11 ACCESSORIES
FWEC1A wall-mounted microprocessor control
having the following main features:
• Room air temperature reading and adjustment
• Water temperature reading (water probe as an optional)
• Manual and automatic adjustment of fan speed
• Manual and automatic switching of heating and cooling mode depending on the water temperature within the heat exchanger or on the room temperature, with
a neutral zone that can be selected in the range from 2° to 5°C.
The controller is equipped with a large display (3”) to show and set all the functions of the unit.
Using the installation kit available FWEC1A can be mounted on the unit.
FWEC2A - wall-mounted microprocessor control
having the following main features:
• Room air temperature reading and adjustment
• Room humidity reading and adjustment
• Water temperature reading (water probe as an optional)
• Manual and automatic adjustment of fan speed
• Manual and automatic switching of heating and cooling mode depending on the water temperature within the heat exchanger or on the room temperature, with
a neutral zone that can be selected in the range from 2° to 5°C.
• Serial port for Bus connection
The controller is equipped with a large display (3”) to show and set all the functions of the unit.
Using the installation kit available, FWEC2A can be mounted on the unit.
FWEC3A- wall-mounted microprocessor control
having the following main features:
• Room air temperature reading and adjustment
• Room humidity reading and adjustment
• Water temperature reading (water probe as an optional)
• Manual and automatic adjustment of fan speed
• Manual and automatic switching of heating and cooling mode depending on the water temperature within the heat exchanger or on the room temperature, with
a neutral zone that can be selected in the range from 2° to 5°C.
• Clock and hourly timer-programmed operation
• 2 Analogue outputs for controlling modulating evices -10V
• 2 Digital outputs for controlling (On/Off) external devices (novoltage contacts)
• Serial port for Bus connection
The controller is equipped with a large display (3”) to show and set all the functions of the unit. Using the installation kit available, FWEC3A can be mounted on
the unit.
FWECS - wall-mounted microprocessor split controller with display
FWECS controller is a system composed of:
• Circuit board comprising the power circuit, the microprocessor system and the removable screw connectors for the connection of the inlet and outlet devices;
• User interface comprising a graphic display and a keyboard (six keys) provided with clock and sensor to read the ambient temperature.
Main functions:
• Room air temperature reading and adjustment
• Room humidity reading and adjustment
• Water temperature reading (water sensor as an optional)
• Manual/automatic regulation of the fan speed with ON -OFF step and modulating control
• Automatic adjustment of valve opening with ON/OFF and modulating controller
• Manual and automatic switching of heating and cooling mode depending on the water temperature within the heat exchanger or on the room temperature,
with a selectable neutral zone
• Clock and hourly timer-programmed operation
• 3 Analogue outputs for controlling modulating devices -10V
• Economy function and minimum temperature
• 1 Digital outputs for controlling (On/Off) external devices (novoltage contacts)
• Serial port for RS485 connection
• Serial port for OC connection
• 3 digital inputs for ON-OFF, Economy, Operating mode remote setting
Operating mode
The controller is provided with a programmable display that allows you to view and set the hydronic unit functions by means of the specific interface with parameter
description.
FWTSKA - water temperature sensor for microprocessor controls model FWECS, FWEC1A/2A/3A
Directly connected to the microprocessor controllers FWECS and FWEC1A/2A/3A to measure the water temperature through the heat exchanger.
If the temperature registered is lower than 17 °C the unit works in cooling mode and the temperature range of the control panel will be referred to the cooling mode
(19/31 °C); if the temperature registered is higher than 37 °C the unit works in heating mode and the temperature range of the control panel will be referred to the
heating mode (14/26 °C). If the temperature registered is between 17 °C e 37 °C the control panel will disable the unit operation.
FWHSKA - Humidity sensor for FWECS, FWEC1A/2A/3A) microprocessor controller
Directly connected to the microprocessor controllers FWECS and FWEC1A/2A/3A, it enables the control of the heating element ventilation (if present, as support in
heating mode) and the automatic cooling/heating changeover according to the water temperature.