FTXM-V Series EDUS042101
119
3P627027-1
1-3-2 Installation site
•
Provide sufficient space around the unit for servicing and air
circulation as outlined in the unit installation manual.
• Make sure the installation site withstands the weight and
vibration of the unit.
•
Make sure the area is well ventilated. Do NOT block any
ventilation openings.
•
Make sure the unit is level.
Do NOT install the unit in the following places:
•
In potentially explosive atmospheres.
• In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control
system, and cause malfunction of the equipment.
•
In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fiber,
or ignitable dust.
• In places where corrosive gas (example: sulfurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may
cause the refrigerant to leak.
Instructions for equipment using R32 refrigerant
WARNING: FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
•
Do NOT pierce or burn.
• Do NOT use means to accelerate the defrosting
process or to clean the equipment, other than those
recommended by the manufacturer.
•
Be aware that R32 refrigerant does NOT contain an
odor.
WARNING
The appliance should be stored so as to prevent
mechanical damage and in a well-ventilated room
without continuously operating ignition sources
(example: open flames, an operating gas appliance or
an operating electric heater), and the room size should
be as specified.
(Refer to “Minimum required floor area for each
refrigerant amount charged” on page 1.)
WARNING
Ventilated area
Ensure that the area is in the open or that it is
adequately ventilated before breaking into the system
or conducting any hot work. A degree of ventilation
should continue during the period that the work is
carried out. The ventilation should safely disperse any
released refrigerant and preferably expel it externally
into the atmosphere.
WARNING
Make sure installation, servicing, maintenance and
repair comply with instructions from Daikin and with
applicable legislation (for example national gas
regulations) and are executed only by authorized
persons.
WARNING
If one or more rooms are connected to the unit using a
duct system, make sure:
• there are no operating ignition sources (example:
open flames, an operating gas appliance or an
operating electric heater) in case the floor area is less
than A
min
(ft
2
) defined in the table
(Refer to “Minimum required floor area for each
refrigerant amount charged” on page 1.)
• no auxiliary devices, which may be a potential ignition
source, are installed in the duct work (example: hot
surfaces with a temperature exceeding 158°F and
electric switching devices)
• only auxiliary devices approved by the manufacturer
are used in the duct work
• an air inlet or outlet is connected directly with a room
by ducting. Do NOT use spaces such as a false ceiling
as a duct for the air inlet or outlet.
CAUTION
Do NOT use potential sources of ignition in searching
for or detection of refrigerant leaks.
NOTICE
•
Do NOT re-use joints which have been used already.
• Joints made during installation between parts of the
refrigerant system should be accessible for
maintenance purposes.
NOTICE
• Precautions should be taken to avoid excessive
vibration or pulsation of refrigeration piping.
•
Protection devices, piping and fittings should be
protected as much as possible against adverse
environmental effects.
• Provisions should be made for expansion and
contraction of long sections of piping.
• Piping in refrigerating systems should be designed
and installed so that the likelihood of hydraulic shock
damaging the system is minimized.
• The indoor equipment and pipes should be securely
mounted and guarded so that accidental rupture of
equipment or pipes cannot occur from events such as
moving furniture or reconstruction activities.
4
01_EN_3P627027-1.indd 4
2021/02/08 15:05:33
Summary of Contents for FTXM09VVJU
Page 1: ...Heat Pump Split Type Air Conditioners FTXM V Series EDUS042101...
Page 2: ......
Page 10: ...8 FTXM V Series EDUS042101 C 3D129694 FTXM24VVJU...
Page 11: ...FTXM V Series EDUS042101 9 3D123362 RXM18VVJU 3D131944B RXM09 12VVJU 4 2 Outdoor Unit...
Page 12: ...10 FTXM V Series EDUS042101 3D107983A RXM24VVJU...
Page 14: ...12 FTXM V Series EDUS042101 C 3D129644B RXM18 24VVJU C 3D129643B RXM09 12VVJU 5 2 Outdoor Unit...
Page 16: ...14 FTXM V Series EDUS042101 3D132216 RXM18VVJU 3D131979 RXM09 12VVJU 6 2 Outdoor Unit...
Page 17: ...FTXM V Series EDUS042101 15 3D132217 RXM24VVJU...
Page 28: ...26 FTXM V Series EDUS042101 3D133582A 8 Operation Limit...
Page 30: ...28 FTXM V Series EDUS042101 C 3D133575 FTXM12VVJU C 3D133574 FTXM09VVJU 9 2 Indoor Unit...
Page 31: ...FTXM V Series EDUS042101 29 C 3D133577 FTXM24VVJU C 3D133576 FTXM18VVJU...
Page 32: ...30 FTXM V Series EDUS042101 C 3D133581 RXM12VVJU C 3D133580 RXM09VVJU 9 3 Outdoor Unit...
Page 33: ...FTXM V Series EDUS042101 31 C 3D133618 RXM24VVJU C 3D133617 RXM18VVJU...
Page 117: ...FTXM V Series EDUS042101 115 C 3P628774 1 Quick Reference...
Page 149: ...FTXM V Series EDUS042101 147 1P124687 1A...
Page 150: ...148 FTXM V Series EDUS042101 1P124687 1A...
Page 151: ...FTXM V Series EDUS042101 149 1P124687 1A...
Page 152: ...150 FTXM V Series EDUS042101 1P124687 1A...
Page 156: ...154 FTXM V Series EDUS042101 3P124623 1E 4 Fig 6 Fig 5 Fig 8 Fig 7...
Page 167: ...FTXM V Series EDUS042101 165 3P124623 1E 15...
Page 177: ...FTXM V Series EDUS042101 175 3P124623 1E 25 Fig 9 Fig 12 Fig 10 Fig 11...
Page 178: ...176 FTXM V Series EDUS042101 3P124623 1E 26 Fig 14 Fig 13 Fig 16 Fig 15...
Page 180: ...178 FTXM V Series EDUS042101 1P126474 1B...
Page 181: ...FTXM V Series EDUS042101 179 1P126474 1B...
Page 182: ...180 FTXM V Series EDUS042101 1P126474 1B...
Page 183: ...FTXM V Series EDUS042101 181 1P126474 1B...
Page 188: ...186 FTXM V Series EDUS042101 3P162015 1A...
Page 189: ...FTXM V Series EDUS042101 187 3P162015 1A...
Page 190: ...188 FTXM V Series EDUS042101 3P162015 1A...
Page 191: ...FTXM V Series EDUS042101 189 3P162015 1A...
Page 207: ...FTXM V Series EDUS042101 205 3P534932 1D 13 14 KPW063B4 Air Direction Adjustment Grille...
Page 208: ...206 FTXM V Series EDUS042101 3P534932 1D...
Page 209: ...FTXM V Series EDUS042101 207 2P403095 1 13 15 KKG063A42 Back Protection Wire Net...
Page 229: ...FTXM V Series EDUS042101 227 3P436071 1 13 21 KPS063A41 Snow Hood Intake Side Plate...
Page 230: ...228 FTXM V Series EDUS042101 3P436071 1...
Page 231: ...FTXM V Series EDUS042101 229 3P436072 1 13 22 KPS063A44 Snow Hood Intake Rear Plate...
Page 232: ...230 FTXM V Series EDUS042101 3P436072 1...
Page 233: ...FTXM V Series EDUS042101 231 3P436073 1 13 23 KPS063A47 Snow Hood Outlet...
Page 234: ...232 FTXM V Series EDUS042101 3P436073 1...
Page 235: ......