1-9
English
ELECTRICAL WIRING CONNECTION
X1
IMPORTANT:
* These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with label data on the unit.
There must be an all pole disconnection in the supply mains with a contact separation of at least 3mm.
Model
FWG05AAT(F)
FWG08AAT(F)
FWG11AAT(F)
Voltage Range**
220V-240V/~/50Hz +
Recommended time delay fuse*
(A)
2
2
2
Power Supply Cable*
(mm
2
)
1.5
1.5
1.5
Interconnection cable size*
(mm
2
)
Number of conductors
3
3
3
Model: FWG05/08/11AAT
X2
X3
FCU 1
FCU 2
L
N1
CVLV
L
N
CHILLER
Model: FWG05/08/11AAF
L
N
3WV
X1
X2
FCU 1
HVLV
CHILLER
N
L
N1
CVLV
N
3WV
L
N1
CVLV
N
FCU 3
N1
CVLV
N2
L
N
3WV
FCU 2
HVLV
N1
CVLV
N2
L
N
3WV
3WV
L
N
X3
3 Way Valve
Relay
3WV
X1, X2,X3
Field Supply Wire
3 Way Valve
Relay
3WV
X1, X2,X3
Field Supply Wire
L
N
L
N
3WV
3WV
FCU 3
HVLV
N1
CVLV
N2
L
N
3WV
3WV
L
N
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
All power line must be from the
same phase.
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
All power line must be from the
same phase.