Functions
SiBE01-829
20
Functions and Control
1.6
Sleep Operation
When the Sleep Operation is set, the Sleep Operation circuit activates.
The Sleep Operation circuit maintains the airflow setting made by users.
The Sleep
Operation Circuit
When the unit is operating under cooling mode, the set temperature is increased by 0.5°C
after the first half an hour, 1°C after the second half an hour and total of 2°C after the
following 1 hour. This function will prevent excessive cooling during summer season.
When the unit is operating under heating mode, the set temperature is decreased by 1°C
after the first half an hour, 2°C after the second half an hour and total of 3°C after the
following 1 hour. This function will prevent night sweat during summer season.
This function is available under COOL, HEAT and AUTO mode.
+2
+1
1
2
1
2
0.5
passed time (hour)
set temperature (cooling mode)
set temperature (heating mode)
+0.5
3
(R8495)
Summary of Contents for FTY25GXV1
Page 1: ...SiBE01 829 Applied Models Non Inverter Pair Heat Pump SPLIT Pair Wall Mounted Type G Series ...
Page 5: ...SiBE01 829 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 11: ...Introduction SiBE01 829 x ...
Page 12: ...SiBE01 829 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 15: ...Functions SiBE01 829 4 List of Function ...
Page 16: ...SiBE01 829 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 19: ...Specifications SiBE01 829 8 Specifications ...
Page 49: ...Instructions SiBE01 829 38 Operation Manual ...
Page 69: ...Check SiBE01 829 58 Service Diagnosis ...
Page 111: ...Outdoor Unit SiBE01 829 100 Removal Procedure ...
Page 119: ...Wiring Diagrams SiBE01 829 108 Appendix ...