Check
SiENBE04-507A
148
Service Diagnosis
5.1.7 Outdoor Unit Fan System Check
Check No.9
DC motor
5.1.8 Power Supply Waveforms Check
Check No.10
Measure the power supply waveform between pins 1 and 3 on the terminal board, and check
the waveform disturbance.
Check to see if the power supply waveform is a sine wave (Fig.1).
Check to see if there is waveform disturbance near the zero cross (sections circled in Fig.2)
5.1.9 Inverter Units Refrigerant System Check
Check No.11
Check the outdoor unit fan system.
(R2857)
Outdoor unit fan running?
Fan motor lead wire
connector disconnected?
Outdoor unit fan system
functioning.
Go to
Check No. 15
.
NO
NO
YES
YES
Reconnect.
[Fig.1]
[Fig.2]
Di
s
ch
a
rge pre
ssu
re check
Repl
a
ce compe
ss
or.
Open the
s
top v
a
lve.
Repl
a
ce the pipe in
s
t
a
lled
a
t
the
s
ite.
Cle
a
n.
Repl
a
ce the compre
ss
or.
At the he
a
t exch
a
nger
a
nd
a
ir filter dirty?
I
s
the
s
top v
a
lve open?
I
s
the connection
pipe deformed?
High
YE
S
YE
S
NO
NO
NO
YE
S
YE
S
NO
Summary of Contents for FTKS20DVMW(L)
Page 10: ...SiENBE04 507A List of Functions 1 Part 1 List of Functions 1 List of Functions 2...
Page 85: ...Control Specification SiENBE04 507A 76 Function and Control...
Page 159: ...Check SiENBE04 507A 150 Service Diagnosis...
Page 215: ...Others SiENBE04 507A 206 Others...
Page 221: ...Wiring Diagrams SiENBE04 507A 212 Appendix...
Page 225: ...SiENBE04 507A iv Index...