background image

11

English

Indoor Unit Installation

6.

Drain piping

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water flows 

smoothly.

3) If drain hose extension or embedded drain piping is required, use appropriate parts that match the hose front end.

[Figure of hose front end]

4) When extending the drain hose, use a commercially 

available extension hose with an inner diameter of 
16mm. Be sure to thermally insulate the indoor section of 
the extension hose.

5) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with 
embedded piping work, use any commercially 
available drain socket (nominal diameter 13mm) 
as a joint.

Refrigerant Piping Work

1.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a dryer to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

Indoor unit 
drain hose

Extension drain hose

Heat insulation tube 
(field supply)

Drain hose supplied 
with the indoor unit

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

Drain hose supplied 
with the indoor unit

A

A

(Cut exactly at 
right angles.)

Remove burrs.

Set exactly at the position shown below.

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

(Ri

d

gid-type)

1.5-2.0mm

(Imperial-type)

Conventional flare tool

Summary of Contents for FTXLS25K3V1B

Page 1: ...DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series MODELS FTXLS25K3V1B FTXLS35K3V1B DAIKIN...

Page 2: ......

Page 3: ...ivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B...

Page 4: ...cause overheating electric shocks or fire Make sure that all wiring is secured the specified wires are used and that there is no strain on the terminal connections or wires Improper connections or se...

Page 5: ...emote controller signals are properly received by the indoor unit within 7m CAUTION Do not install the air conditioner at any place where there is a danger of flammable gas leakage In the event of a g...

Page 6: ...grille there are 3 upper hooks Lightly pull the front grille toward you with one hand and push down on the hooks with the fingers of your other hand When there is no work space because the unit is cl...

Page 7: ...move the front grille Opening the service lid The service lid is removable 1 Remove the service lid screw 2 Pull out the service lid diagonally down in the direction of the arrow 3 Pull down The mount...

Page 8: ...o the hole 3 Insert a wall cover into wall pipe 4 After completing refrigerant piping wiring and drain piping caulk pipe hole gap with putty 3 Installing the indoor unit In the case of bending or curi...

Page 9: ...late hooks by using the markings at the top of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to preparation before installation 5 Pass the inter unit wire from the...

Page 10: ...onto the left side 1 Remove the insulation fixing screw on the right and remove the drain hose 2 Remove the drain plug on the left side and attach it to the right side 3 Insert the drain hose and tig...

Page 11: ...R T THERMISTOR DS DIPSWITCH RC RECEIVER E H HEATER S C LIMITSWITCH F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S L FLOATSWITCH FG CONNECTOR FRAMEGROUND S NPH PRESSURESENSOR HIGH H HARNESS...

Page 12: ...nnect the power wire to the indoor unit Doing so may cause electric shock or fire 5 When connecting to an HA system Wired remote controller central remote controller etc 1 Remove the metal plate elect...

Page 13: ...trical wiring covers as shown below 1 Lean the metal plate electrical wiring cover as shown in the figure and attach tab 1 on the lower side to the electrical wiring box 2 Attach tab 2 on the lower si...

Page 14: ...properly made WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for pre...

Page 15: ...frigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide ins...

Page 16: ...stem will restore the original operation mode when the circuit breaker is opened again 2 Test items If the is not displayed make sure not to cut the switching jumper J8 for cooling operation when cutt...

Page 17: ......

Page 18: ...3P377527 3D 2017 03 Copyright 2015 Daikin...

Reviews: