8. ELECTRIC WIRING WORK

• All field supplied parts and materials and electric works must conform to local codes.
• Use copper wire only.
• For electric wiring work, refer also to “WIRING DIAGRAM” attached to the unit body.
• For remote controller wiring details, refer to the installation manual attached to the remote controller.
• All wiring must be performed by an authorized electrician.
• A circuit breaker capable of shutting down power supply to the entire system must be installed.
• Be sure to install an earth leakage breaker. 

Failure to install an earth leakage breaker may result in electric shocks.

• Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire 

connected to the outdoor unit, the capacity of the circuit breaker and switch, and wiring instructions.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas pipes, plumbing pipes, lightning rods, or telephone ground wires.

Gas pipes: could explode and cause fires if there was a gas leak.

Plumbing pipes: no grounding effect if hard vinyl pipes are used.

Telephone ground wires or lightning rods: the ground potential could rise dangerously high if hit by 
lightning.

Specifications for field wire 

NOTE

1.

Shows only in case of protected pipes. Use H07RN-F in case of no protection.

2.

Insulated thickness : 1mm or more. 

〈 

Methods of wiring units and connecting remote controller cords 

• Detach the Terminal box lid as shown in the figure and connect the wires to the unit wiring terminal board 

(3P) on the right side of the unit matching phase. Then, fix the wire using the clamp.

• Arrange the wires and fix a lid firmly so that the lid does not float during wiring work.
• Lock wires connecting the units and the grounding line to the pipe retainer.

[ PRECAUTIONS ]

• Do not clamp remote controller cords together with wires connecting the units. Doing so may cause 

malfunction.

• Remote controller cords and wires connecting the units should be located at least 50mm from other electric 

wires. Not following this guideline may result in malfunction due to electrical noise.

Wire

Size (mm

2

)

Length

Wiring the units

H05VV-U4G

(NOTE 1)

2.5

Remote controller cord 

(In case of installing the 

control panel separately)

Vinyl cord with sheath or 

cable (2 wire) (NOTE 2)

0.75 - 1.25

Max. 500m

3

2

1

Earth terminal

Earth terminal

Clamp

Wiring 
diagram

Terminal box lid

Power supply 
terminal board (3P)

Wiring the units

Earth wire

Pipe retainer

How to connect wiring

01_EN_3PA60136-8Y.fm  Page 12  Saturday, December 22, 2007  1:04 PM

Summary of Contents for FVQ100BV1B

Page 1: ...RA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGVULDIG DOO...

Page 2: ...FHY100BJV1 FHY125BJV1 FH35BJV1 FH45BJV1 FH60BJV1 II FHYP35BV1 FHYP45BV1 FHYP60BV1 FHYP71BV1 FHYP100BV1 FHYP125BV1 FH35BZV1 FH45BZV1 FH60BZV1 III FHQ35BUV1B FHQ50BUV1B FHQ60BUV1B FHQ71BUV1B FHQ100BUV1...

Page 3: ...rty damage or personal injury which may be serious depending on the circumstances WARNING Ask your dealer or qualified personnel to carry out installation work Do not attempt to install the air condit...

Page 4: ...e breaker may result in electric shocks or fire CAUTION While following the instructions in this installation manual install drain piping to ensure proper drainage and insulate piping to prevent conde...

Page 5: ...ETTING install them on an adequate place referring to the related technical information As for the installation procedure follow the instruction in Remote controller installation procedure attached to...

Page 6: ...e The unit may malfunction or the components burn out Are wiring and piping correct The unit may malfunction or the components burn out Is the unit safely grounded Dangerous at electric leakage Is wir...

Page 7: ...nit power supply wiring and transmission wiring at least 1 meter away from televisions and radio receivers This is to prevent image interference and noise in those electrical appliances Noise may be g...

Page 8: ...ompletely on both sides of the gas piping and the liquid piping Otherwise a water leakage can result sometimes When using a heat pump the temperature of the gas piping can reach up to approximately 12...

Page 9: ...ut included with the unit main body CAUTION Do not let oil get on the screw holders on the dressing board Oil can weaken the screw holders Table 1 Refer to Table 1 to determine the proper tightening t...

Page 10: ...g through the hole on the bottom frame After rigging pipes and wiring lock down the refrigerant pipes drain hose inside the unit indoor outdoor unit transmission wiring and grounding line in the pipin...

Page 11: ...smoothly and that water does not leak from connections Carefully pour approximately 1 000cc of water through the air discharge outlet so that it falls directly onto the heat exchanger at an angle with...

Page 12: ...troller cable from the remote controller terminal board 2 Remove the remote controller holding plate on the back side of the front plate panel 3 Fix the attached hole covering plate on the front plate...

Page 13: ...r with screw drivers etc 2 Attach the remote controller wiring 3 Reassemble the remote controller in the opposite order of 1 and at last install the attached remote controller lid 7 6 After the remote...

Page 14: ...angerously high if hit by lightning Specifications for field wire NOTE 1 Shows only in case of protected pipes Use H07RN F in case of no protection 2 Insulated thickness 1mm or more Methods of wiring...

Page 15: ...the screw may be damaged The tightening torque of each terminal screw is shown in the table on the right hand side 9 WIRING EXAMPLE For the wiring of outdoor units refer to the installation manual att...

Page 16: ...oller must be set to MAIN and the other to SUB MAIN SUB CHANGEOVER 1 Insert a screwdriver into the recess between the upper and lower part of remote controller and working from the 2 positions pry off...

Page 17: ...it the grille stopper front panel into the groove on the air intake grille and lock the grille down in its original place by screw See below figure Be careful not to overtighten screws S M M S Factory...

Page 18: ...upper part of the button and select the FIRST CODE NO 5 Press the part of the button and select the SECOND CODE NO 6 Press the TIMER ON OFF button once to fix the change of the setting 7 Press the INS...

Page 19: ...N button 4 times 2 times for wireless remote controller and operate at Test Operation mode for 3 minutes 6 Push AIR FLOW DIRECTION ADJUST button to make sure the unit is in operation 7 Press INSPECTIO...

Page 20: ...igure of the error code flashes 6 Continue pressing the PROGRAMMING TIME button unit it makes a long beep and find the lower code A long beep indicate the error code NOTE 1 Press the INSPECTION TEST O...

Page 21: ...c thermal outdoor unit Possible electrical overload in the compressor or cut line in the compressor motor L9 Stall prevention outdoor unit Compressor possibly locked LC Transmission malfunction betwee...

Page 22: ...emote controller UA Miss setting for multi system Error in multi system settings for simultaneous ON OFF operation UC Central control address overlapping UJ Transmission failure in accessory equipment...

Page 23: ...ASE OF PROTECTED PIPES USE H07RN F IN CASE OF NO PROTECTION INDOOR UNIT A1P PRINTED CIRCUIT BOARD CAPACITOR SIGNAL RECEIVER CIRCUIT CONNECTOR FOR OPTIONAL PARTS THERMISTOR AIR THERMISTOR COIL MAGNETIC...

Page 24: ...0802 HT 3PA60136 8Y EM07A043A 00_CV_3PA60136 8Y fm Page 2 Saturday December 22 2007 1 03 PM...

Reviews: