Function & Control
22
2.20 Overall Current Control
To monitor the overall current and to restrict the compressor upper limit rotation in order to prevent circuit
breakers from exceeding the rated capacity.
Detected during compressor running.
Current (A)
L1
L2
L3
Stop zone
Reset zone
Frequency
reduce zone
Frequency
remain zone
Model
L1
ARXN/RXN25/35L/M
14.0A
ARXN/RXN50/60_L
12.0A
ARXN/RXN50/60M
RXB50/60B
RX50/60CGXV1
16.5A
When the input current for running compressor exceeds L2, running frequency will be reduced by 1 step. If
current still exceeds L2, frequency will be reduced by another 1 step until total current falls between L2 and
L3.
This protection cut in when the input current exceeds L1 for 2 seconds. Compressor will stop and it is
considered total current overload.
If input current < L3, the compressor frequency is reset based on the OD ambient, set and room
temperature.
Summary of Contents for FTXB50BV1B
Page 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A...
Page 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M...
Page 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L...
Page 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M...