Control Specification
Part 4 Functions and Control
65
3.4.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
The function is not used when defrosting.
3.4.5 Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency is set as follows. (The
function is not used when defrosting.)
09/12 class
18/24 class
Cooling
Heating
Cooling
Heating
A
(Hz)
36
36
48
48
B
(Hz)
52
52
48
48
C
(Hz)
68
68
62
62
D
(Hz)
80
80
80
80
E
(Hz)
110
110
—
—
F
(sec)
120
120
100
100
G
(sec)
120
120
800
800
H
(sec)
480
480
300
300
J
(sec)
180
180
470
470
K
(sec)
600
600
—
—
(sec.)
Time
(R23251)
(Hz)
Freq
u
ency
C
D
E
B
F
G
H
J
K
A