background image

14 Electrical installation

Installation and operation manual

19

FXAA15~63AUV1B
VRV system air conditioner
3P622285-1B – 2020.10

Class

Pipe outer diameter (mm)

Liquid pipe

Gas pipe

15~32

Ø6.4

Ø9.5

40~63

Ø12.7

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

13.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

12~15 mm

≥13 mm

12.7 mm (1/2")

14~16 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

13.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

13.2.1

To connect the refrigerant piping to the
indoor unit

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Pipe length

. Keep refrigerant piping as short as possible.

1

Flare connections

. Connect refrigerant piping to the unit using

flare connections.

2

Insulation

.  Insulate  the  refrigerant  piping,  the  insulating  tape

should  be  wrapped  from  the  L-shaped  bend  all  the  way  to  the
end inside the unit as follows:

d

f

b

e

g

a

c

h

d

b

i

a

Field piping

b

Indoor unit piping insulation tubing

c

Indoor unit piping

d

Insulating tubing tape

e

Insulating tape (accessory)

f

Large tie wrap (accessory)

g

Beginning of wrapping

h

L-shaped bend

i

Insulation tubing seam (make sure there are no gaps in
the insulation tubing seam)

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

14

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

14.1

Specifications of standard wiring
components

Component

Class

15+20

25~40

50

63

Power
supply
cable

MCA

(a)

0.3 A

0.4 A

0.5 A

0.6 A

Voltage

220~240 V

Phase

1~

Frequency

50 Hz

Wire sizes

1.5 mm

(3‑core wire)

H07RN-F (60245 IEC 66)

Transmission wiring

0.75 to 1.25 mm² (2‑core wire)

H05RN-F (60245 IEC 57)

User interface cable

Summary of Contents for FXAA15AUV1B

Page 1: ...lation and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXAA15AUV1B FXAA20AUV1B FXAA25AUV1B FXAA32AUV1B FXAA40AUV1B FXAA50AUV1B FXAA63AUV1B ...

Page 2: ...dili on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele съответстват на следните стандарти или други нормативни документи при условие че се използват съгласно нашите инструкции atitinka žemiau nurodytus standartus ir arba kitus norminius dokumentus su sąlyga kad yra naudojami pagal mūsų nurodymus tad ja lietoti atbilstoš...

Page 3: ...rigerant piping 18 13 1 1 Refrigerant piping requirements 18 13 1 2 Refrigerant piping insulation 19 13 2 Connecting the refrigerant piping 19 13 2 1 To connect the refrigerant piping to the indoor unit 19 14 Electrical installation 19 14 1 Specifications of standard wiring components 19 14 2 To connect the electrical wiring to the indoor unit 20 15 Finishing the indoor unit installation 21 15 1 T...

Page 4: ...efrigerant gas leakage CAUTION Install the refrigerant piping or components in a position where they are unlikely to be exposed to any substance which may corrode components containing refrigerant unless the components are constructed of materials that are inherently resistant to corrosion or are suitably protected against corrosion Electrical installation see 14 Electrical installation 419 WARNIN...

Page 5: ...n piping Protection devices piping and fittings shall be protected as far as possible against adverse environmental effects Provision shall be made for expansion and contraction of long runs of piping Piping in refrigerating systems shall be designed and installed such as to minimise the likelihood of hydraulic shock damaging the system The indoor equipment and pipes shall be securely mounted and ...

Page 6: ...ol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negative consequences for the environment and human health 3 2 Instructions for safe operation WARNING Do NOT ...

Page 7: ...esult in a fire Maintenance and service see 7 Maintenance and service 410 CAUTION Pay attention to the fan It is dangerous to inspect the unit while the fan is running Be sure to turn off the main switch before executing any maintenance task CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury WARNING NEVER rep...

Page 8: ... breakage electric shock or fire Contact your dealer 4 About the system WARNING Do NOT modify disassemble remove reinstall or repair the unit yourself as incorrect dismantling or installation may cause an electric shock or fire Contact your dealer In case of accidental refrigerant leaks make sure there are no naked flames The refrigerant itself is entirely safe non toxic and mildly flammable but i...

Page 9: ... operation modes Setback A function that keeps the room temperature in a specific range when the system is turned off by the user the schedule function or the OFF timer 6 2 1 Basic operation modes The indoor unit can operate in various operation modes Icon Operation mode Cooling In this mode cooling will be activated as required by the setpoint or by Setback operation Heating In this mode heating ...

Page 10: ...by an authorized installer or service agent We recommend performing maintenance at least once a year However applicable legislation might require shorter maintenance intervals CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet When the fan is rotating at high speed it will cause injury NOTICE NEVER inspect or service the unit by yourself Ask a qualified service person...

Page 11: ...cloth and let it dry up in the shade 5 Attach the front panel Align the hooks of the front panel with the slots and push them all the way in 6 Close the front panel slowly 7 2 3 To clean the air filter NOTICE Do NOT use water of 50 C or higher Possible consequence Discoloration and deformation When to clean the air filter Rule of thumb Clean every 6 months If the air in the room is extremely conta...

Page 12: ...efrigerant leakage sensor INFORMATION Lifetime of the sensor is 10 years The user interface displays error CH 05 6 months before the end of the sensor lifetime and error CH 02 after the end of the sensor lifetime For more information refer to the reference guide of the user interface and contact you dealer In case of detection when the unit is standby When the detection occurs when the unit is sta...

Page 13: ...ral safety precautions c Screw pack M4 25L 8 for FXAA15 32 9 for FXAA40 63 2 M4 12L d Tie wraps 1 large 3 small e Insulation tape f Paper pattern for installation 12 Unit installation 12 1 Preparing the installation site Avoid installation in an environment with a lot of organic solvents such as ink and siloxane WARNING The appliance shall be stored in a room without continuously operating ignitio...

Page 14: ...el 414 2 Remove the screws 2 for FXAA15 32 2 3 for FXAA40 63 3 3 Push down the 3 upper hooks marked with a symbol with 3 circles in the direction of the arrows Remove cardboard between the filter and the heat exchanger a b a Hook b Cardboard 4 Making sure not to catch the horizontal flaps remove the front grille by pulling in the direction of the arrow 12 2 4 To re install the front grille 1 Insta...

Page 15: ... the mounting plate on the wall and install it temporarily 5 Level the mounting plate use tabs on the mounting plate 6 Mark the centers of the drilling points on the wall using a tape measure Position the end of tape measure at symbol 7 Finish the installation by securing the mounting plate on the wall When using M4 25L screws accessory use 8 screws for FXAA15 32 or 9 screws for FXAA40 63 Install ...

Page 16: ... or fire NOTICE Be sure to seal the gaps around the pipes with sealing material field supply in order to prevent water leakage 1 Drill a 80 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a wall cover into the wall pipe Ø80 a b c a Wall embedded pipe field supply b Putty field supply c Wall hole cover field suppl...

Page 17: ...nt pipes Do NOT push the refrigerant pipes onto the bottom frame or the front grille 4 Pass the drain hose and refrigerant pipes through the wall hole 5 When the complete installation is finished drain piping 12 3 6 To provide drainage 4 17 the refrigerant piping 13 Piping installation 4 18 and the electrical wiring 14 Electrical installation 4 19 fix the indoor unit on the mounting plate 15 1 To ...

Page 18: ... left side 1 Remove the insulation fixing screw on the right side and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side NOTICE Do NOT apply lubricating oil refrigerant oil to the drain plug when inserting it The drain plug may deteriorate and cause drain leakage from the plug 3 Insert the drain hose on the left side and do not forget to tighten it with ...

Page 19: ...suitably protected against corrosion WARNING MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable Pipe length Keep refrigerant piping as short as possible 1 Flare connections Connect refrigerant piping to the unit using flare connections 2 Insulation Insulate the refrigerant piping the insulating tape should be wrapped from the L shaped bend all the way to the end inside ...

Page 20: ...the terminal block make sure the symbols F1 F2 match with the symbols on the outdoor unit 4 Fix user interface cable together with the transmission cable with a tie wrap accessory 5 Power supply cable Connect the cable to the terminal block L N earth a b a Circuit breaker b Residual current device 6 Seal all gaps with a sealing material field supply to prevent small animals from entering the syste...

Page 21: ...missing phases or reversed phases The system is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply voltage matches the voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO...

Page 22: ...s a remote sensor set the increase decrease increments If you want to change increments to Then 1 M SW 1 C 12 22 2 01 0 5 C 02 Setting Differential for automatic changeover Set temperature difference between cooling setpoint and heating setpoint in automatic mode availability depends on the system type Differential is cooling setpoint minus heating setpoint If you want to set the temperature diffe...

Page 23: ...elligent power module K R KCR KFR KHuR K M Magnetic relay L Live L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor Symbol Meaning MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power module PS Switching power supply PTC PTC thermistor Q Insulated ...

Page 24: ...3P622285 1B 2020 10 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Reviews: