Indoor Unit Installation (2)

3.

Installing indoor unit.

3-1. Right-side, right-back, or right-bottom piping.

1) Attach the drain hose to the underside of the refrigerant pipes 

with an adhesive vinyl tape.

2) Wrap the refrigerant pipes and drain hose together with an 

insulation tape.

3) Pass the drain hose and refrigerant pipes through the wall 

hole, then set the indoor unit on the mounting plate hooks by 
using the    markings at the top of the indoor unit as a guide.

4) Open the front panel, then open the service lid. (Refer to 

Installation Tips.)

5) Pass the inter-unit wiring from the outdoor unit through the 

feed-through wall hole and then through the back of the indoor 
unit. Pull them through the front side. 
Bend the ends of tie wires upward for easier work in advance. 
(If the inter-unit wiring ends are to be stripped first, bundle wire 
ends with adhesive tape.)

6) Press the bottom frame of the indoor unit with both hands to 

set it on the mounting plate hooks. Make sure that the wires do 
not catch on the edge of the indoor unit.

3-2. Left-side, left-back, or left-bottom piping.

1) Attach the drain hose to the underside of the refrigerant pipes 

with adhesive vinyl tape.

2) Be sure to connect the drain hose to the drain port in place of 

a drain plug.

3) Shape the refrigerant pipe along the pipe path 

marking on the mounting plate.

4) Pass drain hose and refrigerant pipes through 

the wall hole, then set the indoor unit on 
mounting plate hooks, using the    markings at 
the top of indoor unit as a guide.

5) Pull in the inter-unit wiring.
6) Connect the inter-unit piping.
7) Wrap the refrigerant pipes and drain hose together with 

insulation tape as right figure, in case of setting the drain hose 
through the back of the indoor unit.

8) While exercising care so that the inter-unit wiring do not catch 

indoor unit, press the bottom edge of indoor unit with both hands 
until it is firmly caught by the mounting plate hooks.  Secure 
indoor unit to the mounting plate with the screws (M4 × 12L).

3-3. Wall embedded piping.

Follow the instructions given under

1) Insert the drain hose to this depth so it won’t be pulled out of 

the drain pipe.

Right-bottom 
piping

Right-back piping

Bind coolant pipe 
and drain hose 
together with 
insulating tape.

Remove pipe port cover 
here for right-side piping.

Remove pipe port cover 
here for right-bottom piping.

Mounting plate

A

Wire guide

When stripping the 
ends of inter-unit wiring 
in advance, bind right 
ends of wires with 
insulating tape.

Hang indoor unit’s hook here.

Inter-unit wiring

Mounting plate

A

Remove pipe port cover here for left-bottom piping.

Remove pipe port 
cover here for 
left-side piping.

Left-bottom piping

Left-side 
piping

Left-back 
piping

How to set drain plug

No gap

Do not apply lubricating 
oil (refrigerant oil) when 
inserting.
Application of causes 
deterioration and drain 
leakage of the plug.

Insert a hexagon wrench (4mm)

Wrap insulating tape around the 
bent portion of refrigerant pipe. 
Overlap at least half the width 
of the tape with each turn.

Drain 
hose

Caulk this hole 
with putty or 
caulking material.

Bind with plastic 
tape.

 A Mounting plate

Refrigerant
pipes

Drain hose

Bottom frame

H  M4 

×

 12L (2 point)

Mounting
plate

A

Left-side, left-back, or left-bottom piping   

.

Inner wall

Vinyl chloride 
drain pipe 
(VP-30)

Drain hose

50mm 
or more

Insert drain hose to this 
depth so it won’t be 
pulled out of drain pipe.

Outer wall

Summary of Contents for FTXS80FVMA

Page 1: ...oxic gas if exposed to flames Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage If the gas leaks and builds up around the unit it may catch fire Establish drain piping according to the instructions of this manual Inadequate piping may cause flooding Tighten the flare nut according to the specified method such as with a torque wrench If the f...

Page 2: ...and open until the panel stops Slide the front panel sideways to disengage the rotating shaft Then pull the front panel toward you to remove it Installation method Align the tabs of the front panel with the grooves and push all the way in Then close slowly Push the center of the lower surface of the panel firmly to engage the tabs 2 Removing and installing front grille Removal method 1 Remove fron...

Page 3: ...ceived by indoor unit How to attach the indoor unit Hook the claws of the bottom frame to the mounting plate If the claws are difficult to hook remove the front grille How to remove the indoor unit Push up the marked area at the lower part of the front grille to release the claws If it is difficult to release remove the front grille Mounting plate fixing screws M4 25L 9 B Fixing screws for remote ...

Page 4: ... 1 Bore a feed through hole of 80mm in the wall so it has a down slope toward the outside 2 Insert a wall pipe into the hole 3 Insert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty Indoor Unit Installation 1 125 60 83 413 5 44 5 290 52 1050 99 5 52 90 55 100 100 Keep here the piece cut out from the unit for piping Through th...

Page 5: ...rant pipes and drain hose together with insulation tape as right figure in case of setting the drain hose through the back of the indoor unit 8 While exercising care so that the inter unit wiring do not catch indoor unit press the bottom edge of indoor unit with both hands until it is firmly caught by the mounting plate hooks Secure indoor unit to the mounting plate with the screws M4 12L 3 3 Wall...

Page 6: ...air filters and pour some water into the drain pan to check the water flows smoothly 3 When drain hose requires extension obtain an extension hose commercially available Be sure to thermally insulate the indoor section of the extension hose 4 When connecting a rigid polyvinyl chloride pipe nominal diameter 13mm directly to the drain hose attached to the indoor unit as with embedded piping work use...

Page 7: ...lass I D 14 16mm Gas side Minimum bend radius Gas pipe thermal insulation 50 60 71 80 90 classs O D 6 4mm 30mm or more Thickness 0 8mm C1220T O 50 60 71 80 90 class I D 8 10mm Liquid side Liquid pipe thermal insulation Flare nut tightening torque Gas side Liquid side 1 2 inch 49 5 60 3N l m 505 615kgf l cm 61 8 75 4N l m 630 770kgf l cm 14 2 17 2N l m 144 175kgf l cm 5 8 inch 1 4 inch 1 Use the fl...

Page 8: ...6 C to 28 C in cooling mode 20 C to 24 C in heating mode 3 For protection the system disables restart operation for 3 minutes after it is turned off n For Cooling only Select the lowest programmable temperature 1 Trial operation in cooling mode may be disabled depending on the room temperature Use the remote controller for trial operation as described below 2 After trial operation is complete set ...

Reviews: