensor is used.

1°C

0.5°C

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure

Disabled

Enabled

9

Fixed cool/heat master

Disabled

Enabled

13 

(23)

4

Airflow direction range setting
This setting is to be changed 
when range of swing flap 
movement needs to be 
changed.

Upper

Normal

Lower

15 

(25)

3

Drain pump ope 
humidifier interlock

Equipped

Not equipped

Note 1 :

Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 
indoor units can also be set individually.

Note 2 :

Factory settings of the Second code No. are marked in grey backgrounds.

Note 3 :

Only use in combination with optional remote sensor or when setting 10-2-03 is used.

Note 4 :

If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.

Note 5 :

If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 
10-2-02 or 10-2-03 have priority.

Note 6 :

If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have 
priority.

Note 7 :

More settings for Differential automatic change over temperatures are:
Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

1

Remote controller PC board

2

Factory setting

3

Only one remote controller needs to be changed

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum applicable load 

of 15 V DC, 10 mA

1

Input A

Forced off

on/off operation

Input "on" stops operation

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control

input on 

 off: turns off the unit 

(by remote controller)

1

Second code No.

2

Mode No.

3

First code No.

4

Field set mode

Summary of Contents for FXCQ20M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXCQ20M8V3B FXCQ25M8V3B FXCQ32M8V3B FXCQ40M8V3B FXCQ50M8V3B FXCQ63M8V3B FXCQ80M8V3B FXCQ125M8V3B System air conditioners...

Page 2: ...680 20 20 20 20 C B 6 5 A D 2 7 1 2 3 4 7 2 6 5 2 3 4 5 1 100 1 2 3 4 1 3 6 4 5 2 1 3 4 5 2 1 2 300 mm 1 15 m 600 290 2 3 4 6 5 1 5 6 8 7 9 13 12 10 11 3 4 2 1 100 mm 1 1 7 5 6 2 3 4 P 1 P 2 F 1 F 2 T...

Page 3: ...zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastr...

Page 4: ...cessories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appr...

Page 5: ...ng Consult the builder for details 3 Install the suspension bolts use either a W3 8 or M10 size bolt Use anchors for existing ceilings and a sunken insert sunken anchors or other field supplied parts...

Page 6: ...to a fire Finally make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Table 1...

Page 7: ...indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping between the outdoor unit and an indoor unit are mismatched...

Page 8: ...ld damage the entire system 7 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that...

Page 9: ...if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display indications Display Do not display 5 Information to I manager...

Page 10: ...ILTERS AND OUTSIDE PANELS How to clean the air filter Clean the air filter when the display shows TIME TO CLEAN AIR FILTER Increase the frequency of cleaning if the unit is installed in a room where t...

Page 11: ...e outdoor unit How to clean the air outlet and outside panels Clean with a soft cloth When it is difficult to remove stains use water or neutral detergent DISPOSAL REQUIREMENTS Dismantling of the unit...

Page 12: ...N OFF BUTTON H1P LIGHT EMITTING DIODE ON RED H2P LIGHT EMITTING DIODE TIMER GREEN H3P LIGHT EMITTING DIODE FILTER SIGN RED H4P LIGHT EMITTING DIODE DEFROST ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELE...

Page 13: ...P1 P2 F1 F2 T1 T2 1 2 3 4 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25081 1A...

Reviews: