69
Service & Maintenance
Service & Maintenance
Disconnect from main supply before servicing the air conditioner.
The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly
checked and the following items should be given due attention.
•
•
Components
Maintenance Procedures
Period
Air Filter
(Indoor Unit)
1. Remove any dust adhering to the
fi
lter by using a vacuum cleaner
or wash in lukewarm water (below 40°C) with a neutral cleaning
detergent.
2. Rinse the
fi
lter well and dry before placing it back onto the unit.
3. Note: Never use gasoline, volatile substances or chemicals to
clean the
fi
lter.
At least once every 2
weeks.
More frequently if
necessary.
Indoor Unit
1. Clean any dirt or dust on the grille or panel by wiping it with a
soft cloth soaked in lukewarm water (below 40°C) and a neutral
detergent solution.
2. Note: Never use gasoline, volatile substances or chemicals to
clean the indoor unit.
At least once every 2
weeks.
More frequently if
necessary.
Condense Drain
Pan & Pipe
1. Check the cleanliness and clean it if necessary.
2. Check the condensate water
fl
ow.
Every 3 months.
Indoor Fan
Check if there is any abnormal noise.
If necessary.
Indoor / Outdoor
Coil
1. Check and remove the dirt between the
fi
ns.
2. Check and remove any obstacles which hinder air
fl
ow through
the indoor or outdoor.
Every month.
Power Supply
1. Check the running current and voltage for indoor and outdoor
unit.
2. Check the electrical wiring and tighten the wire onto the
terminal block if necessary.
Every 2 months.
Every year.
Compressor
No maintenance needed if refrigerant circuit remains sealed. How-
ever, check for refrigerant leak at joint and
fi
tting.
Every 6 months.
Don’t touch the metal parts of the indoor unit. It may cause an injury.
When removing or attaching the front panel, use a robust and stable stool and watch your steps carefully.
When removing or attaching the front panel, support the panel securely with hand to prevent from it falling.
For cleansing, do no use hot water above 40°C, benzene, gasoline, thinner, nor other volatile oils, polishing
compound, scrubbing brushes, nor other hand stuff.
After cleaning, make sure that the front panel is securely
fi
xed.
•
•
•
•
•
DAIKIN_FL(Y).indb 69
DAIKIN_FL(Y).indb 69
9/27/2012 12:13:28 PM
9/27/2012 12:13:28 PM
Summary of Contents for FL15EXV1
Page 2: ......
Page 58: ...55 Wiring Diagrams Indoor Unit Model FL35EXV1 Outdoor Unit Model R35DXV1...
Page 59: ...56 Wiring Diagrams Indoor Unit Model FL40EXV1 Outdoor Unit Model R40DXV1...
Page 63: ...60 Wiring Diagrams Heatpump Indoor Unit Model FLY15EXV1 Outdoor Unit Model RY15CXV1...
Page 64: ...61 Wiring Diagrams Indoor Unit Model FLY20 25EXV1 Outdoor Unit Model RY18 20 25CXV1...
Page 66: ...63 Wiring Diagrams Indoor Unit Model FLY28EXV1 Outdoor Unit Model RY30DXV1...
Page 67: ...64 Wiring Diagrams Indoor Unit Model FLY35EXV1 Outdoor Unit Model RY35DXV1...
Page 68: ...65 Wiring Diagrams Indoor Unit Model FLY40EXV1 Outdoor Unit Model RY40DXV1...
Page 69: ...66 Wiring Diagrams Indoor Unit Model FLY40EXV1 Outdoor Unit Model RY40DXY1...
Page 78: ......