background image

Outdoor Unit 

4.

Purging air and checking gas leakage

it, 

WARNING-----------------------

• Make sure that air or any matter other than refrigerant (R32) does not get into the refrigeration cycle. 

• If refrigerant gas leaks occur, ventilate the room as soon and as much as possible. 

• To prevent air pollution, a vacuum pump should be used for air  purging  wherever possible. 

• If using additional refrigerant, purge the air from the refrigerant pipes  and 

indoor unit using a vacuum pump, then charge additional refrigerant. 

• Use a  hexagonal  wrench to operate the stop valve rod. 

• All 

refrigerant pipe joints should be  tightened with a torque wrench to the 

specified tightening torque. 

1) Connect projection side (on which pin is pressed) of charging hose (which comes from gauge 

manifold) to gas stop valve's service port. 

2)  Fully open gauge manifold's low-pressure valve (Lo) and completely close its high-pressure valve (Hi). 

(High-pressure valve will require no further operation.) 

3)  Begin vacuum pumping and make sure that the compound pressure gauge reads --0.1 MPa (-76cmHg) *1. 

4)  Close the gauge manifold's low-pressure valve (Lo) and stop vacuum pumping. 

(Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer 

does not swing back.) *2. 

5) Remove the valve caps from the liquid stop valve and gas stop valve. 

6) Turn the liquid stop valve's rod 90

° 

counter-clockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage. 

Using soapy water, check for gas leakage from indoor unit's flare and outdoor unit's flare and valve rods. 

After the check is complete, wipe all soapy water off. 

7) Disconnect charging hose from the gas stop valve's service port, then fully open the liquid and gas stop valves. 

(Do not attempt to turn the valve rod further than it can go.) 

8) Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench 

to the specified torques. 

*1. Pipe length vs. vacuum pump run time 

Pipe length  I Up to 15m 

More than 15m 

*2.  If the compound pressure gauge pointer swings back, the 

refrigerant may have water content or there may be a 

loose pipe joint. Check all pipe joints and retighten nuts as 

needed, then repeat steps 2) through 4). 

Run time  I At least 1 O min. 

At least 15 min. 

5.

Wiring

it, 

WARNING---------------

Never use short cables for connecting  end of conductor to each other. 

• For inter-unit wiring, refer to 

"4. Wiring" 

in the section 

"Indoor Unit".

•  Regarding the inter-unit wire 

and power supply wire. 

• When connecting the inter-unit wire to the terminal block 

using a single core wire, be sure to curl the end of the lead. 

Improper work may cause heat and fire. 

;:::t·'�mm1aL 

-

�:) 

� 

�retamer 

�  � 

QGood 

XWrong 

Stripping wire at terminal block 

• Precautions to be taken for power supply wiring. When using 

stranded  wires, make sure to use the round crimp-style 

terminal for connection to the power supply terminal block. 

Place the round crimp-style terminals on the wires up to the 

covered part and secure in place. 

XWrong 

Precautions to be taken for power supply wiring. When using starnded wires, 

/ Flat washer 

Screw 

� Rou�d crimp-style 

terminal 

Screw 

Compound 

Pressure meter 

pressure gauge 

'-'---· 

Gauge 

----.j 

manifold  L'i> 

Low-

High-

I I 

Liquid 

pressure 

caps  stop 

valve 

Charging 

hoses 

Vacuum pump 

Service port  valie 

Round crimp­

style terminal 

� 

Stranded wire 

'�

QA

J)� 

Round crimp-style terminal 

� Flat washer 

Good 

Arrow view A 

/

Screw 

�--- Flat washer 

�- Round crimp-style 

terminal 

XWrong 

6. Drain work

•  If the drain port is covered by a mounting base or floor surface, place additional foot bases of at least 30mm in 

height under the outdoor unit's feet. 

10 

Summary of Contents for FTKZ50UV16U4

Page 1: ...DAIKIN DAIKIN ROOM AIR CONDITIONER 3P665364 3T M21P078B OPERATION MANUAL MODELS FTKZ50UV16U4 fC _JNVERTER 3P665364 3T M21P078B...

Page 2: ...quality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that produce naked flam...

Page 3: ...beep sound Case Sound type Operation start beep beep Settings changed Operation stop 12 OPERATION lamp green 13 TIMER lamp orange 14 lndoor unit ON OFF switch beep long beep Press this switch once to...

Page 4: ...cts the operation mode COOUDRY FAN 8 Eco button Eco Operation 9 Timer button 1o Display button 7 11 12 1 RB2CA1 2 8 5 4 3 6 _ ____ 4 8 DAIKIN Displays the ambient temperature set temperature and turn...

Page 5: ...ls between the unit and the remote controller such as a curtain the unit will not operate Do not drop the remote controller Do not get it wet The maximum transmission distance is about 7m Receiver To...

Page 6: ...g cannot be changed Default Set Temperature Setting As per BEE regulation whenever Air Conditioner will be switched ON from the remote the default set temperature will be set as mentioned in below tab...

Page 7: ...r turn off child lock function When child lock functions is on 1111 icon is displayed on remote controller If you operate the remote controller the 1111 icon will blink three times without sending sig...

Page 8: ...is displayed on the LCD The louvres vertical blades will begin to swing The 3 D airflow direction 1 Press and and are displayed on the LCD The flap and louvres move in turn To cancel 3 D airflow press...

Page 9: ...To cancel I FEEL operation 2 Press 8 again 1 1 1 1 is disappears from the LCD NOTE Notes on ECO operation ECO operation can only be set when the unit is running Pressing Causes the settings to be can...

Page 10: ...set hour is 0 0 hour NOTE 9 Note on TIMER operation Once you set Timer Sleep operation the time setting is kept in the memory The memory is cleared when the remote controller batteries are replaced Ti...

Page 11: ...disengage one of the front panel shafts 2 Disengage the front panel shaft on the other side in the same manner 3 After disengaging both front panel shafts pull the front panel toward yourself and rem...

Page 12: ...rt the filters into slots of the front grille Close the front panel slowly and push the panel at the 3 points I Accessory filter I Filter type Ag ion filter Micro filter PM2 5 Maintenance 11 The acces...

Page 13: ...1 set Ag ion filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Part No KAF970A45 KAF057A41 KAF500A504 KAF250A502 Operation with dirty filters 1 cannot deodorise the air 3 results in po...

Page 14: ...is heard A sound like flowing water This sound is generated because the refrigerant in the air conditioner is flowing This is a pumping sound of the water in the air conditioner and can be heard when...

Page 15: ...breaker been tripped or the fuse blown operate Is there a power failure OPERATION lamp is off Are batteries set in the remote controller Is the timer setting correct The room does not cool down Is th...

Page 16: ...air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood stop operation and turn off the circ...

Page 17: ...ompressor overload protection 17 Anti freezina orotection 18 4 wav valve reversed malfunction protection 19 ODU ambient temperature malfunction protection 20 Comoressor non svnchronism orotection 21 C...

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ...is properly installed Water leakage System is properly earthed Electrical leakage Only specified wires are used for all wiring and all No operation or burn damage wires are connected correctly Indoor...

Page 22: ...open theliquidand gas stop valves Do not attempt to turn the valve rod further than it can go 8 Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to...

Page 23: ...scaping gas Piping size Flare nut Valve cap Service port cap tightening torque tightening torque tightening torque Gas side O D 12 7mm 35 43N m 25 31N m 357 439kgl cm 255 316kgfocm 10 8 14 N m Liquid...

Page 24: ...wly Push the centre of the lower surface of the panel firmly ntpanel shaft GrooveHr Removing and installing the front grille Removal method 1 Remove the front panel and air filters 2 Remove the flap h...

Page 25: ...rant Failure to do so may result in reduced performance 30m 3m 20m 20g m The suggested shortest pipe length is 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibra...

Page 26: ...yl tape This illustration shows the case of the left rear piping wire Sectional view Heat Insulation pipe cover Insulation tape Ventilation hose Overwrap more than half of heat insulation tape Wrap th...

Page 27: ...____ _ umt Firmly fix the wires with the terminal screws Outdoor unit Power supply wire 3 core 1 5mm2 or more IS 694 ir Earth leaka circuit breake A voltage stabilizer is not needed Model Protectionag...

Page 28: ...he mounting plate hooks 5 Pull in the inter unit wire 6 Connect the refrigerant pipes 7 Wrap the refrigerant pipes and drain hose together withinsulation tape fieldsupply as shown in the figure in cas...

Page 29: ...bedded pipe and wall hole cover in the feed through hole to prevent possible heat electrical shock or fire Be sure to caulk the gaps around the pipes with caulking material to prevent inside Outside w...

Page 30: ...there is no fear of inflammable gas leakage 7 the unit is away from electronic ignition type fluorescent lamps inverter or rapid start type as they may affect the remote controller range 8 the unit i...

Page 31: ...t gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leaka...

Page 32: ...3P665364 3T M21P086B DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL r J C INVERTEI MODELS FTKZ50UV16U4 3P665364 3T M21P086B...

Reviews: