6

4. Fix the air filter.

Align the two hanger brackets and push the two clips in their
place (pull the cloth if necessary, rear (5), bottom suction(6)).
Confirm that four hangers are fixed.

5. Shut the air inlet grille. (Only for bottom suction.(7))
6. After turning on the power, press FILTER SIGN RESET button.

The “TIME TO CLEAN AIR FILTER” display is turned off.

For FDY-units 

(Refer to figure 13)

1. Remove the screws from the bottom of the filter frame and

remove the filter frame downwards.

2. Clean the air filter. (Refer to figure 10. 

 air flow direction over

filter.)
Use compressed air (C) for blowing dust particles of the filter.
When the air filter is very dirty, use soft brush and neutral
detergent or wash with hot (30-40

°

C) water if needed (B). Do not

rub or wring.

3. Remove water and dry in the shade.
4. Fix the air filter. Put the air filter frame back in its position and fix

firmly with the screws.

How to clean the suction grille 

(for FH(Y)C only, refer to figure 11)

1. Open the suction grill.

Push both knobs simultaneously and carefully lower the grille (1).
(Identical procedure for closing.)

2. Detach the suction grill

Open the suction grill 45 degrees (6) and lift it upward (7).

3. Detach the air filter.

Refer to “HOW TO CLEAN THE AIR FILTER”.

4. Clean the suction grille.

Wash with a soft bristle brush and neutral detergent or water,
and dry thoroughly.

NOTE 

When the suction grill is very dirty, use a typical kitchen cleaner
and let it sit for about 10 minutes. Than, wash it with water.

5. Reattach the suction grill (7)(6)

See item n

°

  2.

6. Close the suction grill (1)

See item n

°

 1.

H

OW

 

TO

 

CLEAN

 

AIR

 

OUTLET

 

AND

 

OUTSIDE

 

PANELS

• Clean with soft cloth.
• When it is difficult to remove stains, use water or neutral

detergent.

• When the blade is extremely contaminated, remove it as below

and clean or exchange it. (for FH(Y)C only)
(Blade for exchange is optional.)

NOTE:

• Do not use gasoline, benzene, thinner, polishing powder, liquid

insecticide. It may cause discoloring or warping.

• Do not let the indoor unit get wet. It may cause an electric shock

or a fire.

S

TART

-

UP

 

AFTER

 

A

 

LONG

 

STOP

Confirm the following.

• Check that the air inlet and outlet are not blocked.

Remove any obstacle.

• Check if the earth is connected.

Clean the air filter and outside panels.

• After cleaning the air filter, make sure to attach it.

Turn on the main power supply switch.

• The control panel display lights when the power is turned on.
• To protect the unit, turn on the main power switch at least

6 hours before operation.

W

HAT

 

TO

 

DO

 

WHEN

 

STOPPING

 

THE

 

SYSTEM

 

FOR

 

A

 

LONG

PERIOD

Turn on FAN OPERATION for a half day and dry the unit.

• Refer to “OPERATION PROCEDURE, Fan operation”.

Cut off the power supply.

• When the main power switch is turned on, some wattage is being

consumed even if the system is not operating.

• The remote controller display is turned off when the main power

switch is turned off.

D

ISPOSAL

 

REQUIREMENTS

Dismantling of the unit, treatment of the refrigerant, oil and eventual
other parts, should be done in accordance with the relevant local
and national regulations.

Summary of Contents for FHB35FK7V1

Page 1: ...HYC45BZ7V1 FHYCP35B7V1 FHYCP45B7V1 FHYCP60B7V1 FHYCP71B7V1 FHYCP100B7V1 FHYCP125B7V1 FDYP125B7V1 FDYP200B7V1 FDYP250B7V1 FHB35FK7V1 FHB45FK7V1 FHB60FK7V1 FHYB35FK7V1 FHYB45FK7V1 FHYB60FK7V1 FHYB71FK7V...

Page 2: ...18 35 14 24 18 33 12 24 18 35 12 25 18 35 14 28 80 80 5 46 5 46 15 46 0 46 C 15 27 15 24 CDB CDB CDB CWB CDB CWB 9 21 10 15 5 9 21 10 15 5 RY35 45 60 RY P 71 100 125 RY P 200 250 C C C R22 R407C 15 43...

Page 3: ...10 11 12 13 A B C 1 2 3 4 5 6 7 1 7 2 3 4 5 6 2 1 1...

Page 4: ...ss the button again and the system will stop 2 OPERATION LAMP RED The lamp lights up during operation 3 DISPLAY UNDER CENTRALIZED CONTROL When this display shows the system is UNDER CENTRALIZED CONTRO...

Page 5: ...ference in the picture or sound OPERATION PROCEDURE Warning If a function that is not available is selected the message NOT AVAILABLE will appear Operating procedure varies with heat pump type and str...

Page 6: ...e display Up and down adjustment Operation mode Operation conditions Cooling When room temperature is lower than the set temperature When operating continuously at horizontal air flow direction Heatin...

Page 7: ...em does not restart immediately when the TEMPERATURE SETTING button is returned to its former position after pushing It does not restart immediately because one of its safety devices actuates to preve...

Page 8: ...is very dirty use soft brush and neutral detergent Remove water and dry in the shade TROUBLE SHOOTING If one of the following malfunctions occurs take the measures shown below and contact your Daikin...

Page 9: ...ner and let it sit for about 10 minutes Than wash it with water 5 Reattach the suction grill 7 6 See item n 2 6 Close the suction grill 1 See item n 1 HOW TO CLEAN AIR OUTLET AND OUTSIDE PANELS Clean...

Page 10: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW10622 1...

Reviews: