71
Installation and Maintenance
Service Manual
11.2 Removal Procedure of Outdoor Unit
Warning: Be sure to wait for a minimum of 20 minutes
after turning off all power supplies and discharge the
refrigerant completely before removal.
Procedure
Steps
1.Remove cable cross plate 2 and valve cover
2.Remove top cover
Before disassamble
.
Remove 3 connection screw fixing cable
cross plate 2 and then remove the Cable
cross plate 2.
Remove 1 connection screw fixing valve cover
and then remove the valve cover.
Remove 3 connection screws among
top cover plate, front panel and right
side plate. Then remove top cover
plate.
screw
Cable cross plate 2
Valve Cover
screw
top cover plate
RKS09SL216
RXS09SL216
RKS12SL216
RXS12SL216