INDOOR UNIT INSTALLATION
Mounting the remote controller
Refer to the “installation manual of the remote controller” supplied with remote controller.
Wall mounted type/floor standing concealed type
The unit requires minimum 100mm clearance (
F
) and clearance (
E
) on the bottom side for air intake and maximum 20mm
clearance from the wall by using spacers (field supply).
Caution
Make sure no short circuit of air is caused when placing the unit directly under a windowsill.
NOTE: The unit must be installed within a fully enclosed casing built by others. The casing shall include as minimum a removable
access panel, suction air grille and discharge air grille. These removable items shall prevent any access to the unit by its shape,
position and by the use of fixings that require the use of a tool for removal.
Positioning of holes for fastening to the wall
Unit of measurement = mm
Wall mounted type
Floor standing concealed type
F
F
1750
C
E
100
E
A
618
500
Suspension
bolt pitch
(Suspension bolt pitch)
Air outlet
740
1140
25 / 35 type
50 / 60 type
A
Model