background image

 

Installation and operation manual

5

FXCQ20~125M8V3B

VRV System air conditioners

4PW25081-1A

W

IRING

 

EXAMPLE

 

AND

 

HOW

 

TO

 

SET

 

THE

 

REMOTE

 

CONTROLLER

How to connect wiring 

(See figure 11)

Power supply wiring
Remove the switch box lid (1) and connect the wires to the
power supply terminal board inside. While doing this, pull the
wires inside through the rubber bush A and clamp the wires
along with other wires using clamp A, untightening the clip of
clamp A by pressing. After the connection, tighten clamp A as
before.

Unit wiring and remote controller wiring
Remove the switch box lid (2) and pull the wires inside through
the rubber bush B and connect to the terminal board for unit
transmission wiring.

Precautions 

(See figure 12)

1

Observe the notes mentioned below when wiring to the power
supply terminal board.

Do not connect wires of different gauge to the same power supply
terminal. (Looseness in the connection may cause overheating.)

When connecting wires of the same gauge, connect them
according to the figure.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal board of the unit
in accordance with electrical equipment standards, when using

two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller cords and wires connecting the units should
be located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal board for
transmission wiring. This mistake could damage the entire
system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire. 

W

IRING

 

EXAMPLE

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 13

.

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit. 
(Normal operation.) 

(See figure 14)

.

For group control or use with 2 remote controllers 

(See figure 15)

.

When including BS unit 

(See figure 16)

.

Precautions

1.

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

2.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

3.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

F

IELD

 

SETTING

Field setting must be made on the remote controller in function of the
installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.

1

Terminal board for unit transmission wirings

2

Clamp

3

Transmission wiring between units

4

Remote controller wiring

5

Power supply wiring

6

Field supplied wires

7

Power supply terminal board

8

Earth terminal (supplied with the unit)

1

Power supply

2

Main switch

3

Power supply wiring

4

Transmission wiring

5

Switch

6

Fuse

7

BS unit REYQ only

8

Indoor unit

9

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (Optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is automati-
cally set when the power is activated.

Summary of Contents for FXCQ20M8V3B

Page 1: ...INSTALLATION AND OPERATION MANUAL FXCQ20M8V3B FXCQ25M8V3B FXCQ32M8V3B FXCQ40M8V3B FXCQ50M8V3B FXCQ63M8V3B FXCQ80M8V3B FXCQ125M8V3B System air conditioners...

Page 2: ...680 20 20 20 20 C B 6 5 A D 2 7 1 2 3 4 7 2 6 5 2 3 4 5 1 100 1 2 3 4 1 3 6 4 5 2 1 3 4 5 2 1 2 300 mm 1 15 m 600 290 2 3 4 6 5 1 5 6 8 7 9 13 12 10 11 3 4 2 1 100 mm 1 1 7 5 6 2 3 4 P 1 P 2 F 1 F 2 T...

Page 3: ...zgodnie z naszymi instrukcjami 18 sunt n conformitate cu urm torul urm toarele standard e sau alt e document e normativ e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastr...

Page 4: ...cessories are included with your unit Optional accessories There are two types of remote controllers wired and wireless Select a remote controller according to customers request and install in an appr...

Page 5: ...ng Consult the builder for details 3 Install the suspension bolts use either a W3 8 or M10 size bolt Use anchors for existing ceilings and a sunken insert sunken anchors or other field supplied parts...

Page 6: ...to a fire Finally make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Table 1...

Page 7: ...indoor unit as unit A unit B and be sure the terminal board wiring to the outdoor unit and BS unit are properly matched If wiring and piping between the outdoor unit and an indoor unit are mismatched...

Page 8: ...ld damage the entire system 7 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the terminals Keep wiring in neat order so that...

Page 9: ...if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display indications Display Do not display 5 Information to I manager...

Page 10: ...ILTERS AND OUTSIDE PANELS How to clean the air filter Clean the air filter when the display shows TIME TO CLEAN AIR FILTER Increase the frequency of cleaning if the unit is installed in a room where t...

Page 11: ...e outdoor unit How to clean the air outlet and outside panels Clean with a soft cloth When it is difficult to remove stains use water or neutral detergent DISPOSAL REQUIREMENTS Dismantling of the unit...

Page 12: ...N OFF BUTTON H1P LIGHT EMITTING DIODE ON RED H2P LIGHT EMITTING DIODE TIMER GREEN H3P LIGHT EMITTING DIODE FILTER SIGN RED H4P LIGHT EMITTING DIODE DEFROST ORANGE SS1 SELECTOR SWITCH MAIN SUB SS2 SELE...

Page 13: ...P1 P2 F1 F2 T1 T2 1 2 3 4 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 LN P1 P2 F1 F2 T1 T2 1 3 6 2 L N IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T...

Page 14: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW25081 1A...

Reviews: