![background image](http://html.mh-extra.com/html/daikin/fxaq-p/fxaq-p_technical-data-manual_2459645015.webp)
3
1
6
• VRV Systems • Indoor Unit
13
• Indoor Unit • Wall mounted unit • FXAQ-P
6
Capacity tables
6 - 3
Capacity Correction Factor
FXAQ-P
3D079901
Capacity correction factor Te = 9°C
Indoor air
temperature
14.0 °CWB
16.0 °CWB
18.0 °CWB
19.0 °CWB
20.0 °CWB
22.0 °CWB
24.0 °CWB
20.0 °CDB
23.0 °CDB
26.0 °CDB
27.0 °CDB
28.0 °CDB
30.0 °CDB
32.0 °CDB
FXAQ20P
TC
0.687
0.692
0.742
0.759
0.780
0.813
0.836
SHF
1.132
1.194
1.139
1.116
1.093
1.061
1.046
FXAQ25P
TC
0.691
0.692
0.739
0.759
0.780
0.814
0.836
SHF
1.123
1.193
1.140
1.115
1.093
1.061
1.046
FXAQ32P
TC
0.700
0.692
0.736
0.760
0.781
0.815
0.836
SHF
1.107
1.190
1.140
1.089
1.091
1.059
1.050
FXAQ40P
TC
0.681
0.684
0.748
0.772
0.792
0.824
0.853
SHF
1.142
1.192
1.127
1.101
1.081
1.058
1.037
FXAQ50P
TC
0.688
0.690
0.751
0.775
0.797
0.832
0.854
SHF
1.119
1.182
1.122
1.097
1.077
1.053
1.052
FXAQ63P
TC
0.694
0.690
0.753
0.781
0.806
0.833
0.853
SHF
1.102
1.181
1.121
1.095
1.074
1.054
1.050