FMCQ50~125A7VEB
Air conditioning system
4PW47629-1
Installation and operation manual
8
Summary of field settings
■
When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.
Control by 2 Remote Controllers (Controlling 1 indoor
unit by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB".
Main/sub changeover
1.
Insert a wedge-head screwdriver into the recess between the
upper and lower part of the remote controller and, working from
the 2 positions, pry off the upper part. (See figure 18)
(The remote controller PC board is attached to the upper part of
the remote controller.)
2.
Turn the main/sub changeover switch on one of the two remote
controller PC boards to "S". (See figure 19)
(Leave the switch of the other remote controller set to "M".)
Computerised control (forced off and on/off operation)
1.
Wire specifications and how to perform wiring.
•
Connect input from outside to terminals T1 and T2 of the terminal
block (remote controller to transmission wiring).
See figure 17.
2.
Actuation
•
The following table explains "forced off" and "on/off operations" in
response to input A.
3.
How to select forced off and on/off operation
•
Turn the power on and then use the remote controller to select
operation.
•
Set the remote controller to the field set mode. For details, refer to
the chapter "How to set in the field", in the remote controller
manual.
•
When in the field set mode, select mode No. 12, then set the first
code (switch) No. to "1". Then set second code (position) No. to
"01" for forced off and to "02" for on/off operation. (forced off at
factory set.) (See figure 16)
Centralized control
For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.
Mode
No.
(Note 1)
First
code
No.
Description of setting
Second code No. (Note 2)
01
02
03
04
10
(20)
0
Filter contamination
- Heavy/Light
= Setting to define
time between 2 filter
cleaning display
indications. (When
contamination is
high, setting can be
changed to half the
time inbetween 2
filter cleaning
display indications.)
Long-life
filter
Light ±2,500 hrs.
Hea
vy
±1,250 hrs.
–
–
2
Thermostat sensor selection
Use both the
unit sensor (or
remote sensor if
installed) AND
the remote
controller
sensor.
(See note 5+6)
Use unit sensor
only (or remote
sensor if
installed).
(See note 5+6)
Use remote
controller
sensor only.
(See note 5+6)
—
3
Setting for display of time
between 2 filter cleaning display
indications
Display
Do not display
—
—
5
Information to I-manager,
I-touch controller
Only unit sensor
value (or remote
sensor value if
installed).
Sensor value as
set by 10-2-0X
or 10-6-0X.
—
—
6
Thermostat sensor in group
control
Use unit sensor
only (or remote
sensor if
installed).
(See note 6)
Use both the
unit senor (or
remote sensor if
installed) AND
the remote
controller
sensor. (See
note 4+5+6)
—
—
12
(22)
0
Output signal X1-X2 of the
optional KRP1B PCB kit
Thermostat-on +
compressor run
—
Operation
Mal-
function
1
ON/OFF input from outside
(T1/T2 input) = Setting when
forced ON/OFF is to be
operated from outside.
Forced OFF
ON/OFF
operation
—
—
2
Thermostat differential
changeover = Setting when
remote sensor is used.
1°C
0.5°C
—
—
3
Fan setting during thermostat
OFF at heating operation
LL
Set speed
OFF
(See note 3)
—
4
Differential automatic
changeover
0°C
1°C
2°C
3°C
(See
note 7)
5
Auto-restart after power failure
Disabled
Enabled
—
—
13
(23)
0
Setting for air outlet
velocity
This setting is to be
changed in function
of ceiling height.
other
models
≤
2.7 m
>2.7
≤
3.0 m
>3.0
≤
3.5 m
—
FMCQ125
only
≤
3.2 m
>3.2
≤
3.6 m
>3.6
≤
4.2 m
—
1
Selection for air flow direction
This setting is to be changed
when blocking pad optional kit
is used.
4-way flow
3-way flow
2-way flow
—
4
Airflow direction range setting
This setting is to be changed
when range of swing flap
movement needs to be
changed.
Upper
Medium
Lower
—
Note 1 : Setting is carried out in the group mode, however, if the mode number inside parentheses is selected,
indoor units can also be set individually.
Note 2 : Factory settings of the Second code No. are marked in grey backgrounds.
Note 3 : Only use in combination with optional remote sensor or when setting 10-2-03 is used.
Note 4 : If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.
Note 5 : If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01,
10-2-02 or 10-2-03 have priority.
Note 6 : If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have priority.
Note 7 : More settings for Differential automatic change over temperatures are:
Second code No.
05
4°C
06
5°C
07
6°C
08
7°C
1
Remote controller PC board
2
Factory setting
3
Only one remote controller needs to be changed
Wire specification
Sheathed vinyl cord or cable (2 wire)
Gauge
0.75-1.25 mm
2
Length
Max. 100 m
External terminal
Contact that can ensure the minimum applicable load
of 15 V DC, 1 mA
1
Input A
Forced off
on/off operation
Input "on" stops operation
input off
➜
on: turns on the unit
(impossible by remote controllers)
Input "off" enables control
input on
➜
off: turns off the unit
(by remote controller)
1
Second code No.
2
Mode No.
3
First code No.
4
Field set mode
1O_IM+OM_4PW47629-1.book Page 8 Wednesday, July 16, 2008 11:04 AM