background image

English

9

To avoid the influence of noise from the power supply line on the transmission wiring and the remote 
controller wiring, these wirings must be kept as far as possible from the power/ground wirings. As shown in the 
figure, keep the power supply wiring and the ground wiring together. Keep the transmission and remote con-
troller wirings together and route them maintaining a good distance from the power supply/ground wirings 
(that is, on the other side of the power supply/ground wirings). Then, fix them securely on the refrigerant pipe.

Seal the piping through-hole with putty corking material.

(9) Push on both bottom edges of the indoor unit using both hands and hook the tab on the back of 

the indoor unit onto the installation panel (1). (Refer to Fig. 9)

At this time remove the buffering material placed in step (6).

Make sure power supply wiring, transmission wiring, ground wiring and remote controller wiring are not 
caught inside the indoor unit.

When screwing in the indoor unit

Remove the front grill. 

(Refer to Fig. 7)

Secure the indoor unit to the installation panel (1) with the securing 
screws (6). 

(Refer to Fig. 11)

5. REFRIGERANT PIPING WORK

For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.

〉 

Execute heat insulation work completely on both sides of the gas piping and the liquid piping. 

Otherwise, a water leakage can result sometimes.

〉 

(

When using a heat pump, the temperature of the gas piping can reach up to approximately 120°C, so use 

insulation which is sufficiently resistant.)

Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed 

30°C or RH80 %, reinforce the refrigerant insulation. (20 mm or thicker) Condensation may form on the 
surface of the insulating material.

Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not pos-

sible if the types of refrigerant are not the same.

CAUTION

• Use a pipe cutter and flare suitable for the type of refrigerant.
• Apply ester oil or ether oil around the flare section before connecting.
• To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end 

or cover it with tape.

• Do not allow anything other than the designated refrigerant to get mixed into the refrigerant 

circuit, such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room 
thoroughly right away.

• Do not mix air or other gas with the specified refrigerant in the refrigeration cycle.
• Ventilate the room if refrigerant gas leaks during the work.

The outdoor unit is charged with refrigerant.

Use copper alloy seamless pipes (ISO 1337)

Installation panel 
(accessory) (1)

Refrigerant piping

Insulating tape 
(accessory) (4)

M4 × 12L 
(accessory) (6)

Fig. 11

01_EN_3P156215-12U.fm  Page 9  Thursday, August 27, 2009  4:09 PM

Summary of Contents for FXAQ20PV1

Page 1: ...STE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORGVULDIG DOOR VOOR INSTALLATIE BEWAAR DEZE HAN DLEINDING WAAR U HEM KUNT TERUGVINDEN VOOR LATERE NASLAG LEIA COM ATENÇÃO ESTAS INSTRUÇÕES ANTES DE REALIZAR A INSTALAÇÃ...

Page 2: ...2 40 DAIKIN TCF 024D16 06 2009 TÜV Rheinland EPS B V 0510260101 A B C FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE FXAQ20PV1 FXAQ25PV1 FXAQ32PV1 FXAQ40PV1 FXAQ50PV1 FXAQ63PV1 Low Voltage 2006 95 EC Machinery Safety 98 37 EC Electromagnetic Compatibility 2004 108 EC 3P223078 1B fm Page 1 Saturday June 27 2009 10 25 AM ...

Page 3: ...ve these instructions properly may result in property damage or per sonal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do not attempt to install the air conditioner yourself Improper installation may result in water leakage electric shocks or fire Install the air conditioner in accordance with the instructi...

Page 4: ...evisions or radios to prevent picture interference and noise Depending on the incoming signal strength a distance of 1 meter may not be sufficient to eliminate noise Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible Do not i...

Page 5: ...ombustible gases and where voltatile flammable gas like thinner or gasoline is used Gas in the vicinity of the unit could ignite Where machines can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories Also in vehicles or vessels 2 2 ACCESSORIES Check the fo...

Page 6: ...at shown on the name plate The unit may malfunction or the compo nents burn out Are wiring and piping correct The unit may malfunction or the compo nents burn out Is the unit safely grounded Dangerous at electric leakage Is wiring size according to specifications The unit may malfunction or the compo nents burn out Is something blocking the air outlet or inlet of either the indoor or outdoor units...

Page 7: ...s out of the air inlet Where the cool warm air reaches all across the room CAUTION The indoor and outdoor units and the power supply wiring and remote controller cord must be installed at least 1m away from any televisions or radios This is to prevent interference with picture and sound recep tion Interference may occur even at 1m away depending on the reception quality If installing the wireless ...

Page 8: ...stallation 3 and use a level to make sure the drain hose is either level or tilted slightly downward c Secure the installation panel 1 to the wall using either screws or bolts If using the attachment screws for the installation panel 2 attach using at least 4 screws on either side for a total of 8 screws 20 32 type 9 screws 40 63 type of the recommended installation cleat position on the included ...

Page 9: ...ove the tabs 3 places securing the front grill by pushing them in the direction of the arrows 4 Making sure not to catch the horizontal flaps remove the front grill by pulling in the direction of the arrow Remove the drain plug the insulation tubing and the drain hose from the drain pan and replace Refer to Fig 8 Connect the local refrigerant piping ahead of time matching it to the liquid pipe and...

Page 10: ... leaks Insert using a hexagon wrench 4mm Make sure there are no gaps Refrigerant piping Be sure to pass all wires through the wiring guide Tab There are 2 places Wiring locally procured Power supply wiring Transmission wiring Ground wiring Remote controller wiring Wall Installation panel accessory 1 Front panel Front grill Service lid Place buffering material Hook the indoor unit hook onto the ins...

Page 11: ...s of the gas piping and the liquid piping Otherwise a water leakage can result sometimes When using a heat pump the temperature of the gas piping can reach up to approximately 120 C so use insulation which is sufficiently resistant Also in cases where the temperature and humidity of the refrigerant piping sections might exceed 30 C or RH80 reinforce the refrigerant insulation 20 mm or thicker Cond...

Page 12: ...anner there is a point where the tightening torque suddenly increases From that position further tighten the flare nut the angle shown below Table 2 After the work is finished make sure to check that there is no gas leak CAUTION CAUTION TO BE TAKEN WHEN BRAZING REFRIGERANT PIPING Do not use flux when brazing refrigerant piping Therefore use the phosphor copper brazing filler metal BCuP 2 JIS Z 326...

Page 13: ...After checking for gas leaks be sure to insulate the pipe connections using the supplementary piping insulation tubing and insulating tape 4 The insulating tape 4 should be wrapped from the L shaped bend all the way to the end inside the unit Refer to Fig 15 CAUTION Be sure to insulate any field piping all the way to the piping connection inside the unit Any exposed piping may cause condensation o...

Page 14: ...ir filter pouring water into the drain pan and making sure water flows smoothly out of the drain hose Refer to Fig 19 CAUTION Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain pipes and corrode the heat exchanger Keep in mind that it will become the cause of getting drain p...

Page 15: ...ht cause explosions or fire if gas leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 7 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse Amps A kW Fan Motor Rated Output kW FLA Full Load Amps A 7 3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND W...

Page 16: ... transmission wiring using the included clamp small 5 and then firmly secure using the included clamp small 5 according to the figure Refer to Fig 21 Be sure to attach it to prevent the infiltration of water as well as any insects and other small creatures from the outside Otherwise a short circuit may occur inside the control box PRECAUTIONS Observe the notes mentioned below when wiring to the po...

Page 17: ...ure the cover closes tight Incomplete connections could result in overheating and in worse case electric shock or fire Round crimp style terminal Attach insulation sleeve Power supply wiring and ground wire 40mm or m ore Fig 20 REMOTE CNTRL FORCED OFF TRANSMISSION WIRING F1 F2 T1 T2 P1 P2 L N Terminal block 6P Ground terminal Ground wiring Power supply wiring Power supply terminal block 3P In case...

Page 18: ...e only specified wire and tightly connect wires to terminals Be careful wires do not place external stress on terminals Keep wiring in neat order and so as not to obstruct other equipment such as popping open the service cover Make sure the cover closes tight Incomplete connections could result in overheating and in worse case electric shock or fire 8 2 WIRING EXAMPLE Fit the power supply wiring o...

Page 19: ...P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 L N Outdoor unit No 2 System Indoor unit A Indoor unit B Indoor unit C Most downstream indoor unit Fig 24 For use with 2 remote controllers Power supply 220 240V 50Hz Note It is not necessary to designate indoor unit address when using group control The address is automatically set when power is activated Fig...

Page 20: ...f the terminal block 6P for remote controller 2 Actuation The following table explains FORCED OFF and ON OFF OPERATIONS in response to Input A 3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation 8 5 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each option...

Page 21: ...e 3 9 2 SETTING AIR FLOWRATE INCREASE MODE It is possible to raise set airflow HIGH and LOW from the field Change the SECOND CODE NO as shown in Table 4 to suit your needs SECOND CODE NO is factory set to 01 for Standard Table 4 When using wireless remote controllers When using wireless remote controllers wireless remote controller address setting is necessary Refer to the installation manual atta...

Page 22: ...nished at the end of the test run If the air conditioner is operated substances discharged from the paint adhesive etc can contaminate the indoor unit and they may cause splashing or leakage of water NOTE After the test run is finished check the items listed in b Items to be checked at time of delivery Remote controller display Content Concentrated Management is lit up There is a short circuit at ...

Page 23: ... 0909 HT 3P156215 12U EM09A027B 00_CV_3P156215 12U fm Page 2 Thursday August 27 2009 10 13 AM ...

Reviews: