![background image](http://html1.mh-extra.com/html/daikin/ffrn25cxv1/ffrn25cxv1_technical-manual_3292825028.webp)
25
Engineering & Physical Data
MODEL
INDOOR
FCQN100EXV1
OUTDOOR
RQ90DXV1
RQ100DXV1
RQ100DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE
NC
OPEN
kPa / psi
4140 / 600.46
CLOSE
kPa / psi
3310 / 480.07
LOW PRESSURE
SWITCH
TYPE
NC
OPEN
kPa / psi
48 / 6.96
CLOSE
kPa / psi
152 / 22.05
PHASE SEQUENCER
N/A
YES
DISC. THERMOSTAT SETTING
°C / F
N/A
130 / 266
MODEL
INDOOR
FCQN125EXV1
OUTDOOR
RQ125DXY1
SAFETY
DEVICE
HIGH PRESSURE
SWITCH
TYPE
NC
OPEN
kPa / psi
4140 / 600.46
CLOSE
kPa / psi
3310 / 480.07
LOW PRESSURE
SWITCH
TYPE
NC
OPEN
kPa / psi
48 / 6.96
CLOSE
kPa / psi
152 / 22.05
PHASE SEQUENCER
YES
DISC. THERMOSTAT SETTING
°C / F
130 / 266
ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
DAIKIN_FFRN.indb 25
DAIKIN_FFRN.indb 25
12/27/2012 9:28:10 AM
12/27/2012 9:28:10 AM