![background image](http://html1.mh-extra.com/html/daikin/ftxn25l9/ftxn25l9_technical-data-manual_2459484006.webp)
• Indoor Unit • Wall mounted unit • FTXN-L9
1
2
• Split - Sky Air • Indoor Unit
4
2
Specifications
Standard Accessories : Titanium apatite filters;
Standard Accessories : Mounting plate;
Standard Accessories : Remote control holder;
Standard Accessories : Batteries;
Standard Accessories : Wireless remote control;
Standard Accessories : Operation manual;
Standard Accessories : Installation manual;
Fan motor
Quantity
1
Model
MWM10/15J-501
MWMY20/25JR
Index of Protection
20
Insulation grade
Class "E"
Poles
4
8
Drive
Direct drive
Speed
Steps
3 steps, turbo, quiet, auto
Cooling High/
Mediu
m/Low/
Silent
operati
on
rpm
1,240/1,020/850/700
1,280/1,050/900/700
1,050/960/870/800
1,250/1,140/1,010/900
Heating High/
Mediu
m/Low/
Silent
operati
on
rpm
1,240/1,020/850/700
1,280/1,050/900/700
1,090/960/870/800
1,280/1,140/1,010/900
Phase x Voltage
V
1 x 230V
DC310
Full load amps
(FLA)
Cooling
A
0.19
0.21
0.32
0.56
Heating
A
0.19
0.21
0.33
0.56
Sound power level
Cooling
High
dBA
53
54
55
61
Sound pressure level
Cooling
Super high/High/
Nom./Low/Silent
operation
dBA
41/40/34/29/21
42/41/34/30/22
44/40/38/35/32
46/43/41/37/33
Heating
Super high
dBA
-
Refrigerant
Type
R-410A
Piping connections
Liquid
Type/OD
mm
Flare valve/6.35
Gas
Type/OD
mm
Flare valve/9.5
Flare valve/12.7
Flare valve/15.9
Drain
16.5
Heat insulation
Both liquid and gas pipes
Temperature control
Microcomputer control
Air direction control
Right, Left, Horizontal, Downward
Air filter
Type
Titanium apatite
Quantity
pc
2
2-2 Electrical Specifications
FTXN25L9
FTXN35L9
FTXN50L9
FTXN60L9
Power supply
Name
V1
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
-10
Max.
%
10
Current
Nominal running
current (RLA) - 50Hz
Cooling
A
4.07
4.92
6.84
8.59
Heating
A
3.86
5.12
6.72
7.63
Current - 50Hz
Maximum running current
A
7.19
7.21
10.0
Maximum fuse amps (MFA)
A
16
20
Wiring connections -
50Hz
For power supply
Quantity
3
Remark
3 for power supply, 4 for interunit wiring (Earth wire included)
2-1 Technical Specifications
FTXN25L9
FTXN35L9
FTXN50L9
FTXN60L9
Summary of Contents for FTXN25L9
Page 1: ...Air Conditioning Technical Data Wall mounted unit EEDEN13 004A FTXN L9...
Page 2: ......
Page 14: ......