uT66002760-02
All copying, even partial, of this manual is strictly forbidden
9
» 4 pipes
FWB-C
04
05
06
08
Speed
min
med
max
min
med
max
min
med
max
min
med
max
Declared speed
2,5,7
1,5,7
1,6,7
1,4,7
Rated air flow
(E)
m³/h
109
243
270
170
272
336
195
357
398
302
524
642
Available static pressure
(E)
Pa
10
50
63
19
50
77
19
50
63
17
50
75
Power input
(E)
W
24
57
82
34
69
106
34
85
106
76
143
192
Maximum current absorption
A
0,40
0,56
0,56
1,10
Total cooling capacity
(1)(E)
kW
0,92
1,70
1,86
1,26
1,88
2,24
1,57
2,67
2,93
1,89
3,13
3,64
Sensible cooling capacity
(1)(E)
kW
0,61
1,20
1,31
0,88
1,33
1,57
1,07
1,84
2,01
1,41
2,35
2,78
FCEER class
(E)
D
E
Water flow
(2)
l/h
160
302
333
221
335
404
274
473
522
339
562
656
Water pressure drop
(2)(E)
kPa
2
5
6
3
6
8
3
7
9
3
8
11
Heating capacity
(3)(E)
kW
1,14
1,93
2,06
1,55
2,07
2,32
2,09
3,09
3,29
2,80
3,82
4,24
FCCOP class
(E)
C
D
C
D
Water flow
(3)
l/h
100
169
180
136
181
204
183
271
288
245
334
371
Water pressure drop
(3)(E)
kPa
1
2
3
2
3
3
2
3
4
3
5
6
Additional coil - number of rows
1
1
1
1
Total sound power level
(4)
dB(A)
28
49
52
39
50
54
39
50
54
38
52
58
Inlet + radiated sound power level
(4)(E)
dB(A)
26
47
50
37
48
52
37
48
52
36
50
56
Outlet sound power level
(4)(E)
dB(A)
25
46
49
36
47
51
37
47
51
35
49
55
Water content - additional coil
dm³
0,47
0,47
0,59
0,59
Power supply cable type
N07V-K
Cross-section area of power cables
(5)
mm²
1,00
1,00
1,00
1,50
Safety fuse F
A
1
1
1
2
Fuses type
gG
FWB-C
10
11
15
17
Speed
min
med
max
min
med
max
min
med
max
min
med
max
Declared speed
1,6,7
1,6,7
5,6,7
5,6,7
Rated air flow
(E)
m³/h
333
683
755
333
683
755
1050
1163
1289
1050
1163
1289
Available static pressure
(E)
Pa
12
50
61
12
50
61
40
50
60
40
50
60
Power input
(E)
W
76
167
192
76
167
192
235
280
332
235
280
332
Maximum current absorption
A
1,10
1,10
2,10
2,10
Total cooling capacity
(1)(E)
kW
2,22
4,20
4,60
2,44
4,76
5,20
6,15
6,66
7,21
6,91
7,49
8,12
Sensible cooling capacity
(1)(E)
kW
1,60
3,07
3,36
1,70
3,31
3,62
4,51
4,88
5,29
4,83
5,23
5,67
FCEER class
(E)
D
Water flow
(2)
l/h
394
749
822
432
846
925
1095
1191
1295
1225
1333
1448
Water pressure drop
(2)(E)
kPa
2
7
8
3
10
12
13
16
18
20
23
26
Heating capacity
(3)(E)
kW
3,40
5,17
5,45
3,40
5,17
5,45
6,42
6,73
7,06
6,42
6,73
7,06
FCCOP class
(E)
D
Water flow
(3)
l/h
297
452
477
297
452
477
562
590
618
562
590
618
Water pressure drop
(3)(E)
kPa
6
13
14
6
13
14
19
21
22
19
21
22
Additional coil - number of rows
1
1
1
1
Total sound power level
(4)
dB(A)
38
55
58
38
55
58
61
63
69
61
63
69
Inlet + radiated sound power level
(4)(E)
dB(A)
36
53
56
36
53
56
59
61
67
59
61
67
Outlet sound power level
(4)(E)
dB(A)
35
52
55
35
52
55
58
60
66
58
60
66
Water content - additional coil
dm³
0,97
0,97
0,97
0,97
Power supply cable type
N07V-K
Cross-section area of power cables
(5)
mm²
1,50
1,50
1,50
1,50
Safety fuse F
A
2
2
2
2
Fuses type
gG
(1) Water temperature 7°C / 12°C, air temperature dry bulb 27°C, wet bulb 19°C (47% relative humidity) according to EN1397:2015
(2) Water temperature 7°C / 12°C, air temperature dry bulb 27°C, wet bulb 19°C (47% relative humidity)
(3) Water temperature 65°C / 55°C, air temperature 20°C
(4) Sound power measured according to standards ISO 3741 and ISO 3742
(5) The shown section is to be considered as the minimum recommended section. The cables must be chosen in compliance with CEI - UNEL 35024/1. standard.
(E) EUROVENT certified data
Power supply 230-1-50 (V-ph-Hz)