Troubleshooting
SiUS041829E
100
Part 6 Service Diagnosis
4.20 Position Sensor Abnormality
Error Code
H6
Method of Error
Detection
A compressor start-up failure is detected by checking the compressor running condition through the
position detection circuit.
Error Decision
Conditions
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 11 minutes without any other error
Supposed
Causes
Power supply voltage out of specification
Disconnection of the compressor harness
Defective compressor
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage outside the specified range
Summary of Contents for FTXR-T Series
Page 17: ...SiUS041829E Part 2 Specifications 13 1 Specifications 14 Part 2 Specifications...
Page 125: ...SiUS041829E Check Part 6 Service Diagnosis 121 18 class R25105 1 2 3 4 Multimeter...
Page 127: ...SiUS041829E Check Part 6 Service Diagnosis 123 18 class R20704 W V U DC_P1 DC_N1...
Page 143: ...SiUS041829E Operation Limit Part 8 Appendix 139 4 Operation Limit RX09 12 18RMVJU9 3D092209E...