Check
SiBE041434E
105
Service Diagnosis
5.12 Main Circuit Short Check
Check No.20
Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is
approximately 0 V before checking.
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is
∞
or less than 1 k
Ω
, short circuit occurs on the main circuit.
20/25/35 class
42/50 class
Positive terminal (+) of
digital multimeter
~
(2, 3)
+
(4)
~
(2, 3)
–
(1)
Negative terminal (–) of
digital multimeter
+
(4)
~
(2, 3)
–
(1)
~
(2, 3)
Resistance is OK.
several k
Ω
~ several M
Ω
Resistance is NG.
0
Ω
or
∞
(R19933)
1
2
3
4
Multimeter
–~
~
+
–
+
(R21203)
1
2
3
4
Multimeter
–~
~
+
–
+