Safety Precautions

• The precautions described herein are classified as WARNING and CAUTION. They both contain important 

information regarding safety. Be sure to observe all precautions without fail. 

• Meaning of WARNING and CAUTION notices 

WARNING.....Failure to follow these instructions properly may result in personal injury or loss of life. 

CAUTION......Failure to observe these instructions properly may result in property damage or personal injury, which 

may be serious depending on the circumstances. 

• The safety marks shown in this manual have the following meanings: 

• After completing installation, conduct a trial operation to check for faults and explain to the customer how to operate  

the air conditioner and take care of it with the aid of the operation manual.

• The English text is the original instruction. Other languages are translations of the original instructions. 

Be sure to follow the instructions. 

Be sure to establish an earth connection. 

Never attempt. 

WARNING

• Ask your dealer or qualified personnel to carry out installation work. 

Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire. 

• Install the air conditioner in accordance with the instructions in this installation manual. 

Improper installation may result in water leakage, electric shocks or fire. 

• Be sure to use only the specified accessories and parts for installation work. 

Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. 

A foundation of insufficient strength may result in the equipment falling and causing injury. 

• Electrical work must be performed in accordance with relevant local and national regulations and with instructions 

in this installation manual. Be sure to use a dedicated power supply circuit only. 

Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire. 

• Use a cable of suitable length. 

Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire. 

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal 

connections or wires. 

Improper connections or securing of wires may result in abnormal heat build-up or fire. 

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires 

so that the control box lid can be securely fastened. 

Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals. 

• If refrigerant gas leaks during installation, ventilate the area immediately. 

Toxic gas may be produced if the refrigerant comes into contact with fire. 

• After completing installation, check for refrigerant gas leakage.  

Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire, such as a fan heater, 
stove or cooker. 

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, 

and use only the specified refrigerant (R410A). 

The presence of air or other foreign matter in the refrigerant circuit causes abnormal pressure rise, which may result in equipment damage 
and even injury. 

• During installation, attach the refrigerant piping securely before running the compressor. 

If the refrigerant pipes are not attached and the stop valve is open when the compressor is run, air will be sucked in, causing abnormal 
pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• During pump-down, stop the compressor before removing the refrigerant piping. 

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed, 
causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• Be sure to earth the air conditioner. 

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks. 

• Be sure to install an earth leakage breaker. 

Failure to install an earth leakage breaker may result in electric shocks or fire. 

CAUTION

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage.  

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out. 

• While following the instructions in this installation manual, install drain piping to ensure proper drainage 

and insulate piping to prevent condensation. 

Improper drain piping may result in indoor water leakage and property damage. 

• Tighten the flare nut according to the specified method such as with a torque wrench. 

If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage. 

Summary of Contents for FTXS35K2V1B

Page 1: ...N MANUAL R410A Split Series English Deutsch Français Nederlands Español Italiano Eλληνικά Portugues Pyccкий Türkçe MODELS FTXS35K2V1B FTXS35K3V1B FTXS42K2V1B FTXS42K3V1B FTXS50K2V1B FTXS50K3V1B ATXS35K2V1B ATXS35K3V1B ATXS50K2V1B ATXS50K3V1B ...

Page 2: ...ndo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Informatio...

Page 3: ...a delineato nel A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt v...

Page 4: ...αι κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Mer...

Page 5: ...n abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produ...

Page 6: ...as they may shorten the remote controller range 8 the unit is at least 1m away from any television or radio set unit may cause interference with the picture or sound 9 no laundry equipment is located 2 Wireless remote controller Turn on all the fluorescent lamps in the room if any and find the site where remote controller signals are properly received by the indoor unit within 7m This appliance is...

Page 7: ...front grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space because the unit is close to ceiling CAUTION Be sure to wear protection gloves Place both hands under the centre of the front grille and while pushing up pull it toward you Installation method 1 Install the front gril...

Page 8: ...lle Opening the service lid The service lid is removable 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mounting plate should be installed on a wall which can support the weight of the indoor unit 30mm or more from ceiling Front panel 50mm or more from walls on both sides Air filters Mounting plate Mounting plate Mounting plat...

Page 9: ... into the hole 3 Insert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curing refrigerant pipes keep the following precautions in mind Abnormal sound may be generated if improper work is conducted 1 Do not strongly press the refrigerant pipes onto the bottom frame 2 Do n...

Page 10: ...late hooks by using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the outdoor unit through the feed through wall hole and then through the back of the indoor unit Pull them through the front side Bend the ends of tie wires upward for easier work in advance If the inter ...

Page 11: ...cing onto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tighten with included insulation fixing screw Forgetting to tighten this may cause water leakages Drain hose attachment position The drain hose is on the back of the unit Front side of unit Attachmen...

Page 12: ...ess remote controller SIGNAL RECEIVER Signal receiver BZ Buzzer C101 C102 Capacitor FG Frame ground F1U Fuse 3 15A H1P H3P Pilot lamp MR10 Magnetic relay M1F Fan motor M1S M3S Swing motor PCB1 PCB4 Printed circuit board R1T R2T Thermistor S1 S9 Connector SW1 Operation switch V1 Varistor X1M Terminal strip Protective earth CAUTION Note that operation will restart automatically if the main power sup...

Page 13: ...ot connect the power wire to the indoor unit Doing so may cause electric shock or fire 5 When connecting to an HA system Wired remote controller central remote controller etc 1 Remove the metal plate electrical wiring cover Refer to the Removal attachment methods of metal plate electrical wiring covers 2 Snap off the claw 3 Attach the connection cord to the S21 connector and pull the harness out t...

Page 14: ...ctrical wiring covers as shown below 1 Lean the metal plate electrical wiring cover as shown in the figure and attach tab 1 on the lower side to the electrical wiring box 2 Attach tab 2 on the lower side of the metal plate electrical wiring cover 3 Push in the upper part of the metal plate electrical wiring cover and attach the 3 tabs 3 Raise the 2 upper parts of the metal plate electrical wiring ...

Page 15: ...y made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never install a dryer to this R410A unit in order to guarantee its lifetime The drying material may dissolve and damage the system Incompl...

Page 16: ...hes 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation 35 42 class 50 class O D 6 4mm I D 12 15mm I D 8 10mm O D 9 5mm O ...

Page 17: ...he system will restore the original operation mode when the circuit breaker is opened again 2 Test items If the is not displayed make sure not to cut the switching jumper J8 for cooling operation when cutting the address jumper If it has been cut replace the remote controller Trial operation from remote controller 1 Press ON OFF button to turn on the system 2 Press TEMP button 2 locations and MODE...

Page 18: ......

Page 19: ......

Page 20: ...3P363588 2B 2014 06 Copyright 2013 Daikin ...

Reviews: