5 Installation

Installation manual

6

FTXTA30A2V1BW

Split system air conditioner

3P482320-9M – 2019.04

(mm)

44.5

605

17

110

798

150

155

44.5

 

Ø65

Ø65

d

g

g

a

e

d

a

f

f

b

c

a

a

a

a

a

a

h

± 610

± 605

± 555

k

j

i

a

Recommended mounting plate fixing spots

b

Pocket for the pipe port cover

c

Use tape measure as shown

d

Tabs for placing a spirit level

e

Unit center

f

Hole for embedded piping Ø65 mm

g

Value for tape measure

h

Position the end of tape measure at symbol " "

i

Drain hose

j

Liquid pipe

k

Gas pipe

5.2.2

To drill a wall hole

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

NOTICE

Be  sure  to  seal  the  gaps  around  the  pipes  with  sealing
material (field supply), in order to prevent water leakage.

1

Bore  a  65  mm  large  feed-through  hole  in  the  wall  with  a
downward slope towards the outside.

2

Insert a wall embedded pipe into the hole.

3

Insert a wall cover into the wall pipe.

Ø65

a b

c

a

Wall embedded pipe

b

Putty

c

Wall hole cover

4

After  completing  wiring,  refrigerant  piping  and  drain  piping,  do
NOT forget to seal the gap with putty.

5.2.3

To remove the pipe port cover

To  connect  the  piping  on  right-side,  right-bottom,  left-side  or  left-
bottom, the pipe port cover MUST be removed.

1

Cut  off  the  pipe  port  cover  from  inside  the  front  grille  using  a
coping saw.

2

Remove  any  burrs  along  the  cut  section  using  a  half  round
needle file.

NOTICE

Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.

5.2.4

To provide drainage

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

Summary of Contents for FTXTA30A2V1BW

Page 1: ...Installation manual Split system air conditioner English Installation manual Split system air conditioner FTXTA30A2V1BW ...

Page 2: ...on and ask him her to keep it for future reference Target audience Authorised installers INFORMATION This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin and in addition comply wi...

Page 3: ...ency range 2400 MHz 2483 5 MHz Radio protocol IEEE 802 11b g n Radio frequency channel 1 11 Output power 0 dBm 18 dBm Parameter Value Effective radiated power 17 dBm 11b 13 dBm 11g 12 dBm 11n Power supply DC 3 3 V 500 mA 4 Preparation 4 1 Preparing the installation site WARNING The appliance shall be stored so as to prevent mechanical damage and in a well ventilated room without continuously opera...

Page 4: ...ide a a a Panel lock 3 Push the right arm lightly to the right to disconnect the shaft from the shaft slot on the right side a c b a Arm b Shaft c Shaft slot 4 Disconnect the front panel shaft from the shaft slot on the left side a c b a Arm b Shaft slot c Shaft 5 Remove the front panel 6 To re install the front panel perform the steps in the opposite order 5 1 4 To open the service cover 1 Remove...

Page 5: ...re clamp 5 Close the front panel Refer to 5 1 2 To close the front panel on page 4 5 1 7 To remove the electrical wiring box cover 1 Remove the front grille 2 Remove 1 screw from the electrical wiring box 3 Open the electrical wiring box cover by pulling it to the front 4 Remove the electrical wiring box cover from the 2 rear hooks 1 2 b a c c a Screw b Electrical wiring box c Rear hook 5 To re in...

Page 6: ...ial field supply in order to prevent water leakage 1 Bore a 65 mm large feed through hole in the wall with a downward slope towards the outside 2 Insert a wall embedded pipe into the hole 3 Insert a wall cover into the wall pipe Ø65 a b c a Wall embedded pipe b Putty c Wall hole cover 4 After completing wiring refrigerant piping and drain piping do NOT forget to seal the gap with putty 5 2 3 To re...

Page 7: ...cur a b a b a Insulation fixing screw b Drain hose 4 Attach the drain hose to the refrigerant pipes bottom side using adhesive vinyl tape A B C b a A Left side piping B Left back piping C Left bottom piping a Remove the pipe port cover here for left side piping b Remove the pipe port cover here for left bottom piping To check for water leaks 1 Remove the air filters 2 Gradually pour approximately ...

Page 8: ... may NOT run parallel In order to avoid any electrical interference the distance between both wirings should ALWAYS be at least 50 mm WARNING Provide adequate measures to prevent that the unit can be used as a shelter by small animals Small animals that make contact with electrical parts can cause malfunctions smoke or fire a b c a Terminal block b Electrical component block c Wire retainer 5 Stri...

Page 9: ... reference guide The indoor units are properly mounted The outdoor unit is properly mounted Air inlet outlet Check that the air inlet and outlet of the unit is NOT obstructed by paper sheets cardboard or any other material There are NO missing phases or reversed phases The refrigerant pipes gas and liquid are thermally insulated Drainage Make sure drainage flows smoothly Possible consequence Conde...

Page 10: ...OUTDOOR Outdoor unit Wire clamp Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink BRN Brown PRP PPL Purple GRN Green RED Red GRY Grey WHT White YLW Yellow Symbol Meaning A P Printed circuit board BS Pushbutton ON OFF operation switch BZ H C Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X A K R_ Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heat...

Page 11: ...l strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite core ZF Z F Noise filter A P Printed circuit board BS Pushbutton ON OFF operation switch BZ H C Buzzer C Capacitor AC CN E HA HE HL HN HR MR _A MR _B S U V W X ...

Page 12: ...3P482320 9M 2019 04 Copyright 2019 Daikin ...

Reviews: